T2PXK7F8V T2PXK7F8V Installation Guide

Overview:

Altronix T2PXK7F8V Trove Paxton kit is pre-assembled and consists of Trove2PX2 enclosure/backplane with factory installed Altronix power 

supply/charger and sub-assemblies. T2PXK7F8 kit also accommodates up to eight (8) Paxton Net2 Plus modules for up to eight (8) doors in a 

single enclosure.

Configuration Chart:

Altronix

Model Number

220VAC 60Hz Input Current (A)

Power Supply Board Input Fuse Rating

Power Supply Board Battery Fuse Rating

Maximum Supply

Current for Main and 

Aux. Outputs on 

Power Supply board 

and ACM8 Access Power 

Controller’s outputs

Nominal DC 

Output Voltage

Fail-Safe/Fail-Secure  or Dry Form “C”  Outputs

Additional Fused  Outputs

ACM8 Board  Input Fuse Rating

ACM8 Board Output Fuse Rating

PDS8 Board Input Fuse Rating

PDS8 Board Output Fuse Rating

[DC]

[Aux]

Output 

Range 

(VDC)

Output 

Range 

(VDC)

T2PXK7F8V

2.7 6.3A/

250V

15A/

32V

24VDC @ 9.7A

20.17-

26.4

20.28-

26.4

8

8

10A/

250V

2.5A/

250V

10A/

32V

3A/

32V

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. 

Product is intended for indoor use only. 

1.  Remove backplane from enclosure. Do not discard hardware.

2.  Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws in the 

 

wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws, level and secure. Mark the position 

 

of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes 

 

over the three upper screws. Install the three lower screws and make sure to tighten all screws.

3.  Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location, 

 

opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure, approximately 

 

2” from the right side 

(Fig. 1, pg. 2)

. Connect tamper switch wiring to the Access Control Panel

 

input or the appropriate UL Listed reporting device. 

 

To activate alarm signal open the door of the enclosure.

4.  Mount Paxton Net2 Plus modules to TPX2 backplane, refer to

 page 3

.

5.  Refer to the 

eFlow Power Supply/Charger Installation Guide

 for eFlow104NBV and corresponding 

 

Sub-Assembly Installation Guides

 for the following models: ACM8, PDS8 and VR6 for 

 

further installation instructions. 

Hardware:

Fig. 1

Tamper Switch

(included)

To Access Control Panel or

UL Listed Reporting Device

Edge of

Enclosure

Enclosure

Nylon Spacer |            5/16” Pan Head Screw |         Lock Nut