Altherma EKHBH016AA Скачать руководство пользователя страница 7

EKHBH/ EKSWW150-300V3/Z2

Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system

4PW36978-1C

Installation manual

4

Sanitary heating

When sanitary heating mode is enabled (either manually by the user,
or automatically through a schedule timer) the target sanitary water
temperature will be achieved by a combination of the heat exchanger
coil and the electrical booster heater.

When the sanitary water temperature is below the user configured
set point, the 3-way valve will be activated to heat the sanitary water
by means of the heat pump. In case of large sanitary water demand
or a high sanitary water temperature setting, the booster heater (10)
can provide auxiliary heating.

Application 3

Space cooling and heating application with a room thermostat
suitable for cooling/heating changeover
  connected to the indoor
unit. Heating is provided through floor heating loops and fan coil
units. Cooling is provided through the fan coil units only.
Sanitary warm water is provided through the sanitary water tank
which is connected to the indoor unit.

Pump operation and space heating and cooling

According to the season, the customer will select cooling or heating
on the room thermostat (T). This selection is not possible by
operating the user interface.

When space cooling/heating is requested by the room thermostat
(T), the pump will start operating and the indoor unit (2) will switch to
"cooling mode"/"heating mode". The outdoor unit (1) will start
operating to achieve the target leaving cold/hot water temperature.

In case of cooling mode, the motorised 2-way valve (13) will close as
to prevent cold water running through the floor heating loops (FHL).

The ON/OFF setting of the heating/cooling operation is done by the
room thermostat and cannot be done by the user interface on the
indoor unit.

Sanitary heating

Sanitary water heating is as described under 

"Application 2" on

page 3

.

Application 4

Space cooling and heating application without a room thermostat
connected to the indoor unit
, but with a heating only room
thermostat controlling the floor heating  and a cooling/heating
thermostat controlling the fan coil units. Heating is provided through
floor heating loops and fan coil units. Cooling is provided through the
fan coil units only.

It is possible to connect either a 2-wire or a 3-wire 3-way
valve (8). Make sure to fit the 3-way valve correctly. For
more details, refer to 

"Wiring the 3-way valve" on page 13

.

NOTE

The indoor unit can be configured so that at low
outdoor temperatures the sanitary water is exclusively
heated by the booster heater. This assures that the full
capacity of the heat pump is available for space
heating.

Details on sanitary water tank configuration for low
outdoor temperatures can be found under 

"Field

settings" on page 19

, field settings [5-02] to [5-04].

1

Outdoor unit

10

Booster heater

2

Indoor unit

11

Heat exchanger coil

3

Heat exchanger

12

Sanitary water tank

4

Pump

13

Motorised 2-way valve 
(field supply)

5

Shut-off valve

6

Collector (field supply)

FCU1..3

Fan coil unit (field supply)

7

Shut-off valve

FHL1..3

Floor heating loop 
(field supply)

8

Motorised 3-way valve 
(field supply)

T

Room thermostat with 
cooling/heating switch 
(field supply)

M

M

FHL1

T

FHL2

FHL3

FCU1

FCU2

FCU3

5

4

3

2

1

6

12

7

8

13

11

12

10

Make sure to connect the thermostat wires to the correct
terminals (see 

"Connection of the thermostat cable" on

page 13

) and to configure the DIP switch toggle switches

correctly (see 

"Room thermostat installation configuration"

on page 17

).

Wiring of the 2-way valve (13) is different for a NC (normal
closed) valve and a NO (normal open) valve! Make sure to
connect to the correct terminal numbers as detailed on the
wiring diagram.

M

FCU1

FCU2

FCU3

T4

T5

T6

FHL1

FHL2

FHL3

T

5

4

3

2

1

6

7

13

M

14

6

9

Содержание EKHBH016AA

Страница 1: ...INSTALLATION MANUAL EKHBH016AA EKHBX016AA EKSWW150V3 EKSWW200V3 EKSWW300V3 EKSWW200Z2 EKSWW300Z2 Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system ...

Страница 2: ... 5 6 7 1 2 3 5 4 3 4 5 350 300 35 48 35 668 895 922 39 361 48 142 101 235 235 502 500 23 30 4 7 400 90 200 1 2 3 4 5 3 4 FBSP 1 2 FBSP 0 40 0 H 300 630 220 110 1 2 3 4 5 6 Ø580 3 4 FBSP 3 4 FBSP 3 4 FBSP 1150 1 1 4 FBSP 1 1 4 MBSP 96 30 90 1 2 3 5 4 ...

Страница 3: ...ß den Vorschriften der 03 conformément aux stipulations des 04 overeenkomstig de bepalingen van 05 siguiendo las disposiciones de 06 secondo le prescrizioni per 07 Ì ٠ÚËÛË Ùˆv È Ù Íˆv Ùˆv 08 de acordo com o previsto em 09 в соответствии с положениями 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen määräyksiä 14 za dodržení ustan...

Страница 4: ...nit is the indoor part of the reversible air to water Daikin ERHQ heat pumps These units are designed for wall mounted indoor installation and used for both heating and cooling applications The units can be combined with Daikin fan coil units floor heating applications low temperature radiators and sanitary water heating applications Heating cooling units and heating only units The indoor unit ran...

Страница 5: ...acity 2 Required heating capacity site dependent 3 Additional heating capacity provided by the backup heater 4 Equilibriumtemperature can be set through the user interface refer to Field settings on page 19 TA Ambient outdoor temperature PH Heating capacity NOTE Especially for the United Kingdom For installation of an EKSWWU sanitary water tank refer to the installation manual supplied with the EK...

Страница 6: ...ed in series with another heat source e g gas boiler it shall be made sure that the return water temperature to the heat exchanger does not exceed 55 C Daikin shall not be held liable for any damage resulting from not observing this rule 1 Outdoor unit 6 Collector field supply 2 Indoor unit 7 Shut off valve 3 Heat exchanger FHL1 3 Floor heating loop field supply 4 Pump 5 Shut off valve T Room ther...

Страница 7: ... be done by the user interface on the indoor unit Sanitary heating Sanitary water heating is as described under Application 2 on page 3 Application 4 Space cooling and heating application without a room thermostat connected to the indoor unit but with a heating only room thermostat controlling the floor heating and a cooling heating thermostat controlling the fan coil units Heating is provided thr...

Страница 8: ...internals e g to connect the field wiring the switch box service panel can be removed Thereto loosen the front screws and unhitch the switch box service panel 1 Outdoor unit 14 Motorised 2 way valve for activation of the room thermostat field supply 2 Indoor unit 3 Heat exchanger 4 Pump FCU1 3 Fan coil unit with thermostat field supply 5 Shut off valve 6 Collector field supply FHL1 3 Floor heating...

Страница 9: ...r unit 11 Water inlet connection 12 Water outlet connection 13 Drain and fill valves 14 Water filter The water filter removes dirt from the water to prevent damage to the pump or blockage of the evaporator The water filter should be cleaned on a regular base See Maintenance on page 25 15 Expansion vessel drain valve The drain valve of the expansion vessel allows draining the remaining water in the...

Страница 10: ...IP switch SS2 The DIP switch SS2 provides 4 toggle switches to configure certain installation parameters See DIP switch settings overview on page 17 11 X13A socket The X13A socket receives the K3M connector only for installations with sanitary water tank 12 X9A socket The X9A socket receives the thermistor connector only for installations with sanitary water tank 13 Pump fuse FU2 in line fuse 14 P...

Страница 11: ...ries see Accessories on page 2 are enclosed Bring the unit as close as possible to its final installation position in its original package in order to prevent damage during transport The indoor unit weighs approximately 55 kg and should be lifted by two persons using the two lifting bars provided Requirement Value Maximum allowable refrigerant piping length between outdoor unit and indoor unit 75 ...

Страница 12: ...tallation of the unit check the following points The maximum water pressure is 3 bar Two shut off valves are delivered with the unit To facilitate service and maintenance install one at the water inlet and one at the water outlet of the indoor unit Mind position of the shut off valves Orientation of the integrated drain valves is important for servicing See figure 4 Drain taps must be provided at ...

Страница 13: ...ections must be made in accordance with the outlook diagram delivered with the unit respecting the water in and outlet If air moisture or dust gets in the water circuit problems may occur Therefore always take into account the following when connecting the water circuit Use clean pipes only Hold the pipe end downwards when removing burrs Cover the pipe end when inserting it through a wall so that ...

Страница 14: ...essure relief valve Water quality must be according to EN directive 98 83 EC WARNING A main switch or other means for disconnection having a contact separation in all poles must be incorporated in the fixed wiring in accordance with relevant local and national legislation Switch off the power supply before making any connections All field wiring and components must be installed by a licensed elect...

Страница 15: ... all wiring specifications Connection of the indoor unit power supply and communication cable Power circuit and cable requirements Power supply for the indoor unit is to be provided through the outdoor unit Data communication with the outdoor unit is provided through the same cable For all guidelines and specifications regarding field wiring between the indoor unit and the outdoor unit please refe...

Страница 16: ...wer supply 230 V AC Maximum running current 100 mA Wiring the 2 way valve 1 Using the appropriate cable connect the valve control cable to the X2M terminal as shown on the wiring diagram 2 Fix the cable s with cable ties to the cable tie mountings to ensure strain relief Wiring the 3 way valve 1 Using the appropriate cable connect the valve control cable to the appropriate terminals as shown on th...

Страница 17: ...e water outlet temperature during use Immediately after installation the sanitary water tank must be flushed with fresh water This procedure must be repeated at least once a day the first 5 consecutive days after installation In case of limited consumption of hot water e g at holiday residences or at houses that are occasionally not occupied the sanitary water tank installation must be fitted with...

Страница 18: ...el make sure the wall is sturdy In both cases make sure the tank is mounted level 3 Apply thermal paste to the thermistor and insert the thermistor as deep as possible in the thermistor socket Fix using the nut provided Connecting the water circuits 1 Connect the water inlet and water outlet 2 Connect the hot and cold water supply tubes 3 Connect the pressure relief valve field supply opening pres...

Страница 19: ...e PCB 6 Connect the prewired earth wires of the terminal block X3M and X4M to the earthing screw 7 Connect the booster heater power supply and thermal protection cable field supply to terminal X4M earth 1 2 and X2M 13 14 8 Connect the booster heater power supply cable to the terminal block X3M 9 Fix the cables to the cable tie mountings with cable ties to ensure strain relief 10 Set DIP switch SS2...

Страница 20: ...talled Not installed Default 3 Room thermostat connection see Room thermostat installation configuration on page 17 Room thermostat connected No room thermostat connected Default 4 This setting a decides the operation mode when there is a simultaneous demand for more space heating cooling and sanitary water heating a only applicable in case DIP switch 2 ON Heating cooling Sanitary Default When no ...

Страница 21: ...box on loose connections or damaged electrical components 6 Fixation Check that the unit is properly fixed to avoid abnormal noises and vibrations when starting up the unit 7 Damaged equipment Check the inside of the unit on damaged components or squeezed pipes 8 Refrigerant leak Check the inside of the unit on refrigerant leakage If there is a refrigerant leak call your local Daikin dealer 9 Powe...

Страница 22: ...o exit FIELD SET MODE Detailed description 0 User permission level If required certain user interface buttons can be made unavailable for the user Three permission levels are defined see the table below Switching between level 1 and level 2 3 is done by simultaneously pressing buttons pfi and pfj immediately followed by simultaneously pressing buttons s and ba and keeping all 4 buttons pressed for...

Страница 23: ...heating off temperature 4 02 Space heating off temperature outdoor temperature above which space heating is turned off to avoid overheating 5 Equilibrium temperature and space heating priority temperature Equilibrium temperature The equilibrium temperature field settings apply to operation of the optional backup heater When the equilibrium temperature function is enabled operation of the backup he...

Страница 24: ...ry water tank When the sanitary water is heated and the sanitary water set point temperate as set by the user has been reached the booster heater will continue to heat the sanitary water to a temperature a few degrees above the set point temperature i e the booster heater OFF temperature These extra degrees are specified by the sanitary water step length field setting Correct setting prevents the ...

Страница 25: ...mum leaving water temperature for heating operation 9 02 Cooling set point upper limit maximum leaving water temperature for cooling operation 9 03 Cooling set point lower limit minimum leaving water temperature for cooling operation A Quiet mode This field setting allows to select the desired quiet mode Two quiet modes are available quiet mode A and quiet mode B In quiet mode A priority is given ...

Страница 26: ...atus 1 ON 0 1 01 Priority 0 OFF 0 1 02 Space heating off temperature 35 14 35 1 C 5 Equilibrium temperature and space heating priority temperature 00 Equilibrium temperature status 1 ON 0 1 01 Equilibrium temperature 0 15 20 1 C 02 Space heating priority status 0 OFF 0 1 03 Space heating priority temperatures 0 15 20 1 C 04 Set point correction for sanitary water temperature 10 0 20 1 C 6 DT for s...

Страница 27: ...d as follows when no action is performed the user interface will return to normal mode after 10 seconds or by pressing the z button once To test the heating operation push the h c button so the h icon is displayed To start the test run operation press the y button To test the cooling operation push the h c button so the c icon is displayed To start the test run operation press the y button To test...

Страница 28: ... unit and look for obvious defects such as loose connections or defective wiring Before contacting your local Daikin dealer read this chapter carefully it will save you time and money When a safety device was activated stop the unit and find out why the safety device was activated before resetting it Under no circumstances safety devices may be bridged or changed to a value other than the factory ...

Страница 29: ... reset button Check whether booster heater and backup heater are configured to operate simultaneously field setting 4 02 see Field settings on page 19 Check whether or not the thermal fuse of the backup heater is blown refer to Main components Backup heater thermal fuse on page 6 for location of the reset button The backup heater equilibrium temperature has not been configured correctly Raise the ...

Страница 30: ...e refer to Technical specifications on page 28 Contact your local Daikin dealer E7 Fan lock failure fan is locked Check if the fan is not obstructed by dirt If the fan is not obstructed contact your local Daikin dealer E9 Malfunction of electronic expansion valve Contact your local Daikin dealer EC Sanitary water temperature too high 89 C Check that the contactor of the electric booster heater is ...

Страница 31: ...ry water by heat pump 20 35 C 20 35 C a MBSP Male British Standard Pipe b At 1 m in front of the unit free field condition Heating cooling models EKHBX Heating only models EKHBH Standard unit power supply via outdoor unit Power supply 230 V 50 Hz 1P Nominal running current See outdoor unit installation manual Backup heater Power supply See Connection of the backup heater power supply on page 12 Ma...

Страница 32: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW36978 1C Copyright Daikin ...

Отзывы: