Alula RE305 Скачать руководство пользователя страница 1

The Temperature Sensor 

is used to detect freeze and 

overheat conditions. The sensor will alarm when the 

temperature trip points are reached.

Features

•  Indicates freeze and overheat warnings

•  Industry-leading wireless range and battery life

•  Secure encrypted wireless transmissions

•  5-year warranty

Enroll

 the freeze input (ID ending in 0) by placing the 

panel into wireless enrollment mode and then sending 

an enrollment signal from the sensor.   

Options for sending an Enrollment Signal

•  Remove the battery tab and cover to trip 

tamper

.

Overheat inputs and reed zones must be enabled to 

function. Activate only as needed in order to extend 

battery life.  

To activate and enroll an overheat input (ID ending in 

1):

• Remove magnet from reed switch 

• Hold down tamper and install battery

Install 

by mounting the sensor in the desired location 

using two #4 or #6 screws. An optional cover-securing 

screw is included.  Alternatively, the sensor can also be 
installed using 3M™ VHB™ tape.

Freeze 

or

 Heat 

alarms

 

are transmitted when the 

temperature trip points are reached.

Temperature Trip Points

•  Heat alarms when over 100°F (38°C)

•  Heat restores when under 97°F (36°C)

•  Freeze alarms when under 45°F (7°C)

•  Freeze restores when over 48°F (9°C)

Use the panel installation guide to verify proper system setup.

Mounting Screw Holes

RE305 Temperature Sensor

DSC

®

 Compatible

IN

STALL

G

U I D E

I

Cover-Securing Screw Hole

Resolution Compatibles