AWD108

  Rev. 7 (11/2017)

APPLICATION

The AlphaStatus™ system allows one or more RSS402, 

RSS403, RSS404 and/or RSS405 room status stations 

to provide locking push-button registration (of up to 4 

different colors) of the room status to the CDL104LED 

or CDL102LED corridor dome status light(s). When one 

or more optional master stations are used, the status reg-

istered by each room status station will also be displayed 

at each master station and other indicators based on the 

system configuration. A number of optional accessories 

are available to provide a complete signaling system. 

Models RSS403 and RSS405 also allows for optional 

audible signaling from a room location to the master 

location(s).

PROCEDURE

1.   Read installation instructions for each unit to deter-

mine equipment location and installation method.

2.  Install housings and wiring.

3.  Install equipment.

4.  Check wiring and connect. Observe all local and

 

national electrical and building codes.

5.  Apply power and check operation, making sure to 

observe polarity where indicated.

HOUSING INSTALLATION AND 

EQUIPMENT LOCATION

INSIDE ROOM STATUS STATIONS

Locate stations where needed at a convenient height, 

about 4.5 feet (137cm) from the finished floor. Unit can 

be flush mounted over a double gang electrical box or 

double gang plaster ring, or surface mounted using a 

double gang mounting box (with suitable inside clear

-

ance depth).

CORRIDOR DOME STATUS LIGHTS

Locate corridor dome status lights where needed, in the 

corridor outside of each room location. Typically, these 

dome lights mount right over the doorway to the room. 

They can be mounted on the side of the room door, but 

please mount them high enough to avoid anyone walking 

into the dome light portion that protrudes from the wall. 

Unit can be flush mounted over a double (or single) gang 

electrical box or double (or single) gang plaster ring, or 

surface mounted using a double gang mounting box (with 

suitable inside clearance depth). 

AlphaStatus™ Room Status System

Installation and Use Instructions

for the RSS400 Series Room Stations

and Optional Master Station(s)

MASTER STATION(S)

If one or more master stations are used, locate at a 

convenient viewing height (for wall mounting) or at a 

convenient viewing angle for desk or table-top mounting.

PSR-24/6 POWER SUPPLY

The PSR-24/6 power supply is usually located  in a sep-

arate equipment location, but can be mounted near the 

master station (if used). The PSR-24/6 can be mounted 

on a small shelf, or other suitable location. It  must be 

located away from any source of direct heat or extreme 

cold and in an accessible location. Keep at least 3 feet 

(1 meter) away from transformers, light dimmers or 

other electrical devices or wiring or sources of electrical 

interference. Plug the PSR-24/6 power supply unit(s) 

into a standard 117VAC electrical wall outlet. It is rec-

ommended that one PSR-24/6 power supply be used 

for each 18 room status stations (with full lamp lighting 

capability) or one for each 36 room stations (with 1/2 

lamp lighting capability).

WIRING

INSIDE ROOM STATUS STATIONS

When using a master station, the easiest wiring method 

is to home-run a #22AWG multi-conductor cable from 

each room status station directly to the master station 

location. Run a 5-conductor #22AWG cable from the 

room status station to its corresponding CDL104LED (4-

LED) corridor dome status light, or 3-conductor #22AWG 

cable from the room status station to its corresponding 

CDL102LED (2-LED) corridor dome status light. For 

runs greater than 250 feet, increase the #22AWG cable 

to #18AWG cable.

When a master station is not used, the easiest wiring 

method is to loop a 2-conductor #22AWG cable from the 

PSR-24/6 power supply from one corridor dome status 

light  to  the  next,  to  supply  power. Additional  power 

(or common wires) may be needed as well, depending 

upon  system  options.  Run  a  5-conductor  #22AWG 

cable from the room status station to its corresponding 

CDL104LED  (4-LED)  corridor  dome  status  light,  or 

3-conductor #22AWG cable from the room status station 

to its corresponding CDL102LED (2-LED) corridor dome 

status light. For runs greater than 250 feet, increase the 

#22AWG cable to #18AWG cable.

Cables may be straight or twisted pair type and may be 

solid or stranded conductors. Route cables away from AC 

power wiring, transformers, fluorescent lights, dimmers or 