background image

Overview:

Altronix AL600ULXD power supply/charger converts a 115VAC or 230VAC, 50/60Hz input into a non power-
limited 12VDC or 24VDC output (see specifications)

Specifications:

AL600ULXD

Power Supply/Charger

Agency Listings:

• 

UL 294*  Safety Access Control System Units,  

 

UL 1481  Power Supplies for Fire-Protective 

   

Signaling Systems.

• 

CE 

European Conformity.

Input:

•  115VAC, 60Hz, 1.9A or 230VAC, 60Hz 0.95A.

Output:

•  12VDC or 24VDC selectable output.
•   12VDC or 24VDC @ 6A supply current.
•  Filtered and electronically regulated output.
•  Short circuit and thermal overload protection.

Battery Backup:

•  Built-in charger for sealed lead acid or 
  gel type batteries.
•  Automatic switch over to stand-by battery 
  when AC fails.
•  Maximum charge current 0.7A.

Supervision:

•  AC fail supervision (form “C” contacts). 
•  Low battery supervision (form “C” contacts). 

Visual Indicators:

•  AC input and DC output LED indicators.

Features:

•  Low battery disconnect.
•   Unit is complete with transformers, power supply, 
  grey enclosure, and cam lock.
•  Battery leads included.

Enclosure Dimensions 

(H x W x D approx.)

:

  15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).
  Accommodates up to two 12VDC/12AH batteries.
 

AL600ULXD: Grey Enclosure.

 

AL600ULXDR: Red Enclosure.

*Access Control Performance Levels: Destructive Attack - I; Endurance - IV; Line Security - I; Stand-by Power - IV.

Power Supply Output Selection:

Output

Switch Position

12VDC

SW1 ON

24VDC

SW1 OFF

Stand-by Specifications:

Output

4 hr. of Stand-by and

5 min. of Alarm

24 hr. of Stand-by and

5 min. of Alarm

60 hr. of Stand-by and

5 min. of Alarm

12VDC / 40AH Battery

Stand-By = 6.0A

Alarm = 6.0A

Stand-By = 1.0A

Alarm = 6.0A

Stand-By = 300 mA

Alarm = 6.0A

24VDC / 12AH Battery

Stand-By = 200 mA

Alarm = 6.0A

24VAC / 40AH Battery

Stand-By = 6.0A

Alarm = 6.0A

Stand-By = 1.0A

Alarm = 6.0A

Stand-By = 300 mA

Alarm = 6.0A