1. Safety Instructions and Storage/ Battery Care

1.1.  Safety Instructions 

SAVE THESE INSTRUCTIONS. 

This  manual  contains  important  instructions  that  should  be  followed  during 

installation and maintenance of the UPS and batteries. 

1. Do not open the case as there are no serviceable parts inside. Opening the

case will void your warranty and introduces the risk of electric shock.

2. Do not try to repair the unit yourself. Doing so will void your warranty. Contact

your local supplier for repairs.

3. If liquids are spilt onto the UPS or foreign objects dropped into the unit the

UPS could be damaged, users could be subject to electric stock, and the

warranty will become null and void.

4. Do not install the UPS in an environment with sparks, smoke, or hazardous

gas.

5. This UPS is equipped with an EMI filter. To prevent potential leakage current

hazards ensure that the AC mains supply is securely grounded. Because of

small leakage currents generated by the EMI filter in the UPS it is necessary

to double check that the ground wire of the UPS is properly grounded before

connecting the UPS to the AC mains

6. This UPS is designed to be installed and commissioned in a sheltered,

controlled environment as follows:

 Ensure that the UPS is installed within the proper environmental range. 

(0-40°C  and  0-90%  non-condensing  humidity).  High  ambient 

temperature reduces battery life. 

 Do not install the UPS in direct sunlight. Your warranty may be void if 

the batteries fail 

 Do  not  install  the  UPS  in  an  inflammable  or  otherwise 

hazardous environment. 

 Avoid vibration and areas subject to physical impact. 

 Avoid any area with sparks. 

 Dusty, corrosive, and salty environments can damage any UPS. 

 Install the UPS indoors as it is not designed for installation outdoors. 

7.

To  prevent  overheating  of  the  UPS  keep  all  ventilation  openings  free

 

from obstruction, and do not place anything on top of the UPS. Keep the

 

UPS rear panel 20 cm away from the wall or other obstructions.

8.

Install  the  UPS  in  a  ventilated  area,  ideally  exchanging  5  m

of  air  per

 

hour,  because  the  chemical  reaction  during  battery  charging  causes

 

trace  gas  production.  If  the  batteries  suffer  breakage  electrical  arcing

 

could occur in the UPS interior.

9.

If the product emits a strange noise or smell please immediately stop

 

using 

the product and contact your dealer for maintenance.

10.

Always switch off the UPS and disconnect the batteries when relocating

 

the 

UPS.  Be  aware  that,  even  when  disconnected,  charged  batteries

 

present 

a possible electric shock hazard.

11.

The UPS should be recharged every 2-3 months if unused. If this is not

 

done then the warranty will be null and void. When installed and being

 

used  the  batteries  will  be  automatically  recharged  and  kept  in  top

 

condition.

12.

Make sure that the AC utility outlet is correctly grounded.

13.

Ensure  that  the  input  voltage  of  the  UPS  matches  the  utility  supply

 

voltage.  Use a  certified  input power  cable  with  the correct plugs  and

 

sockets for the system voltage.

14.

To ensure safety in all applications where a UPS is hard wired to the

 

electrical  supply,  ensure  that  the  system  is  installed  by  a  qualified

 

electrical contractor.

15.

The  UPS  has  its  own  internal  energy  source  (battery).  Should  the

 

battery be switched on when no AC power is available there could be

 

voltage at the output terminals.

16.

Make sure that the AC utility outlet is correctly grounded

17.

Install the UPS away from objects that give off excessive heat and

 

areas 

that are excessively wet.

Page 

2

 to 

47

Page 

3

 to 

47

Содержание Continuity 1000

Страница 1: ...Continuity 1000 3000 USER MANUAL...

Страница 2: ...4 4 Installation and Operation 15 4 1 Unpacking 15 4 2 Selecting Installation Position 18 4 3 Operation 19 5 UPS System Block Diagram 33 6 Maintenance Guide 35 6 1 Troubleshooting 35 6 2 Error Codes a...

Страница 3: ...ironments can damage any UPS Install the UPS indoors as it is not designed for installation outdoors 7 To prevent overheating of the UPS keep all ventilation openings free from obstruction and do not...

Страница 4: ...it is not likely to be contacted by people 25 The maximum ambient operating temperature is 40 C o r equivalent 26 Units are considered acceptable for use in a maximum ambient 40 C 27 CAUTION RISK OF...

Страница 5: ...2 2 1 Our High Frequency Transformer less technology and tower convertible enclosure enables the UPS to be integrated into even the most difficult environments with space constraints 2 2 2 This UPS is...

Страница 6: ...voltage for the full load Off indicates abnormal utility voltage 2 In Battery and Load Function Mode indicates battery capacity is 50 Battery Mode LED 1 Indicates load supplied by battery power 2 In B...

