INSTALLATION INSTRUCTIONS

DIGITAL ANNUNCIATOR

DD-40NTV-O, DD-40NTV-U

DEVIATION FROM THESE INSTRUCTIONS MAY LEAD TO IMPROPER OP-

ERATION OF THE MACHINE WHICH COULD CAUSE PERSONAL INJURY 

TO OPERATORS OR OTHER NEARBY PERSONNEL.

WARNING:

www.altronicinc.com

FORM DD-40NTV II 12-09

www.altronicinc.com

1

1.0 OVERVIEW

1.1

  The Altronic DD-40NTV digital annunciator is an electronic, 40-

point monitor and shutdown device. The annunciator has a built-

in hourmeter/tachometer, overspeed and underspeed

*

 protection, 

and pre-/post-lube control

*

. Local display and remote communi-

cation (via ModBus RTU) is included for all critical operating pa-

rameters, including the internal battery, supplied DC power, and 

CD ignition shutdown lead voltages.

1.2

  The DD-40NTV annunciator is suitable for use in Class I, Division 2, 

Group C or D hazardous areas and consists of the following items: 

  

 DD-40NTV-O Annunciator, 40 normally-open points

  

 DD-40NTV-U Annunciator, 40 normally-closed or open 

 

    points (can be mixed)

  

 691200-3 Power Supply: 10–30 Vdc, 50 mA max. 

 

    or 100–400 volt negative ground CD ignition systems 

  

 693115-1 Cable, DB-25 (2 required for DD-40NTV-U    

  unit 

only)

  

 693116-1 Cable, D:B-9 (for RS-232 serial communications)

1.3

  RS-232/RS-485 serial communications are provided for 

remote engine monitoring via modem or satellite. Serial 

communications require the use of the DC power option.

1.4

  For reliable operation, the following instructions must be 

adhered to strictly.

DEVIATION FROM THESE INSTRUCTIONS MAY LEAD TO

IMPROPER OPERATION OF THE MACHINE WHICH COULD

CAUSE PERSONAL INJURY TO OPERATORS OR OTHER

NEARBY PERSONNEL.

WARNING:

NOTE: The DD-40NTV annun-

ciator may also be used with 

the 691200-1 Power Supply 

to emulate the function of 

the DD-40NTS system. For 

more detail, refer to Form 

DD-40NTS II 5-02.

Features designated by an 

in these Installation Instructions 

are NOT available if using the 691200-1 Power Supply.

Содержание DD-40NTV-O

Страница 1: ...following items DD 40NTV O Annunciator 40 normally open points DD 40NTV U Annunciator 40 normally closed or open points can be mixed 691200 3 Power Supply 10 30 Vdc 50 mA max or 100 400 volt negative...

Страница 2: ...exposed wires tightly together Insert the ex posed wire end completely into the terminal strip and securely tighten the clamping screw It is suggested that wire 18 AWG max to 24 AWG min be used for th...

Страница 3: ...THER WIRING AND KEEP SEPARATE THROUGHOUT THE INSTALLATION WIRING TO THE SENSORS MUST HAVE A GRADE OF INSULATION CAPABLE OF WITHSTANDING AN AC VOLTAGE OF 500 V RMS SENSOR LEADS MAY BE CONNECTED TO ANY...

Страница 4: ...clears Use the UP and DOWN keys to select the mode and press the ENTER key to save the mode 4 3 PROGRAMRPM1 This selects the RPM pre divide number equal to the pulses per revolution PPR The RPM signal...

Страница 5: ...e time delay in seconds for tripping SDI and OUTPUT 2 after a fault occurs The range of the delay is from 1 to 60 seconds Use the UP and DOWN keys to select the time and press the ENTER key to save th...

Страница 6: ...E This selects the type of Power Supply being used with the system type 1 for 691200 1 NTS mode or type 3 for 691200 3 NTV mode 4 16 TIMERKEY This selects the B1 and B2 timer delays The range is from...

Страница 7: ...atus and all of the monitored electrical voltages back up battery external DC power and CD ignition power 5 4 ENTER This key allows for selected items to be saved When pre or post lubing pressing the...

Страница 8: ...points will be displayed but will not cause the outputs to trip Testing an additional point requires the TEST key to be pressed again The annunciator will remain in test mode for two minutes before r...

Страница 9: ...wn indicates batteryisOK 00 Reset Beforestartingmachine momentarilypush theRESETbutton Adisplayof 00 indicates allClassAsensorsarereadyforstart up Anynumber10 57indcatesafaultedsensor thatmustbecleare...

Страница 10: ...d by 100 RPM Once armed should the monitored RPM fall below the setpoint the annunciator will trip the fuel and ignition outputs When this occurs the unit will display 72 and activate the FAULT indica...

Страница 11: ...condition or if the STOP key is depressed 7 3 Outputs SDI and SW2 will trip after a pre programmed time delay TIMER PROGM2 from either a fault condition or if the STOP key is depressed 7 4 For Power S...

Страница 12: ...node number is used in the system to identify the desired slave unit being polled The node number can be any numeric value from 1 to 99 9 4 ASCIICOMMUNICATION All communication to and from the annunci...

Страница 13: ...rd as shown with the exception of the not acknowledge NAK which is the industry standard control U header start node space command end ASCII 01 R D HEX 3Eh 28h 30h 31h 20h 52h 44h 29h CommandHeader 3E...

Страница 14: ...mmunications time out error An NAK error response will be sent by the annunciator when it has received a command with an error in the message All commands must be of the format above The header start...

Страница 15: ...ll en hance signal fidelity and is recommended To prevent ground loops the shield should be connected to the shield terminal at the master only LOADING RS 485 uses a balanced differential pair of wire...

Страница 16: ...inssamestatusasdisplay 40005 OutputStatus bit0 SW1 bit1 SW2 1 tripped 0 running 40006 Input chan 10 27 bit0 10 bit8 20 bit15 27 40007 Input chan 30 47 bit0 30 bit8 40 bit15 47 40008 Input chan 50 57 b...

Страница 17: ...ROGRAMMABLE DELAY TIME ON OUTPUT SW2 FEATURES INTEGRATED UNDERSPEED OVERSPEED TACHOMETER AND RUNTIME HOURMETER PRE LUBE POST LUBE DISPLAY CUSTOM 5 DIGIT LCD DISPLAY SCAN RATE SCANS ALL 40 DISCRETE SWI...

Страница 18: ...RPM HOURS PROGM 6 50 6 50 SPECIFICATIONS POWER REQUIRED DC POWERED 12 24 VDC 5 WATTS TYPICAL OR CD IGNITION SYSTEM 100 VOLTS MINIMUM INPUTS RPM SIGNAL FROM CD IGNITION OR PICKUP 40 DISCRETE SWITCH INP...

Страница 19: ...SUPPLY PIN 1 GIRARD OHIO NOTES 1 PLUG DB 9 CABLE FROM POWER SUPPLY INTO ANNUNCIATOR UNIT SECURE WITH SCREWS 2 SECURE POWER SUPPLY TO ANNUNCIATOR UNIT WITH 2 EA B 32 X 5 16 SCREWS PROVIDED 34 35 36 37...

Страница 20: ...RT CD IGNITION SHUTDOWN LEAD 100 400 VOLTS NEGATIVE GROUND ONLY PANEL GROUND 12 24 VDC NOTES 1 ENGINE GROUND AND PANEL GROUND MUST BE THE SAME 2 FOR IGNITION POWER USE IGN AND TERMINALS FOR DC POWER U...

Страница 21: ...AND TERMINALS 3 N O SENSOR SWITCH MUST HAVE JUMPER IN PLACE BETWEEN TOP ROW AND BOTTOM ROW OF TERMINAL BLOCK POWER SUPPLY MINUS AND SENSOR GROUND MUST BE AT GROUND 4 N C SENSOR SWITCH REMOVE JUMPER AN...

Страница 22: ...R PROGM 2 TIME DELAY FOR SDI AND OUTPUT SWITCH 2 OUTPUT SW1 CONFIGURES OUTPUT SWITCH 1 FOR NORMALLY OPEN OR NORMALLY CLOSED CONTACTS OUTPUT SW2 CONFIGURES OUTPUT SWITCH 2 FOR NORMALLY OPEN OR NORMALLY...

Страница 23: ...LAY FOR SDI AND OUTPUT SWITCH 2 OUTPUT SW1 CONFIGURES OUTPUT SWITCH 1 FOR NORMALLY OPEN OR NORMALLY CLOSED CONTACTS OUTPUT SW2 CONFIGURES OUTPUT SWITCH 2 FOR NORMALLY OPEN OR NORMALLY CLOSED CONTACTS...

Страница 24: ...GINE GROUND DO NOT CONNECT TO THE IGNITION SYSTEM COMMON COIL GROUND 3 8 MURPHY M50 CD REMOVE ALL JUMPERS DO NOT GROUND 5 TERMINAL CONNECT ONLY TO COIL LEADS AS SHOWN PNEUMATIC SYSTEM 690019 SOLENOID...

Страница 25: ...690019 SOLENOID VALVE ALTRONIC 690040 1 AC DC CONTROL FUEL VALVE FUEL VALVE E C B D S MURPHY 221 PH CD IGNITION SHUTDOWN LEAD 12 24VDC 1 2 CAUTION LUB TERMINAL 8TH FROM LEFT REPLACES RPM TERMINAL ON T...

Страница 26: ...C D ANNUNCIATOR POWER SUPPLY 24V I G N B A RS485 P U R R L U B S W 1 F V A S W 2 S D I IG SD S2 FV S1 LB RR PU B A IGNITION SHUTDOWN LEAD 12 24VDC VALVE COIL JUMPER CR CR DISCONNECT SWITCH IN FUEL VAL...

Страница 27: ...US CONDITION EXISTS Tx Rx P N 691200 3 S N GIRARD OHIO INSTALL PER FORM DD 40NT V II CERTIFIED CLASS I DIV 2 GRP C D ANNUNCIATOR POWER SUPPLY 24V I G N B A RS485 P U R R L U B S W 1 F V A S W 2 S D I...

Страница 28: ...DOWN SW2 IS FOR IGNITION SHUTDOWN RS 232 DO NOT CONNECT IF HAZARDOUS CONDITION EXISTS Tx Rx P N 691200 3 S N GIRARD OHIO INSTALL PER FORM DD 40NTV II CERTIFIED CLASS I DIV 2 GRP C D ANNUNCIATOR POWER...

Страница 29: ...SUPPLY 24V I G N B A RS485 P U R R L U B S W 1 F V A S W 2 S D I IG SD S2 FV S1 LB RR PU B A 12 24 VDC IGNITION SHUTDOWN LEAD PANEL GROUND 12 24 VDC DC RELAY LUBE MOTOR NOTE LUB IS A SOLID STATE N O...

Страница 30: ...T RESISTOR 5 VDC 50 mA MAX CABLE ASSEMBLY P N 593050 SERIES HALL EFFECT PICKUP P N 791050 SERIES C B A NORTH POLE OF MAGNET MUST FACE PICKUP TYP 030 040 24V I G N B A RS485 P U R R L U B S W 1 F V A S...

Страница 31: ...TS Tx Rx P N 691200 3 S N GIRARD OHIO INSTALL PER FORM DD 40NTV II CERTIFIED CLASS I DIV 2 GRP C D ANNUNCIATOR POWER SUPPLY 24V I G N B A RS485 P U R R L U B S W 1 F V A S W 2 S D I IG SD S2 FV S1 LB...

Страница 32: ...S Tx Rx P N 691200 3 S N GIRARD OHIO INSTALL PER FORM DD 40NTS II CERTIFIED CLASS I DIV 2 GRP C D ANNUNCIATOR POWER SUPPLY 24V I G N B A RS485 P U R R L U B S W 1 F V A S W 2 S D I IG SD S2 FV S1 LB R...

Страница 33: ...T ON POWER SUPPLY P N 693116 CABLE ASSEMBLY DB 9 M F TO RS 232 PORT ON COMPUTER DO NOT CONNECT IF HAZARDOUS CONDITION EXISTS Tx Rx P N 691200 3 S N GIRARD OHIO INSTALL PER FORM DD 40NTV II CERTIFIED C...

Страница 34: ...FT OPEN ACCEPTABLE CABLES FOR RS 232 APPLICATIONS 9534 9536 BELDEN 4 OR 6 CONDUCTOR 9609 9611 BELDEN 4 OR 6 CONDUCTOR LOW CAPACITANCE 9927 9931 BELDEN 4 OR 6 CONDUCTOR LOW CAPACITANCE FOR OTHER ACCEPT...

Страница 35: ...DE NUMBER 2 REFER TO INSTALLATION INSTRUCTIONS AND MODEM USER S GUIDE AND REFER ENCE MANUAL TO CONFIGURE MODEM 3 RS 485 TO RS 232 CONVERTER ADAM 4520 FROM ADVANTECH AMERICA EXTERNAL MODEM MOUNTED NEAR...

Страница 36: ...EM TEMP RANGE 0 C TO 50 C DD 40NTV O ANNUNCIATOR SYSTEM MOUNTED IN PANEL RS 232 STANDARD MAX CABLE LENGTH 50 FT FOR BEST RESULTS AN INDUSTRIAL SHIELDED CABLE SHOULD BE USED NULL MODEM ADAPTER TYPICAL...

Отзывы: