UPS Functional Descriptions

3.1. 

Front Panel Display

3.1.1.  CONTINUITY PLUS < Convertible Type (Rack / Tower) < LED Panel 

(Standard) 

Control Key 

Symbol 

Description 

ON(Alarm Silence) 

a. UPS Power-On Switch

(Press and hold until the buzzer beeps.)

b. Alarm silence

c. Error Code Display Function Mode

After an alarm, press to mute the alarm buzzer and

show an Error Code. (Do not hold for > 1 second.)

OFF 

UPS Power-Off Switch 

(Press and hold until the buzzer beeps.) 

Self-Test 

a. Commands the UPS to perform self-testing

(Press and hold until the buzzer beeps.)

b. Battery and Load Display Function Mode (Do

not hold for > 1 second.)

 Manual Bypass

Press the "ON" key and "Self-Test" key simultaneously 

for three seconds to transfer from "Inverter to Bypass" 

(The bypass LED will continuously blink and the buzzer 

will beep intermittently.) or "Bypass to Inverter" when 

the UPS is in on-line mode and the Bypass Voltage 

Window is Normal. 

LED Indicator 

Symbol 

Description 

Normal Mode LED 

1. Solid indicates normal utility voltage.

Blinking indicates insufficient utility voltage

for the full load. Off indicates abnormal utility

voltage.

2. In Battery and Load Function Mode

indicates battery capacity is 50%.

Battery Mode LED 

1. Indicates load supplied by battery power.

2. In Battery and Load Function Mode

indicates battery capacity is 25%.

Bypass Mode LED 

1. Indicates load supplied by bypass.

2. In Battery and Load Function Mode

indicates battery capacity is 75%.

Battery   

Bad/Weak LED 

1. Indicates  low  battery  power  or  faulty

battery bank.

2. In Battery and Load Function Mode

indicates battery capacity is 100%.

Fault LED 

1. Solid indicates fault or abnormal condition.

2. Blinking  indicates  LED  Panel  in  Error

Code Function Mode.

Overload LED 

1. Indicates UPS is overloaded.

2. In  Error Code  Function  Mode  indicates

Error Code 16.

Site wiring fault LED 

1. Indicates live and neutral lines are

connected wrongly or high neutral-ground

voltage.

2. In Battery and Load Function Mode

indicates load capacity is 100%.

3. In  Error Code  Function  Mode  indicates

Error Code 8.

Outlet1 LED 

1. Indicates UPS Outlets 1 are enabled and

ready to supply loads. (This function is

optional.)

2. In Battery and Load Function Mode

indicates load capacity is 75%.

3. In  Error Code  Function  Mode  indicates

Error Code 4.

Page 

8

 to 

47

Page 

9

 to 

47

Содержание Continuity 1000

Страница 1: ...Continuity 1000 3000 USER MANUAL...

Страница 2: ...4 4 Installation and Operation 15 4 1 Unpacking 15 4 2 Selecting Installation Position 18 4 3 Operation 19 5 UPS System Block Diagram 33 6 Maintenance Guide 35 6 1 Troubleshooting 35 6 2 Error Codes a...

Страница 3: ...ironments can damage any UPS Install the UPS indoors as it is not designed for installation outdoors 7 To prevent overheating of the UPS keep all ventilation openings free from obstruction and do not...

Страница 4: ...it is not likely to be contacted by people 25 The maximum ambient operating temperature is 40 C o r equivalent 26 Units are considered acceptable for use in a maximum ambient 40 C 27 CAUTION RISK OF...

Страница 5: ...2 2 1 Our High Frequency Transformer less technology and tower convertible enclosure enables the UPS to be integrated into even the most difficult environments with space constraints 2 2 2 This UPS is...

Страница 6: ...voltage for the full load Off indicates abnormal utility voltage 2 In Battery and Load Function Mode indicates battery capacity is 50 Battery Mode LED 1 Indicates load supplied by battery power 2 In B...

Страница 7: ...ack Tower LCD panel Item Sign Description LCD Display Green LED steadily lights up to indicate that the Utility input voltage is within the window 160Vac 288Vac the LED flashes flickeringly to indicat...

Страница 8: ...utput circuit breaker for two outlets 10 AC outlets Program Relay 11 AC outlet Remark Optional function Item Sign Description 1 Bypass Input Abnormal UPS fails to transfer to bypass Bypass Abnormal at...

Страница 9: ...first 1 EPO ROO input port 2 Optional interface card 3 Optional USB 4 RS 232 3 3 1 True RS 232 The RS 232 interface must be configured as follows Pin Assignments Pin 3 RS 232 Rx Pin 2 RS 232 Tx Pin 5...

Страница 10: ...4 1 1 Installation Instructions Tower installation Rack Mount installation Step 1 Step 2 Step 3 Page 16 to 47 Page 17 to 47...

Страница 11: ...the UPS main power cord into the utility AC power source receptacle 4 Switch on the AC power source All of the LEDs on the front panel display will flash once after five seconds At the same time the...

Страница 12: ...g fans will continue to operate Switch off the AC power source The ventilating fans will stop The UPS is now completely shut down 2 Shutdown in DC Mode Press and hold the OFF button for five seconds u...

Страница 13: ...n you see figure B means the starting up procedure is finished Please ensure UPS recharge in line mode for at least 4 hours for fully recharged before the first backup test if it s a new installed uni...

Страница 14: ...y 1 UPS measurements can be checked after UPS started by pressing select key The display sequence are as below figure F AC input voltage figure G AC input frequency figure H UPS output voltage figure...

Страница 15: ...eard d Unplug AC input power cord or turn off power source switch e After UPS completely shut off UPS is unlocked 4 3 2 5 UPS Default Data and Special Function Execution After the UPS completely start...

Страница 16: ...is 3 Hz U inverter output voltage V1 The UPS is operating in normal mode V2 The UPS is operating in Eco mode V3 The UPS is operating in CVCF 50 Hz mode V4 The UPS is operating in CVCF 60 Hz mode W Out...

Страница 17: ...3 3 7 Figures V1 V2 V3 and V4 indicate the operation modes of the UPS Possible values are Online Eco Economical mode fixed 50 Hz Output and fixed 60 Hz Output 4 3 3 8 Figure W indicates the adjustmen...

Страница 18: ...ce per second Battery low Quick and short successive beeps Confirm RS 232 port receiving two quick and short beeps Service mode okay one quick and short beep 5 UPS System Block Diagram Figure 4 1 Figu...

Страница 19: ...11 UPS Over Temperature 3 Remove any objects obstructing the ventilation louvers Verify that the cooling fans are working properly Contact your local dealer to replace the fans if necessary 4 Site wir...

Страница 20: ...ches back and forth between battery and utility modes 1 A power strip is connected to the UPS See if there is any damage to the utility wall receptacle or if the cord plug is faulty 1 Do not use the p...

Страница 21: ...saved your data in any open computer applications before you proceed with this battery test Code Meaning Er05 Battery weak or faulty Er06 Output short circuited Er07 EPO mode Er11 UPS over temperatur...

Страница 22: ...contact 4 Inverter On 5 Battery Low 6 Battery Bad or Abnormal 7 UPS Alarm 8 Common 9 Shutdown UPS positive signal 10 Shutdown UPS negative signal 8 3 2 8 3 3 8 3 4 8 3 5 8 3 6 The shutdown function wi...

Страница 23: ...0 9 900 1800 2700W INPUT Voltage Rating 110 150 180 300 VAC Based on load percentage0 60 0 75 0 100 Frequency Rating 45 65 Hz Phase Single phase with ground Power Factor 0 99 with full linear load Ge...

Страница 24: ...cy Full Linear Load Line mode Rating 230Vac 90 91 91 Battery mode 12Vdc pcs 86 87 87 ECO mode Rating 230Vac 97 97 97 MODEL ITEM CONTINUITY PLUS 1K CONTINUITY PLUS 2K CONTINUITY PLUS 3K Battery Sealed...

Страница 25: ...ctronic Circuit Battery ABDM EPO UPS shuts down immediately Over Temperature Normal Mode Transfer to Bypass Mode Battery Mode UPS shuts down immediately Physical Dimensions UPS inches W x H x D mm 17...

Страница 26: ...k energy com France and Benelux fbnl alpha outback energy com Spain spain alpha outback energy com Russia russia alpha outback energy com Africa africa alpha outback energy com Alpha and Outback Energ...

Отзывы: