2. Technical Description
19
Ethernet Interfaces
NET 1 to NET 6
HX3040
Connector
RJ45 shielded female
Auto crossover
Yes
Maximum cable length
100 m
Cable type
UTP or ScTP, category 5
Baud rate
10/100 Mbps
Physical layer
10/100Base-TX
Data link layer
LLC (logic link control)
Network layer
IP (internet protocol)
Transport layer
TCP (transmission control protocol)
UDP (user datagram protocol)
Application layer
MODBUS TCP Client / Server
MODBUS RTU via TCP Client / Server
DNP3 Client / Server
GOOSE Protocol (sending and receiving messages)
MMS Server
HTTP (web server)
MasterTool Xtorm programming protocol (only NET 1)
SNTP (Clock synchronism)
Table 2-7. Ethernet Interface NET 1
Note:
MasterTool Xtorm Programming protocol:
In cases where NET 1 is set as redundant, NET 2 can
also be used to the MasterTool Xtorm programming protocol.
IRIG-B
HX3040
Connector type
Removable terminal connector with 4 terminals (HX9405)
Maximum cable length
5 m
Wire gauge
0.5 mm²
Input and output level
TTL
Input impedance
> 100 kΩ
Delay between input and output
< 10 ns
Maximum output current
10 mA
Maximum output load
500 Ω
Protection against short circuit
Yes
Voltage levels
0 to 1.5 Vdc to logic level 0
3.5 to 5 Vdc to logic level 1
Table 2-8. IRIG-B Interface
Note:
Maximum output load:
The resulting total load of all devices connected to the output should not
exceed this value. There is no maximum predefined limit of devices. The value should be calculated
regarding the minimum input impedance of each device connected to the IRIG-B Xtorm output.