AL6003X220

Triple Output Access Control Power Supply/Charger

Overview:

The AL6003X220 triple output access control power supply/charger is specifically designed for use with access control 
systems and accessories. The AL6003X220 converts a 220VAC 50/60Hz input into three individually PTC protected 
5VDC, 12VDC and 24VDC regulated outputs (see specifications). 

Specifications:

 

Stand-by Specifications

(current is specified on AL3XB input)

:

Output

4 hr. of Stand-by &

5 Minutes of Alarm

24 hr. of Stand-by &

5 Minutes of Alarm

60 hr. of Stand-by &

5 Minutes of Alarm

24VDC / 12AH Battery

--------

Stand-by = 200mA

Alarm = 6.0 amp

--------

24VDC / 40AH Battery

Stand-by = 6.0 amp

Alarm = 6.0 amp

Stand-by = 1.0 amp

Alarm = 6.0 amp

Stand-by = 300mA

Alarm = 6.0 amp

Installation Instructions:

The AL6003X220 should be installed in accordance with article 760 of The National Electrical Code or NFPA 72, as 
well as all applicable Local Codes.
1.  Mount the AL6003X220 in the desired location.
2.  Connect AC power to the two black and two white flying leads of the transformer. Secure green wire lead to 
  earth ground (Fig. 1). Use 18 AWG or larger for all power connections (Battery, DC output).
3.  Measure output voltage before connecting devices. This helps avoiding potential damage.
4.  Connect devices to be powered at 5VDC to the terminals marked [+ Out 3 - ].
5.  Connect devices to be powered at 12VDC to the terminals marked [+ Out 2 - ]. 
6.  Connect devices to be powered at 24VDC to the terminals marked [+ Out 1 - ].
7.  Connect two (2) 12V Stand-by batteries. 
 

Note: For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in

   the loss of output voltage. Batteries must be lead acid or gel type if used. Two (2) 12V Stand-by batteries 
  connected in series to terminals marked [+ BAT -- ] (Fig. 1, pg. 3).
8.  It is required to connect supervisory trouble reporting devices to outputs marked [AC FAIL, LOW BAT] (Fig. 1, pg. 3)
  Use 22 AWG to 18 AWG for AC Fail & Low Battery reporting. AC Failure will report in 5 minutes.

Input:

•  Input 220VAC (working range 198VAC - 256VAC),    
  50/60Hz, 1.25 amp.

Output:

•  1.75 amp continuous supply current @ 5VDC.
•  1.75 amp continuous supply current @ 12VDC.  
•  3 amp continuous supply current @ 24VDC.
•  Filtered and electronically regulated outputs, 100mV     
  peak output voltage ripple.

Battery Backup:

•  Built-in charger for sealed lead acid or gel type batteries.
•  Automatic switch over to stand-by battery when AC fails.
•  Maximum charge current 0.7 amp.

Battery Backup 

(cont’d)

:

•  Zero voltage drop when switched over to 
  battery backup.

Supervision:

•  AC fail supervision (form “C” contacts). 
•  Low battery supervision (form “C” contacts). 

Additional Features:

•  Thermal and short circuit protection with auto reset. 
•  Power supply is complete with enclosure, cam lock, and  
  battery leads.

Enclosure Dimensions 

(H x W x D approximate)

:

15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)

Содержание AL6003X220

Страница 1: ...Connect devices to be powered at 12VDC to the terminals marked Out 2 6 Connect devices to be powered at 24VDC to the terminals marked Out 1 7 Connect two 2 12V Stand by batteries Note For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of output voltage Batteries must be lead acid or gel type if used Two 2 12V Stand by batteries c...

Страница 2: ...ied voltage at the battery terminals and at the board terminals marked BAT to ensure that there is no break in the battery connection wires Note Maximum charge current under discharge is 0 7 amp Note Expected battery life is 5 years however it is recommended changing batteries in 4 years or less if necessary DC AC AC AC BAT OPEN 24V SW1 CLOSED 12V DC RL2 RL3 RLY1 PTC2 AC TROUBLE DELAY OPTION J2 IC...

Страница 3: ...ut AC Fail NC C NO Indicates loss of AC power e g connect to audible device or alarm panel Relay normally energized when AC power is present Contact rating 1 amp 28VDC Bat Fail NC C NO Indicates low battery condition e g connect to alarm panel Relay normally energized when DC power is present Contact rating 1 amp 28VDC BAT Stand by battery connections Maximum charge current 0 7 amp AL3XB Power Out...

Страница 4: ...07 G02M MEMBER 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 1 5 38 1mm 2 0 50 8mm 2 0 50 8mm 1 75 44 45mm 1 75 44 45mm 4 5 114 3mm 1 25 31 75mm 4 5 114 3mm 1 25 31 75mm 1 25 31 75mm 1 25 31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23 114mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm 12 23 310 64mm 4 615 117 22mm 1 5 38 1mm 1 5 38 1mm 4 615 ...

Отзывы: