RBMS Plus Installation and Opera
RBMS Plus Installation and Operation Manual
Alpha Technologies Ltd. | www.alpha.ca
PAGE 47
0370260-J0 Rev B
Discover Sensors Now
will force the
RBMS Plus to discover any new
sensors that have been connected.
The RBMS Plus will periodically go and
discover new sensors but pressing the
button forces it to discover
immediately.
Log Off
will log off the current user. After logging off and returning to the overview display you will again be prompted
for a password when entering into any configuration page.
Reset All Sensors
will reset the sensors on all of the strings. The database is unaffected. The sensors will be
rediscovered on the next polling cycle.
Flash the Modem Power
will switch the power output off for a second and then back on again.
5.4.2.
Provisioning String Settings (with optional battery sensors)
In the Overview Display there is an
S
button corresponding to each battery string. Pressing this button will display the
following page:
To change the
String Name
enter a new name and press one of the buttons to apply the name to this string or to all the
strings.
Checking the
Equalize Enable
box will enable
equalization on this string. Default is enabled.
If the
Measure Admittance on All Jars
button is
pressed, an admittance measurement will be
made on all jars in this string.
If the
Reset This String
button is pressed a reset
command will be sent to all sensors on this
string. This will force the RBMS Plus to reinitialize
the sensors.
If the
Delete This String
button is pressed, the string will be deleted from the RBMS Plus. All user settings for this string
will be lost. If there are sensors connected to this string port on the RBMS Plus they will be reset and rediscovered.
NOTE:
If a string is deleted, all user setting for the sensors on the string will be lost. This includes names, , alarm
settings, initial admittance and calibration settings.
The discharge status indicator displays the present state to this string either “Normal” or Discharging”. The discharge
event is detected by setting a threshold voltage on the string. Enter the desired value in the box on this page.
Pressing the Previous String button will return to the previous string page.
Pressing the Next String button will move to the next string page.
Pressing the Return to Overview Display button will return to the Site Overview page.