Power Supply Voltage Output Selections:

Stand-by Specifications:

Installation Instructions:

The AL400ULXB should be installed in accordance with article 760 of The National Electrical Code or NFPA 72 
as well as all applicable Local Codes.
1. Mount the AL400ULXB in desired location/enclosure.
2. Set the AL400ULXB to the desired DC output voltage by setting SW1 

(Fig. 2, pg. 2)

to the appropriate position

(

refer to Power Supply Voltage Output Selections chart

).

3. Connect AC power (115VAC 50/60Hz) to terminals marked [L, G, N] 

(Fig. 2, pg. 2)

. Use 18 AWG or larger for all 

power connections (Battery, DC output, AC input). Use 22 AWG to 18 AWG for power limited circuits 
(AC Fail/Low Battery reporting).

Keep power limited wiring separate from non-power limited wiring (115VAC / 60Hz Input, Battery Wires).
Minimum .25” spacing must be provided.

4. Connect devices to be powered to terminals marked [ – DC +] 

(Fig. 2, pg. 2)

.

5. Measure output voltage before connecting devices. This helps avoid potential damage.
6. For Access Control applications, batteries are optional. When batteries are not used a loss of AC will result in the 

loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.
Connect battery to terminals marked  [+ BAT – ] 

(Fig. 2, pg. 2)

. Use two (2) 12VDC batteries connected in series for 

24VDC operation (battery leads included).

AL400ULXB
UL Recognized Power Supply/Charger

Rev. 120600

Agency Listings:

• UL Recognized component for: Access Control

System Units (UL 294), Power Supplies for use with 
Burglar-Alarm Systems (UL 603), Power Supplies 
for Fire Protective Signaling Systems (UL 1481).

Input Rating:

• Input 115VAC 50/60Hz, 1.45 amp.

Output Rating:

• Class 2 Rated power limited output.
• 12VDC or 24VDC selectable output. 
• 12VDC @ 4 amp or 24VDC @ 3 amp continuous

supply current. 

• Filtered and electronically regulated output.

Battery Backup:

• Built-in charger for sealed lead acid or gel type batteries. 
• Maximum charge current .7 amp.
• Automatic switch over to stand-by battery when AC fails.
• Zero voltage drop when switched over to battery backup.

Visual Indicators:

• AC input and DC output LED indicators.

Supervision:

• AC fail supervision (form "C" contacts). 
• Low battery and battery presence supervision

(form "C" contacts).

Additional Features:

• Short circuit and thermal overload protection.

Board Dimensions (approximate):

4.6”W x 7.5”L x 2.7”H

OPEN SWITCH

CLOSED SWITCH

Switch Detail

---

D

C

+

L

G

N

PTC3

NC C NO NC C NO

+

B

AT

---

DC

24V - OPEN

12V - CLOSED

AC FAIL

RL2

BAT FAIL

RL1

RL3

J1

SW1

3

.5

A

2

5

0

V

Fuse

Cover

AC

De

la

y

Fig. 1

Overview:

The AL400ULXB is a power supply/charger that converts a 115VAC 50/60Hz input, into a Class 2 Rated power limited
12VDC or 24VDC output (see specifications).

Specifications:

Output

Switch Position

12VDC

SW1 - CLOSED 

(Fig. 1, on right)

24VDC

SW1 - OPEN 

(Fig. 1, on right)

Output

4 hr. of Stand-by &

5 Minutes of Alarm

24 hr. of Stand-by &

5 Minutes of Alarm

60 hr. of Stand-by &

5 Minutes of Alarm

12VDC / 40AH Battery

Stand-by = 4.0 amp

Alarm = 4.0 amp

Stand-by = 1.0 amp

Alarm = 4.0 amp

Stand-by = 300mA

Alarm = 4.0 amp

24VDC / 12AH Battery

--------

Stand-by = 200mA

Alarm = 3.0 amp

--------

24VDC / 40AH Battery

Stand-by = 3.0 amp

Alarm = 3.0 amp

Stand-by = 1.0 amp

Alarm = 3.0 amp

Stand-by = 300mA

Alarm = 3.0 amp