EKHBH/ EKSWW150-300V3/Z2
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36978-1C
Installation manual
12
Internal wiring - Parts table
Refer to the internal wiring diagram supplied with the unit (on the
inside of the indoor unit switch box cover). The abbreviations used
are listed below.
A1P ..................Main PCB
A2P ..................Remote controller PCB (user interface)
A3P ..................Thermostat (field supply, PC= internal Power Circuit)
E1H.......... *......Backup heater element 1
E2H.......... *......Backup heater element 2
E3H.......... *......Backup heater element 3
E4H......... #......Booster heater
F1B .......... *......Fuse backup heater
F2B ......... #......Fuse booster heater
F1T ..................Thermal fuse (250 V, 94°C)
FU1 ..................Fuse 3.15 A T 250 V
FU2 ..................Fuse 5 A T 250 V
K1M ......... *......Contactor backup heater step 1
K2M ......... *......Contactor backup heater step 2
K3M ........ #......Contactor booster heater
K4M .................Pump relay
K5M .................Contactor for thermal fuse
M1P .................Pump
M2S ...... ##......2-way valve for cooling mode
M3S ........ #......3-way valve: floor heating/sanitary warm water
Q1DI ................Earth leakage protector
Q1L .......... *......Thermal protector backup heater
Q2L ......... #......Thermal protector booster heater
R1T (A1P)........Outlet water heat exchanger thermistor
R2T .......... *......Outlet water backup heater thermistor
R3T ..................Refrigerant liquid side thermistor
R4T ..................Inlet water thermistor
R5T ......... #......SWW (sanitary warm water) thermistor
S1L ..................Flow switch
TR1 ..................Transformer 24 V for PCB
V1S ..................Spark suppression 1
V2S ..................Spark suppression 2
X1M-X4M.........Terminal blocks
Field wiring guidelines
■
Most field wiring on the indoor unit side is to be made on the
terminal block inside the switch box. To gain access to the
terminal block, remove the indoor unit cover and switch box
service panel, see
"Opening the indoor unit" on page 5
■
Cable tie mountings are provided at the bottom of the switch
box. Fix all cables using cable ties.
■
A dedicated power circuit is required for the backup heater
(optional).
■
Installations equipped with a sanitary water tank (optional),
require a dedicated power circuit for the booster heater.
Please refer to
"Sanitary water tank (optional)" on page 14
for all
wiring specifications.
Connection of the indoor unit power supply and
communication cable
Power circuit and cable requirements
Power supply for the indoor unit is to be provided through the outdoor
unit. Data communication with the outdoor unit is provided through
the same cable.
For all guidelines and specifications regarding field wiring between
the indoor unit and the outdoor unit, please refer to the outdoor unit
installation manual.
Procedure
1
Using the appropriate cable, connect the power circuit to the
appropriate terminals as shown on the wiring diagram and the
illustration below.
2
Connect the earth conductor (yellow/green) to the earthing
screw on the switch box mounting plate.
3
Fix the cable with cable ties to the cable tie mountings to ensure
strain relief.
4
When routing out cables, make sure that these do not obstruct
mounting of the indoor unit cover, see
Note: only relevant field wiring is shown.
Connection of the backup heater power supply
Power circuit and cable requirements
This power circuit must be protected with the required safety devices
according to local and national regulations.
Select the power cable in accordance with relevant local and national
regulations. For the maximum running current of the backup heater,
refer to the table below.
*
Optional
#
Applications with sanitary water tank only
##
Heating/cooling applications only
■
Be sure to use a dedicated power circuit for the
backup heater. Never use a power circuit shared by
another appliance.
■
Use one and same dedicated power supply for the
outdoor unit, indoor unit, backup heater and booster
heater (sanitary water tank).
Indoor unit model
Backup heater
capacity
Backup heater
nominal voltage
Maximum
running current
EKHB*016AA3V3
3 kW
1 x 230 V
13 A
EKHB*016AA6V3
6 kW
1 x 230 V
26 A
EKHB*016AA6WN
6 kW
3 x 400 V
8.6 A
EKHB*016AA9WN
9 kW
3 x 400 V
13 A
EKHB*016AA6T1
6 kW
3 x 230 V
15 A
EKHB*016AA9T1
9 kW
3 x 230 V
23 A
OPTION EKSWW
OPTION EKSWW
N
L
L2
L1
X3M (230V)
2
1
X4M
OPTIONAL
X2M
18
17
16
15
Q2L
3-way valve
2-way valve
12
11
4
thermostat
2
1
3
5
6
7
8
9
10
13
14
thermal
fuse
F2B
F1B
A1P
K4M
X4M
X2M
X3M
X1M
1 2 3
1
3
2
X1M
1 2 3