Installation
Instruction manual 91/104 V9.2
Drawing 2
Connection from a DC power line
4.1 Preliminary operations
•
Check that the drive has suffered no damage in the transport.
•
Mount the drive vertically away from heat sources and so that there is sufficient free space above and below for good cooling
air circulation.
•
Use unpainted sheet fixing panels connected to the ground.
•
Connect to a good ground the ground terminal placed on the right side of the drive terminal.
•
Follow the link patterns in the manual carefully.
•
Use shielded cables for signal and power connections.
•
Connect to the ground on the carpentry or on the terminals arranged on the two ends of the shields.
•
Do not use terminal blocks but only shielded connectors for signal and power shielded cable junctions.
•
Mounting noise suppressors (off for a.c./diodes for D.C.) parallel to the coils of all contactors, relays, solenoid valves, single-
phase motors, three-phase motors, etc.