T2PXK7F8V T2PXK7F8V Installation Guide
Overview:
Altronix T2PXK7F8V Trove Paxton kit is pre-assembled and consists of Trove2PX2 enclosure/backplane with factory installed Altronix power
supply/charger and sub-assemblies. T2PXK7F8 kit also accommodates up to eight (8) Paxton Net2 Plus modules for up to eight (8) doors in a
single enclosure.
Configuration Chart:
Altronix
Model Number
220VAC 60Hz Input Current (A)
Power Supply Board Input Fuse Rating
Power Supply Board Battery Fuse Rating
Maximum Supply
Current for Main and
Aux. Outputs on
Power Supply board
and ACM8 Access Power
Controller’s outputs
Nominal DC
Output Voltage
Fail-Safe/Fail-Secure or Dry Form “C” Outputs
Additional Fused Outputs
ACM8 Board Input Fuse Rating
ACM8 Board Output Fuse Rating
PDS8 Board Input Fuse Rating
PDS8 Board Output Fuse Rating
[DC]
[Aux]
Output
Range
(VDC)
Output
Range
(VDC)
T2PXK7F8V
2.7 6.3A/
250V
15A/
32V
24VDC @ 9.7A
20.17-
26.4
20.28-
26.4
8
8
10A/
250V
2.5A/
250V
10A/
32V
3A/
32V
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction.
Product is intended for indoor use only.
1. Remove backplane from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws in the
wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws, level and secure. Mark the position
of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes
over the three upper screws. Install the three lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location,
opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure, approximately
2” from the right side
(Fig. 1, pg. 2)
. Connect tamper switch wiring to the Access Control Panel
input or the appropriate UL Listed reporting device.
To activate alarm signal open the door of the enclosure.
4. Mount Paxton Net2 Plus modules to TPX2 backplane, refer to
page 3
.
5. Refer to the
eFlow Power Supply/Charger Installation Guide
for eFlow104NBV and corresponding
Sub-Assembly Installation Guides
for the following models: ACM8, PDS8 and VR6 for
further installation instructions.
Hardware:
Fig. 1
Tamper Switch
(included)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Nylon Spacer | 5/16” Pan Head Screw | Lock Nut