Electromagnetic compatibility
This TRI POWER X33 HE product conforms to the current electromagnetic compatibility (EMC) regulations (C2
class). It may cause radio interference in the home environment. The user may have to adopt supplementary
measures.
This product is for professional use in industrial and commercial environments. Connections to USB and RS232
connectors must be made with the cables provided, or at least with shielded cables less than 3 metres long.
Installation environment
As for the installation area of the TRI POWER X33 HE, and, if necessary, of the Battery Box, follow carefully the
following instructions:
Avoid dusty environments
Make sure that the floor is level and that it is able to withstand the weight of the TRI POWER X33 HE (and of
the Battery Box)
Avoid environments which are too narrow, as they could impede normal maintenance operations
The relative humidity should not exceed 90% with no condensation
Make sure that the ambient temperature remains between 0 and 40°C while the TRI POWER X33 HE is
operating
This TRI POWER X33 HE can operate with an ambient temperature between 0 and 40°C. The
recommended working temperature for the TRI POWER X33 HE and the batteries is between 20
and 25°C. In fact, with a working temperature of 20°C, a battery has an average operating life of 5
years, whilst with a working temperature of 30°C the operating life is halved.
Avoid positioning the TRI POWER X33 HE in places exposed to direct sunlight or hot air
To maintain the temperature in the installation area within the above mentioned range, there must be a system to
dispose of the dissipated heat (the kW / kcal/h / B.T.U./h values dissipated by the TRI POWER X33 HE are shown in
the table in the previous page). The methods that can be used are the following:
Natural ventilation
Forced ventilation, recommended when the external temperature is lower (e.g. 20°C) than the temperature at
which the TRI POWER X33 HE or the Battery Box has to be operated (e.g. 25°C)
Air-conditioning system, recommended when the external temperature is higher (e.g. 30°C) than the
temperature at which the TRI POWER X33 HE or the Battery Box has to be operated (e.g. 25°C)