Rev. 111819
More than just power.
TM
Altronix Corp.
140 58th St. Brooklyn, NY
AL642ULADA
NAC Power Extender
Installation Guide
(see Application Guide for additional information)
Страница 1: ...Rev 111819 More than just power TM Altronix Corp 140 58th St Brooklyn NY AL642ULADA NAC Power Extender Installation Guide see Application Guide for additional information ...
Страница 2: ...t of Notification Appliances per NAC pg 6 Terminal Identification Table AL842LGK Logic Board pg 6 AL600ADA Power Supply Board pg 7 LED Diagnostics pg 7 Battery Calculation Worksheet pg 8 Hookup Diagram pg 9 Optional Hookups pg 10 Maintenance pg 10 Appendix A Compatible UL cUL Listed Devices for Synchronization A 1 Strobes Horns and Horn Strobes pg 11 Appendix B UL Listed Compatible Devices B 1 Rel...
Страница 3: ...ass B FACP inputs Two 2 NC dry contact trigger inputs Input Ratings INP1 and INP2 8 30VDC 6 5mA max from FACP 12V 6 5mA 24V 6 5mA from FACP Output Power limited outputs 24VDC voltage regulated power limited outputs 6 5A max total alarm current 2 5A max current per output Two auxiliary outputs rated at 1A each 1A continuous 1A AC disconnect Two 2 outputs may be paralleled for more power on an indic...
Страница 4: ...pg 4 Output Programming Selection Table pg 5 Sync Mode Selection Table pg 5 Terminal Identification Table pgs 6 7 LED Status Indication Table pg 7 1 Mount the unit in the desired location Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure Install two upper fasteners and screws in the wall with the screw heads protruding Place the enclosure s upper keyholes ov...
Страница 5: ... timing of the strobe allowing audible notification appliances horns and visual notification appliances strobes to be silenced deactivated at the same time Gentex Sync Mode Gentex is a registered trademark of Gentex Corporation 1 2 3 4 This mode is designed to work with the Gentex series of horns strobes and horn strobes to provide a means of synchronizing the Temporal coded horns synchronizing th...
Страница 6: ...cted to these regulated outputs see Application Guide pg 2 4 Each power limited output will supply 2 5A Two 2 outputs may be connected in parallel for a maximum NAC output capability of 4A Total supply current is 8A see note below Outputs are controlled by designated Input 1 IN1 or Input 2 IN2 Output Programming Selection Table pg 5 Maximum line loss or voltage drop tested with 2 5V Loop 1 Loop 2 ...
Страница 7: ...nds Low battery condition will report at approximately 21VDC Battery presence detection will report with in 180 seconds after battery remains undetected missing or removed A restored battery will report within 30 seconds LED Diagnostics AL600ADA Power Supply Board Red DC Green AC Power Supply Status ON ON Normal operating condition ON OFF Loss of AC Stand by battery is supplying power OFF ON No DC...
Страница 8: ...mA mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 6 5A 6500mA 0mA mA D Total alarm current mA mA E Total current ratings converted to amperes line D x 001 A A F Number of standby hours 24 for NFPA 72 Chapter 1 1 5 2 5 H G Multiply lines E and F Total stand by AH AH H Alarm sounding period in hours For example 5 minutes 0 0833 hours H I Multiply...
Страница 9: ... non power limited Line Input Fuse Ground Neutral Magnetic Door Holder Supervised Non Supervised Class E Power Limited Inputs 5A 250V Compatible Special Application Devices See Compatibility List Non Supervised Class E Non Supervised Class E Power Limited Common trouble output to Digital Communicator or Local Annunciator Dry output Contact Form C contacts Non Supervised Class E Connection to trigg...
Страница 10: ...ld connect to the host control panel for local annunciation of the trouble condition Note If common trouble input terminals marked C FAULT NC are not used these terminals must be shorted connect jumper to remain inactive For optional hookups see Fig 2a Maintenance Unit should be tested at least once a year for the proper operation as follows Output Voltage Test Under normal load conditions the DC ...
Страница 11: ... UL SPSCWVH P UL SRHK R UL P2RHK P UL PC2R P UL SCRH P UL SPSR UL SRK UL P2RHK R UL PC2RH UL SCRH SP UL SPSR P UL SRK P UL P2RK UL PC2RH P UL SCRHK UL SPSRH UL SRK R UL P2RK P UL PC2RH SP UL SCRK UL SPSRH P UL SW UL P2RK R UL PC2RHK UL SCW UL SPSRHK UL SW ALERT UL P2W UL PC2RK UL SCW CLR ALERT UL SPSRK UL SW CLR ALERT UL P2W P UL PC2W UL SCW P UL SPSRK P UL SW P UL P2W SP UL PC2W P UL SCW SP UL SP...
Страница 12: ...ECG24PWR W UL WSSPK24 15 75AWR AWW UL WSSPKA24 15 75PWW UL GECR24PWR W UL GES24 177WR UL WSSPKB24 15 75PWR UL GCSA24PCR W UL GES24 177WW UL WSSPKB24 15 75PWW UL GCSB24PCR W UL GES24 15 75WR UL WSSPKG24 15 75PWR UL GCSG24PCR W UL GES24 15 75WW UL WSSPKG24 15 75PWW UL GCSR24PCR W UL GEC24 177WR UL WSSPKR24 15 75PWR UL GCCA24PCR W UL GEC24 177WW UL WSSPKR24 15 75PWW UL Potter Amseco CM24CR UL CSL 122...
Страница 13: ...H90 24MCC FW UL cUL E90H 24MCCH FW UL cUL LHSW A UL cUL RSS 24MCWH FW UL cUL CH90 24MCCH FR UL cUL EET90 24MCCH FR UL cUL LHSW AL UL cUL RSSA 24MCC NW UL CH90 24MCCH FW UL cUL ET 1010 R UL LHSW N UL cUL RSSA 24MCCH NW UL E50 241575W FW UL cUL ET 1010 W UL LSPSTR UL cUL RSSB 24MCC NW UL E50 24MCWH FR UL cUL ET70 241575W FR UL cUL LSPSTR AL UL cUL RSSB 24MCCH NW UL E50 24MCWH FW UL cUL ET70 241575W ...
Страница 14: ...lists relays compatible with AL642ULADA AUX output and Outputs 1 8 when programmed as AUX Manufacturer Model Current mA Manufacturer Model Current mA System Sensor PR 1 15 System Sensor R 20T 40 PR 2 30 R 24T 40 PR 3 30 R 10E 23 EOLR 1 30 R 14E 23 R 10T 23 R 20E 40 R 14T 23 R 24E 40 ...
Страница 15: ...AL642ULADA 15 Notes ...
Страница 16: ...L642ULADA K18S MEMBER 6 0 152 4mm 1 5 38 1mm 2 5 63 5mm 1 0 25 4mm 2 75 69 9mm 2 75 69 9mm 4 5 114 3mm 4 5 114 3mm 14 5 368 3mm 1 0 25 4mm 1 5 38 1mm 8 5 215 9mm 18 0 457 2mm 18 0 457 2mm 18 0 457 2mm 1 25 31 75mm 1 25 31 75mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 2 5 63 5mm 2 5 63 5mm 14 5 368 3mm 14 5 368 3mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm Enclosure Dimensions 18 x...