background image

Agency Listings:

•  UL Recognized component for Access Control
  System Units (UL 294).

Input:

•  Input 115VAC / 60Hz, 2.6A.

Output:

•  12VDC output. 
•  10A continuous supply current. 
•  Filtered and electronically regulated output.

Fuse Ratings:

•  Input Fuse: 250VAC, 5A
•  Output Fuse: 32VDC, 15A

Battery Backup:

•  Built-in charger for sealed lead acid or gel type batteries. 
•  Maximum charge current 0.7A.
•  Automatic switch over to stand-by battery
  when AC fails.
•  Zero voltage drop when switched over to battery backup.

Visual Indicators:

•  AC input and DC output LED indicators.

Supervision:

•  AC fail supervision (form “C” contacts). 
•  Battery presence supervision (form “C” contacts).

Additional Features:

•  Short circuit and thermal overload protection.

Board Dimensions 

(W x L x H approximate)

:

   4.5” x 7.25” x 1.75” (114.3mm x 184.15mm x 44.45mm)

Stand-by Specifications:

When 12VDC/12AH battery is used, the unit provides 30 minutes of backup @ 10A.

Installation Instructions:

The AL1012ULXB must be installed in accordance with article 760 of the National Electrical Code, ANSI/NFPA 70 and 
all applicable Local Codes.
1.  Mount the AL1012ULXB in the desired location/enclosure.
2.  Connect unswitched AC power (115VAC / 60Hz) to the terminals marked [L, G, N] (Fig. 1, pg. 2). Use 18 AWG or
 

larger for all power connections (Battery, AC input, DC output). Use 22 AWG to 18 AWG for power-limited circuits 

 

(AC Fail/Low Battery reporting). 

 

Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, Battery Wires).    

 

Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. 

 

There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.

3.  Measure output voltage before connecting devices. This helps avoiding potential damage.
4.  Connect devices to be powered to the terminals marked [+ DC –] (Fig. 1, pg. 2).
5.  For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the  
 

loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect  

 

battery to the terminals marked [+ BAT – ] (Fig. 1, pg. 2).

6.  If it is required to connect appropriate signaling notification devices to [AC FAIL] and [BAT FAIL] supervisory 
 

relay outputs (Fig. 1), use 22AWG to 18AWG wires.

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test:  Under normal load conditions, the DC output voltage should be checked for proper
 

voltage level (13.2volts).

Battery Test: 

Under normal load conditions check that the battery is fully charged, check specified

 

voltage both at battery terminal and at the board terminals marked [+ BAT -] to ensure there

 

is no break in the battery connection wires.

Note: 

Maximum charging current under discharge is 0.7A.

Note: 

Expected battery life is 5 years; however, it is recommended changing batteries in 4 years

 

or less if needed.

AL1012ULXB

UL Recognized Power Supply/Charger

Overview:

The AL1012ULXB power supply converts a 115VAC / 60Hz input into a 12VDC non power-limited output 
(see specifications).

Specifications:

Отзывы: