Operating mode 

The mode that  guarantees the maximum protection for the  load is the ON LINE mode, in  which the Energy for the 

load  undergoes  a  double  conversion  and  is  reconstructed  at  the  output  in  a  perfectly  sinusoidal  manner,  with  the 

frequency and the voltage set by a precise digital control of the DSP regardless of the input (V.F.I.). 

In addition to the traditional ON LINE double-conversion mode, it is possible to select the following modes: 

ECO (LINE INTERACTIVE) 

SMART (SMART ACTIVE) 

STBYOFF (STAND-BY OFF) 

In order to optimise the efficiency, in ECO mode the load is normally powered from the bypass (any interference on 

the mains can affect the load). In absence of the mains, or when the mains voltage exceeds its tolerance limit, the 

TRI POWER X33 HE commutates to the normal ON LINE double-conversion mode. About five minutes after having 

returned within its tolerance limits, the load is commutated back to bypass. 

If the user cannot decide which is the most suitable operating mode (between ON LINE and ECO) the choice can be 

left to the SMART ACTIVE mode, in which, according to statistical data on the quality of the mains power supply, the 

TRI POWER X33 HE autonomously decides in which mode to configure itself. 

Finally, in STAND-BY OFF mode, the TRI POWER X33 HE is set to operate as a back-up device: 

In presence of the mains power, the load is not powered, whilst in the event of a black-out, the load is powered by 

the inverter via the batteries. When the mains power is restored, the load is powered off again. The activation time is 

less than 0.5 seconds. 

Maintenance bypass (SWMB) 

WARNING: Maintenance inside the TRI POWER X33 HE must be carried out by qualified personnel 

trained by the manufacturer only. In fact,  inside the equipment there may be a voltage  even when 

the input, output and battery switches are open. Removal of the TRI POWER X33 HE panels by non-

qualified personnel may cause harm to the operator and damage to the equipment. 

Listed  below  are  the  operations  to  be  performed  in  order  to  carry  out  the  maintenance  on  the  equipment  with  no 

interruption of the power supply to the load: 

With the  mains  voltage  present,  the  TRI  POWER  X33  HE  must  power  the  load  through  the  inverter  or  the 

automatic bypass. 

N.B.: If the TRI POWER X33 HE is in battery power mode, activating the maintenance bypass may imply an

interruption of the power supply to the load.

Close  the  maintenance  bypass  isolator  (SWMB)  located  behind  the  door.  This  way,  the  input  is  short-

circuited with the output.

Open  the  input  switches  (SWIN),  the  output  switches  (SWOUT),  and  the  battery  fuse  holders  (SWBATT)

located  behind  the  door.  The  signal  panel  is  turned  off.  Wait  for  the  electrolytic  condensers  on  the  power

board to discharge (about 20 minutes) and then proceed with the maintenance operations.

N.B.: 

During  this  phase,  with  the  load  powered  via  the  maintenance  bypass,  any  disturbance  on  the  TRI

POWER X33 HE power supply line would affect the equipment powered (the load is connected directly to the 

mains. The TRI POWER X33 HE is no longer active). 

Moreover, the auxiliary "Power share" and "Power 

out" sockets, are no longer powered (see "Auxiliary (power share)sockets" in the "USE" section). 

Содержание Tri Power X33 HE

Страница 1: ...Page 0 to 52 Tri Power X33 HE 30 125KVA User Manual...

Страница 2: ...he best performance This manual contains detailed instructions on how to use and install this product For information on how to use this equipment and obtain the best performance this manual must be c...

Страница 3: ...Tri Power X33 HE internal protections 18 External protection devices 19 Cross section of the cables 20 Connections 20 Connections of the model with separate bypass 21 R E P O 21 External Sync 22 Remot...

Страница 4: ...ation ports 37 RS232 AND USB CONNECTORS 37 Communication Slot 38 AS400 PORT 38 Buzzer 40 Software 41 Monitoring and control software 41 Configuration software 41 Troubleshooting 42 Status alarm codes...

Страница 5: ...such as ZERO IMPACT SOURCE ensures low input distortion a power factor close to 1 and maximum generator set compatibility BATTERY CARE SYSTEM allows a customised management for different battery type...

Страница 6: ...Page 5 to 52 Front views of the Tri Power X33 HE Control panel with graphic display Wheels for moving the TRI POWER X33 HE Front door with lock Brake rod Ventilation grid...

Страница 7: ...Separate bypass isolator optional Manual bypass isolator Output isolator From the left Battery start button COLD START R E P O Remote Emergency Power Off connector Contact holder for AS400 USB communi...

Страница 8: ...HE connections Power connections EXTERNAL BATTERY INPUT SEPARATE BYPASS optional OUTPUT Connection for external synchronization signal Connection for remote maintenance bypass command Connection for...

Страница 9: ...Page 8 to 52 Rear view of the Tri Power X33 HE Parallel board slot optional Power board fans Powershare socket Power out socket Battery charger fan Power relay board slot optional...

Страница 10: ...rding to the menu Separate bypass input optional THE OPTIONAL DI VERSION OF THE TRI POWER X33 HE SERIES HAS SEPARATE BYPASS AND INPUT LINES The TRI POWER X33 HE series with Separate Bypass allows a se...

Страница 11: ...r battery 1 1 4 kW 1205 kcal h 4780 B T U h 1 5 kW 1290 kcal h 5120 B T U h Dissipated power with nominal distorting load pf 0 7 and charged battery 1 1 34 kW 1150 kcal h 4565 B T U h 1 35 kW 1160 kca...

Страница 12: ...mains between 0 and 40 C while the TRI POWER X33 HE is operating This TRI POWER X33 HE can operate with an ambient temperature between 0 and 40 C The recommended working temperature for the TRI POWER...

Страница 13: ...he cardboard box by sliding it upwards Remove the packaging material Remove the accessory box NOTE the accessory box can be either inside the packaging or behind the USP door Remove the 2 brackets sec...

Страница 14: ...pallet Make sure that the door is firmly closed CAUTION Push the TRI POWER X33 HE from the rear with great care Given the weight of the equipment this operation needs to be carried out by two people N...

Страница 15: ...ll to allow the air blown by the ventilation fans to outflow correctly No objects should be placed on its upper surface Once the equipment has been positioned secure it with the apposite brake rod see...

Страница 16: ...protective earth of TT TN or IT type Therefore the phase rotation must be respected Optional TRANSFORMER BOXES to convert the distribution systems from 3 wires to 4 wires are available Diagrams of co...

Страница 17: ...HE with no modification of the neutral regime and with separate bypass input TRI POWER X33 HE with input galvanic isolation and with separate bypass input TRI POWER X33 HE with output galvanic isolati...

Страница 18: ...me potential In case the two power supplies were different an isolation transformer would be necessary on one of the inputs TRI POWER X33 HE with no modification of the neutral regime and with separat...

Страница 19: ...so depend on the TRI POWER X33 HE operating status at the time of the fault which can be either TRI POWER X33 HE in NORMAL OPERATION the load is instantly commutated to the bypass line TRI POWER X33 H...

Страница 20: ...put This way the neutral regime of the equipment is not modified THE INPUT NEUTRAL IS CONNECTED TO THE OUTPUT NEUTRAL THE DISTRIBUTION SYSTEM THAT POWERS THE TRI POWER X33 HE IS NOT MODIFIED BY THE TR...

Страница 21: ...inserted in the terminal board is 25 mm2 for trailing cables 35 mm2 per rigid cables Connections As for TRI POWER X33 HEs with separate bypass please see the subsequent paragraph The very first connec...

Страница 22: ...onnections to the BATTERY module are required only when the optional Battery Box is present R E P O This isolated input is used to turn off the TRI POWER X33 HE remotely in case of emergency This TRI...

Страница 23: ...diagram below for example o allow replacing the TRI POWER X33 HE without interrupting the power supply to the load Note The Company provides this accessory already pre assembled in an IP65 plastic box...

Страница 24: ...the indications given in the TRI POWER X33 HE internal protections section OUTPUT switch isolator compliant with the indications given in the TRI POWER X33 HE internal protections section SERVICE BYPA...

Страница 25: ...X33 HE manual IMPORTANT make sure that SWBATT fuse holders of the TRI POWER X33 HE and Battery Box are open Before making any connection read carefully the instructions in the Battery Box manual Conn...

Страница 26: ...to measure the temperature inside a remote Battery Box It is essential that only the kit provided by the manufacturer is used Any uses not conforming to the specifications may cause faults or breakdo...

Страница 27: ...of battery efficiency The TRI POWER X33 HE block diagram is shown below with a description of its individual components TRI POWER X33 HE block diagram IMPORTANT Our TRI POWER X33 HEs are designed and...

Страница 28: ...ecting the TRI POWER X33 HE to the Battery Box optional paragraph the battery fuses and other protections may result damaged In that case please contact the Customer Service department in order to pre...

Страница 29: ...e indications on the terminal board Close the protective panel again Repeat the preliminary operations given in the previous page Press the button to access the start up menu Press YES when requested...

Страница 30: ...turn on Press the button to access the start up menu When requested to confirm press YES and then press the button again to confirm All LEDs on display will turn on for about a second and the buzzer...

Страница 31: ...e pages containing all the data referred to the menu chosen Tri Power X33 HE Status Errors Faults This area of the display shows the TRI POWER X33 HE operating status The first line is always active a...

Страница 32: ...Page 31 to 52 Menu display...

Страница 33: ...is restored the load is powered off again The activation time is less than 0 5 seconds Maintenance bypass SWMB WARNING Maintenance inside the TRI POWER X33 HE must be carried out by qualified personn...

Страница 34: ...h enables under certain operating circumstances the automatic disconnection of the load applied to it The events that determine this automatic disconnection of the power share socket can be selected b...

Страница 35: ...neutral loads In case the output voltage is set to 200V or 208V PHASE NEUTRAL see the Configuring the TRI POWER X33 HE paragraph the maximum power output of the TRI POWER X33 HE is reduced compared to...

Страница 36: ...utonomy limitation Sets the maximum time of battery operation Disabled Disabled complete battery discharge 1 65000 in steps of 1 sec SW Low battery pre alarm Sets the estimated autonomy time left for...

Страница 37: ...ty Enabled High sensitivity Enabled Low sensitivity Disabled with input output synchronisation Disabled without input output synchronisation SW Inverter synchronization External Sync Selects the synch...

Страница 38: ...nector automatically excludes the other Expansion slots for additional COMMUNICATION SLOT interface boards AS400 port Moreover on the rear of the TRI POWER X33 HE it is possible to install as an optio...

Страница 39: ...SNMP protocol RS232 RS485 port with JBUS MODBUS protocol For further information on the accessories available please visit the website AS400 Port PIN NAME TYPE FUNCTION 1 15V POWER Isolated auxiliary...

Страница 40: ...icates that the batteries are about to run out when contact 5 12 is closed 1 6 13 14 BATTERY WORKING OUTPUT 2 Indicates that the TRI POWER X33 HE is running on battery power when contact 6 14 is close...

Страница 41: ...beep Sound B This signal is made when the TRI POWER X33 HE commutates to bypass in order to compensate the surge current due to the insertion of a distorting load Sound C This signal is emitted when...

Страница 42: ...en by the installation program For further information on how to install and use the software please consult the manual provided in the Manuals folder of the CD Rom provided To check for a more recent...

Страница 43: ...HE INPUT TERMINAL MISSING Connect the mains to the terminals following the indications in the paragraph on Installation NEUTRAL CONNECTION MISSING The TRI POWER X33 HE cannot operate without the neutr...

Страница 44: ...OBE Activate the maintenance bypass SWMB turn the TRI POWER X33 HE off and back on again and exclude the maintenance bypass If the problem persists contact the nearest service centre THE DISPLAY SHOWS...

Страница 45: ...see TRI POWER X33 HE internal protections THE DISPLAY SHOWS THE CODE S06 THE BATTERIES ARE DISCHARGED THE TRI POWER X33 HE WAITS FOR THE BATTERY VOLTAGE TO EXCEED THE SET THRESHOLD Wait for the batter...

Страница 46: ...40 C HEAT SOURCES CLOSE TO THE TRI POWER X33 HE VENTILATION SLITS OBSTRUCTED OR TOO CLOSE TO THE WALLS FAULT IN THE TEMPERATURE PROBE OR IN THE BATTERY CHARGER COOLING SYSTEM Eliminate the cause of t...

Страница 47: ...e S08 Economy mode enabled S09 Ready for start up S10 TRI POWER X33 HE locked load not powered S11 TRI POWER X33 HE locked load on bypass S12 BOOST stage or battery charger locked load not powered Com...

Страница 48: ...equency out of tolerance limits A18 Voltage on bypass line out of tolerance limits A19 High current peak on phase 1 output A20 High current peak on phase 2 output A21 High current peak on phase 3 outp...

Страница 49: ...Wrong cyclic sense of the bypass phases F14 Inverter phase 1 sine curve distorted F15 Inverter phase 2 sine curve distorted F16 Inverter phase 3 sine curve distorted F17 Inverter stage anomaly F19 Po...

Страница 50: ...L16 Phase 3 inverter overvoltage L17 Phase 1 inverter undervoltage L18 Phase 2 inverter undervoltage L19 Phase 3 inverter undervoltage L20 Continuous voltage at inverter output or Sine curve of Phase...

Страница 51: ...In for t 500ms Precision of output voltage referred to a 400Vac output voltage 1 Static stability 4 0 5 Dynamic stability 3 resistive load 5 Voltage harmonic distortion with linear and normalised dis...

Страница 52: ...In order to keep the output voltage within the indicated precision range a recalibration may be necessary following a long period of use 3 If the mains frequency is within 5 of the selected value the...

Страница 53: ...k energy com France and Benelux fbnl alpha outback energy com Spain spain alpha outback energy com Russia russia alpha outback energy com Africa africa alpha outback energy com Alpha and Outback Energ...