Страница 7: ...ack Tower LCD panel Item Sign Description LCD Display Green LED steadily lights up to indicate that the Utility input voltage is within the window 160Vac 288Vac the LED flashes flickeringly to indicat...

Страница 8: ...utput circuit breaker for two outlets 10 AC outlets Program Relay 11 AC outlet Remark Optional function Item Sign Description 1 Bypass Input Abnormal UPS fails to transfer to bypass Bypass Abnormal at...

Страница 9: ...first 1 EPO ROO input port 2 Optional interface card 3 Optional USB 4 RS 232 3 3 1 True RS 232 The RS 232 interface must be configured as follows Pin Assignments Pin 3 RS 232 Rx Pin 2 RS 232 Tx Pin 5...

Страница 10: ...4 1 1 Installation Instructions Tower installation Rack Mount installation Step 1 Step 2 Step 3 Page 16 to 47 Page 17 to 47...

Страница 11: ...the UPS main power cord into the utility AC power source receptacle 4 Switch on the AC power source All of the LEDs on the front panel display will flash once after five seconds At the same time the...

Страница 12: ...g fans will continue to operate Switch off the AC power source The ventilating fans will stop The UPS is now completely shut down 2 Shutdown in DC Mode Press and hold the OFF button for five seconds u...

Страница 13: ...n you see figure B means the starting up procedure is finished Please ensure UPS recharge in line mode for at least 4 hours for fully recharged before the first backup test if it s a new installed uni...

Страница 14: ...y 1 UPS measurements can be checked after UPS started by pressing select key The display sequence are as below figure F AC input voltage figure G AC input frequency figure H UPS output voltage figure...

Страница 15: ...eard d Unplug AC input power cord or turn off power source switch e After UPS completely shut off UPS is unlocked 4 3 2 5 UPS Default Data and Special Function Execution After the UPS completely start...

Страница 16: ...is 3 Hz U inverter output voltage V1 The UPS is operating in normal mode V2 The UPS is operating in Eco mode V3 The UPS is operating in CVCF 50 Hz mode V4 The UPS is operating in CVCF 60 Hz mode W Out...

Страница 17: ...3 3 7 Figures V1 V2 V3 and V4 indicate the operation modes of the UPS Possible values are Online Eco Economical mode fixed 50 Hz Output and fixed 60 Hz Output 4 3 3 8 Figure W indicates the adjustmen...

Страница 18: ...ce per second Battery low Quick and short successive beeps Confirm RS 232 port receiving two quick and short beeps Service mode okay one quick and short beep 5 UPS System Block Diagram Figure 4 1 Figu...

Страница 19: ...11 UPS Over Temperature 3 Remove any objects obstructing the ventilation louvers Verify that the cooling fans are working properly Contact your local dealer to replace the fans if necessary 4 Site wir...

Страница 20: ...ches back and forth between battery and utility modes 1 A power strip is connected to the UPS See if there is any damage to the utility wall receptacle or if the cord plug is faulty 1 Do not use the p...

Страница 21: ...saved your data in any open computer applications before you proceed with this battery test Code Meaning Er05 Battery weak or faulty Er06 Output short circuited Er07 EPO mode Er11 UPS over temperatur...

Страница 22: ...contact 4 Inverter On 5 Battery Low 6 Battery Bad or Abnormal 7 UPS Alarm 8 Common 9 Shutdown UPS positive signal 10 Shutdown UPS negative signal 8 3 2 8 3 3 8 3 4 8 3 5 8 3 6 The shutdown function wi...

Страница 23: ...0 9 900 1800 2700W INPUT Voltage Rating 110 150 180 300 VAC Based on load percentage0 60 0 75 0 100 Frequency Rating 45 65 Hz Phase Single phase with ground Power Factor 0 99 with full linear load Ge...

Страница 24: ...cy Full Linear Load Line mode Rating 230Vac 90 91 91 Battery mode 12Vdc pcs 86 87 87 ECO mode Rating 230Vac 97 97 97 MODEL ITEM CONTINUITY PLUS 1K CONTINUITY PLUS 2K CONTINUITY PLUS 3K Battery Sealed...

Страница 25: ...ctronic Circuit Battery ABDM EPO UPS shuts down immediately Over Temperature Normal Mode Transfer to Bypass Mode Battery Mode UPS shuts down immediately Physical Dimensions UPS inches W x H x D mm 17...

Страница 26: ...k energy com France and Benelux fbnl alpha outback energy com Spain spain alpha outback energy com Russia russia alpha outback energy com Africa africa alpha outback energy com Alpha and Outback Energ...

Отзывы: