Overview:
Altronix AL600ULXD power supply/charger converts a 115VAC or 230VAC, 50/60Hz input into a non power-
limited 12VDC or 24VDC output (see specifications).
Specifications:
AL600ULXD
Power Supply/Charger
Agency Listings:
•
UL 294* Safety Access Control System Units,
UL 1481 Power Supplies for Fire-Protective
Signaling Systems.
•
CE
European Conformity.
Input:
• 115VAC, 60Hz, 1.9A or 230VAC, 60Hz 0.95A.
Output:
• 12VDC or 24VDC selectable output.
• 12VDC or 24VDC @ 6A supply current.
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Automatic switch over to stand-by battery
when AC fails.
• Maximum charge current 0.7A.
Supervision:
• AC fail supervision (form “C” contacts).
• Low battery supervision (form “C” contacts).
Visual Indicators:
• AC input and DC output LED indicators.
Features:
• Low battery disconnect.
• Unit is complete with transformers, power supply,
grey enclosure, and cam lock.
• Battery leads included.
Enclosure Dimensions
(H x W x D approx.)
:
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).
Accommodates up to two 12VDC/12AH batteries.
AL600ULXD: Grey Enclosure.
AL600ULXDR: Red Enclosure.
*Access Control Performance Levels: Destructive Attack - I; Endurance - IV; Line Security - I; Stand-by Power - IV.
Power Supply Output Selection:
Output
Switch Position
12VDC
SW1 ON
24VDC
SW1 OFF
Stand-by Specifications:
Output
4 hr. of Stand-by and
5 min. of Alarm
24 hr. of Stand-by and
5 min. of Alarm
60 hr. of Stand-by and
5 min. of Alarm
12VDC / 40AH Battery
Stand-By = 6.0A
Alarm = 6.0A
Stand-By = 1.0A
Alarm = 6.0A
Stand-By = 300 mA
Alarm = 6.0A
24VDC / 12AH Battery
–
Stand-By = 200 mA
Alarm = 6.0A
–
24VAC / 40AH Battery
Stand-By = 6.0A
Alarm = 6.0A
Stand-By = 1.0A
Alarm = 6.0A
Stand-By = 300 mA
Alarm = 6.0A