Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 3 - Features
the front panel. A full defragmentation may take up to 20 minutes to perform, do not power down the
controller during this time.
Note:
Refer also to the software manual – always select the Reset menu item before pressing the
reset button.
3.4. Controller Input and Output
The inputs and outputs refer to both the CXCi+ and the CXCi HP controllers.
Ethernet Port
The Ethernet port is designed for connection to a user supplied network (TCP/IP secured by user) via a
front panel RJ-45 jack and a standard network cable. Local access (e.g. laptop computer) is also possible
from the Ethernet port connection using a standard network cable.
Analog Input Channels
The controller is provided with analog input channels for voltage, current, and temperature.
Voltage Inputs
Two voltage input channels, V1 and V2, provide monitoring of discharge and charge voltage. The
controller software is pre-configured to monitor V1 for battery voltage and V2 for load voltage.
V2 is wired internally to the rectifier shelf to provide a reference for rectifier float voltage, low voltage
disconnect (LVD), system high voltage alarm, and system low voltage alarm.
Wire V1 to battery to monitor battery voltage or change battery setting from V1 to V2 in
Signals >
Configure Signals
.
Current Inputs
The controller software is pre-configured to monitor I1 for load current wired internally to the load current
shunt.
Temperature Inputs
Two temperature input channels, T1 and T2, provide monitoring of battery temperature and temperature
compensation (temp comp) or room/ambient temperature. A voltage is supplied to these terminals to
power the temperature sensors.
Digital Input Channels
The controller can accommodate up to two channels and can monitor digital alarm/control signals from
rectifiers, converters and many other types of equipment.
Alarm and Control Output Relays
The controller contains four Form C digital alarm output relays to extend alarms and control external
apparatus. Each internally generated alarm or control signal may be mapped to any one of the relays, or,
several signals may be mapped to just one relay or none at all.
Page 18
9400021-J0 Rev B