Waterproof Keypad

AS626S

Read all instructions before starting installation

Connect keypad using wiring description.

Wiring description

Power 

12 or 24v AC or DC

 

(AC does not have a polarity)

Brown 

+ Positive

Blue  

- Negative

Output Relay 

Max 2amp @ 24v 

Grey Common
Red 

Selectable – Relay NO or NC (Default is set to NO)

 

To change see 7 & 8 under ‘Programming the Keypad’  

 

Contact 2 Amp. Dry contact for Door Strike 

Exit Button  

Push to make – Volt free

White/Pink 

Exit Button (NO) 

Power Consumption 

Stand by – Approximately 25 milliamps @12vDC

 

Operation – Approximately 80 milliamps @12vDC

For 12vDC inductive loads such as electric strikes and electromagnetic locks, 

the enclosed 12vDC metal oxide varistor must be connected in parallel with 

the load, at the load terminals and not in the keypad.
Ensure power supply is of correct rating, taking into account the current 

requirements of the locking items and accessories.

Do not insert security plugs into fixing holes until all installation and testing has 

been completed. These items require drilling out and cannot be re-fitted.

LED signalling explanation
GREEN LED  Door Strike activated  (unlocked)
RED LED 

Normal Operation: 

3 sec. ON = wrong 

 

 

Code Entry

 

 

Slow flashing = wrong code 

 

 

entry 3 times

 

Programming Mode:  Fast flashing = programming

 

 

different functions

 

 

Slow flashing = programming

  

stand-by

 

 

Very fast flashing = erasing all

 

 

user codes

The door remote opening (via exit switch) is possible when a dry contact is 

made between the wires White and Orange.
The lock is activated for the time the system is programmed. Factory set @ 

5 seconds.
Remote opening is disabled during programming and latch mode.

Apply power

 to the keypad.  The keypad’s buzzer will sound briefly, the 

Red LED will illuminate briefly Initialisation is now complete, with a default 

master code of 1-2-3-4 and a 5-second open door.

PACK CONTENTS

MOUNTING INSTRUCTIONS

ACTIVATION

TESTING THE UNIT

PROGRAMMING THE KEYPAD

TROUBLE SHOOTING

INITIALISATION

Connect to + of

Locking Device

Connect to - of

Locking Device

Breakglass

Pink

White

Brown

Blue

Grey

Red

Power Supply

Exit Button

Enter the master code [1 2 3 4 #]

The Door Relay changes its contacts for 5 sec.

The Green LED will light up for 5 sec. Repeat this step 2,3 times.

If the master code is wrongly typed in, the Red LED lights up for 3 sec. re-

enter the Code as soon as the LED goes OFF.

IMPORTANT: CHANGE THE FACTORY SET MASTER CODE WHEN YOU PROGRAM 

YOUR UNIT FOR USE. THERE IS NO WAY TO RECOVER THE NEW MASTER CODE IF 

IT IS LOST OR FORGOTTEN. THE UNIT CAN BE RESET TO FACTORY PRESETS AND 

CUSTOMISED AGAIN. See Data Reset

Enter

  

H H

1 2 3 4 

H H

The keypad enters programming mode, the Red LED flashes

If no further information is added, the unit will revert to normal 

operation after a 3 second delay. To exit programming press #.

There are six programming options: -

1. Set new master code

It is suggested the Master Code is not changed until person 

programming is familiar with all aspects of programming the keypad!

2. Set new user code
3. Erase a user code
4. Erase all user codes
5. Set door open time (1-99s)
6. Set output to latch option
Continued over...

The keypad does not “respond” when activating the keys.
1. Make sure the electronic unit has been properly wired to the PSU and the 

power has not been cut-off.

The keypad “responds” but the door does not open.
1.  Make sure the Green LED is illuminated.
2.  If not, the entered code has not been programmed yet. Please refer to 

“Programming”.
3.  Enter the Master Code and make sure the door opens correctly. If not, 

check the wiring and the Lock’s integrity.

1

3

5

7

9

*

2

4

6

8

0

#

x2

x2