background image

 

SMP1012Xseries 

- 1 - 

Overview:

These units will convert a 115VAC 50/60Hz input into a regulated 12VDC output at up to 10 amp continuous supply 
current (see specifications).

SMP1012X Series Power Supply Configuration Reference Chart:

Altronix 

Model Number

Accessory 

Power

Distribution

Module(s)

Number of 

Outputs

Fused Outputs

PTC Outputs

Output Rating  (amp) per Output

Supervised

115VAC

 

50/60Hz Input

 

Current (amp)

12VDC Total

 

Output Current

 

(amp)

SMP10C12X

-

1

-

-

10

-

1.45

10

SMP10C12XX*

-

1

-

-

10

-

1.45

10

SMP10PMC12X

-

1

-

-

10

x

1.45

10

SMP10PMC12XX*

-

1

-

-

10

x

1.45

10

SMP10PM12P4

PD4

4

-

3.5

x

1.45

10

SMP10PM12P4CB

PD4CB

4

-

x

2.5

x

1.45

10

SMP10PM12P8

PD8

8

x

-

3.5

x

1.45

10

SMP10PM12P8CB

PD8CB

8

-

x

2.5

x

1.45

10

SMP10PM12P16

PD16W

16

x

-

3.5

x

1.45

10

SMP10PM12P16CB

PD16WCB

16

-

x

2.5

1.45

10

*Refer to Enclosure Dimensions on pg.7 for enclosure size.

Specifications:

Installation Instructions:

Wiring methods should be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI and with all local 
codes and authorities having jurisdiction.  Product is intended for indoor use only. 
1.  Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
  enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s    
  upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the    
  enclosure. Drill the lower holes and install three fasteners. Place the enclosure’s upper keyholes over the two
  upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 6-7).
  Secure enclosure to earth ground. 
2.  Connect AC power to the terminals marked [L & N].
  Use 18 AWG or larger for all power connections (Battery, DC output).
3.  Measure output voltage before connecting devices. This helps avoiding potential damage.

Battery Backup:

•  Built-in charger for sealed lead acid or gel type batteries. 
•  Maximum charge current 0.7 amp.
•  Filtered and electronically regulated outputs.
•  Automatic switch over to stand-by battery when
  AC fails (zero voltage drop).

Features:

•  AC input and DC output LED indicators.

Features 

(cont’d)

:

•  Short circuit and thermal overload protection.
•  Complete with power supply, power distribution module 
  (when applicable), enclosure, cam lock & battery leads. 
•  Power ON/OFF switch.

Supervised models only:

•  AC fail supervision (form “C” contacts). 
•  Low battery supervision (form “C” contacts).

SMP1012X Series - Installation Guide

Содержание SMP1012X Series

Страница 1: ...wall to line up with the top two keyholes in the enclosure Install two upper fasteners and screws in the wall with the screw heads protruding Place the enclosure s upper keyholes over the two upper s...

Страница 2: ...leads included Note When batteries are not used a loss of AC will result in the loss of output voltage 6 Connect appropriate signaling notification devices to the AC Fail Low Bat supervisory relay out...

Страница 3: ...d replace fuse with the same type and rating 15A 32V Power Supply Board L G N OFF ON LOW BAT NC C NO NC C NO AC FAIL BAT DC AC DC 5A 250V 15A 12VDC Rechargeable Battery optional CAUTION Optional recha...

Страница 4: ...r Supply Board Red DC Green AC Power Supply Status ON ON Normal operating condition ON OFF Loss of AC Stand by battery supplying power OFF ON No DC output OFF OFF Loss of AC Discharged or no stand by...

Страница 5: ...act rating 1 amp 120VAC 28VDC Low Battery NC C NO Indicates low battery condition e g connect to alarm panel Relay normally energized when DC power is present Contact rating 1 amp 120VAC 28VDC Low bat...

Страница 6: ...3 5 x 13 x 3 25 342 9mm x 330 2mm x 82 55mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83...

Страница 7: ...127 0mm 1 5 38 1mm 2 0 50 8mm 2 0 50 8mm 1 75 44 45mm 1 75 44 45mm 4 5 114 3mm 1 25 31 75mm 4 5 114 3mm 1 25 31 75mm 1 25 31 75mm 1 25 31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23...

Страница 8: ...aphical errors Product specifications are subject to change without notice 140 58th Street Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 web site www altronix com e mail info altronix com...

Отзывы: