Communication function

 

It  can  communicate  with  the  computer  or  host  through  RS485,  upload  and  save  the  collected 
information. 
CAN bus communication, 2G/3G/4G communication and  Bluetooth  communication  can be 
optional. 

 

Anti-theft function

 

When the external  load is disconnected, the BMS  cannot detect the load  resistance, and it will 
enter into a locked state, unable to conduct charging and discharging 

 

Note: 

1. Please refer to 

Specification of each models

” 

for detail BMS parameter setting value. 

2.

 

LCD display screen is provided as option.

 

3.

 

Anti-theft function is provided as option. 

4.

 

Thermal management in low temperature heating and high temperature heat 

dissipation is optional 

 
 

2.4

 

– Applications

 

 

 

Telecommunication 

 

Terminal of FTTX 

 

Access network system 

 

Indoor distribution system 

 

Integrated outdoor power cabinet 

 

Internet data center (IDC) 

 

Energy storage system 

 
 

2.5

 

– Battery Model Name

 

 

      APL 48-50 LFP 

 

LiFePO

battery 

 

Rated capacity (50Ah) 

 

Rated voltage (48V) 

 

APL product 

 

Содержание APL 48-50 LFP

Страница 1: ...Moorebank NSW 2170 Australia Alpha Power Systems T 02 9602 8331 F 02 9602 9180 E admin alphapower com au W www alphapower com au APL 48 50 LFP Lithium ion Battery Operation Manual APL 48 50 LFP Lithi...

Страница 2: ...Charge Performance 8 3 3 Constant Current Discharge Table 8 3 4 Constant Power Discharge Table 8 Part 4 Operation Maintenance 9 4 1 Requirements for Operation Environment 9 4 2 Parameter Settings of P...

Страница 3: ...ndles Do not place tools or metal objects on the battery Do not direct access to the battery system to the mains grid power outlet Do not put the battery system into fire do not use or storage the bat...

Страница 4: ...ithium iron phosphate battery units in series with the dedicated high performance and high reliability battery management system BMS The output terminal of the battery is connected to the terminal of...

Страница 5: ...elay time of the discharge detection the protective plate judges that the over discharge state occurs The green RUN lamp and red ALM lamp are both extinguished discharge MOSFET is closed and the batte...

Страница 6: ...he equalization function Battery supports up to 7 channels simultaneously to turn on equalization The maximum equalization current is about 75mA Balance will stop when charging stops or the voltage di...

Страница 7: ...able to conduct charging and discharging Note 1 Please refer to Specification of each models for detail BMS parameter setting value 2 LCD display screen is provided as option 3 Anti theft function is...

Страница 8: ...of Cells 15 cells Limited Charge Voltage 54 0 V Discharge Cut off Voltage 42 V Standard Charge Current 10 A Standard Discharge Current 10 A Max Continuous Charge Current 50 A Max Continuous Discharge...

Страница 9: ...liFePO4 Battery Operation Manual Part 3 Technical Characteristics 3 1 Discharge Performance Fig 3 1 Constant Current Discharge Curve of APL LFP 25 Fig 3 1 Discharge Curve of different temperature of...

Страница 10: ...3 33 2 49 1 98 1 65 1 23 0 98 42 0 10 08 4 96 3 97 3 31 2 47 1 96 1 64 1 21 0 96 43 5 10 00 4 92 3 94 3 27 2 45 1 94 1 62 1 19 0 95 45 0 9 91 4 85 3 88 3 22 2 40 1 90 1 58 1 17 0 92 3 4 Constant Power...

Страница 11: ...cid batteries can be replaced by lithium battery of APL48 50LFP if power is matched Table 4 2 Parameter settings of power plant for lithium ion battery No Parameters Units Defaults 1 Charge voltage V...

Страница 12: ...Charge Current 1 0C No Charge Allowed 25 50 Charge Current 0 5C Charge Current 0 75C 1C Charge is allowed when voltage is lower than 3 65V 50 60 Charge Current 0 1C 60 No Charge Allowed Table 4 4 Dis...

Страница 13: ...n port It is adopting RS 232 series port to upload data Contents of data transmit include BMS parameters battery running status alarms etc Generally speed rate of RS 232 is 1200bps RS232 up link commu...

Страница 14: ...ation Batteries shall not be placed in direct sunshine or close to heat source Batteries shall be installed in place with good ventilation to assure enough heat dissipation Batteries shall be placed i...

Страница 15: ...etween battery module and power plant shall be less than 2 0m To make sure similar voltage drop of cable for each battery length of all positive and negative cables should be the same Color for cable...

Страница 16: ...on cable between battery module and power plant shall be less than 0 5V 4 7 Storage The battery storage shall be in the clean and dry ventilation room at the temperature of 0 40 C and shall keep out o...

Страница 17: ...ged Normal charge management Do not need to solve Protection against over voltage Do not need to solve Protection against over temperature or under temperature Ambient temperature is lowerthan 10 or h...

Страница 18: ...lash 1 Flash 2 Alarm light goes off after a few seconds Over temperature under temperature over current protection Flash 1 Flash 2 Discharge Normal Normally on OFF According to the SOC Alarm Normally...

Страница 19: ...ave PACK ON OFF OFF ON OFF OFF PACK 10 001001 Slave PACK OFF ON OFF ON OFF OFF PACK 11 001010 Slave PACK ON ON OFF ON OFF OFF PACK 12 001011 Slave PACK OFF OFF ON ON OFF OFF PACK 13 001100 Slave PACK...

Страница 20: ...CK OFF OFF OFF OFF ON ON PACK 49 110000 Slave PACK ON OFF OFF OFF ON ON PACK 50 110001 Slave PACK OFF ON OFF OFF ON ON PACK 51 110010 Slave PACK ON ON OFF OFF ON ON PACK 52 110011 Slave PACK OFF ON OF...

Страница 21: ...system uses through 6Pin straight PCB welding socket RJ11 to provide RS 232 protocol the pin assignment of RJ11 is defined as follows Table 1 RJ11 Pin Assignment 2 RS 485 The system uses through 8Pin...

Отзывы: