5. Installation
WARNING!
The Alpha FXM module MUST be correctly grounded for proper operation.
The input and output lines to and from the Alpha FXM MUST have disconnect devices attached.
The Alpha FXM must be installed in a restricted area accessible only by qualified service personnel.
Once the installation location has been planned and prepared, you are ready to install the Alpha FXM. There are
three steps to setting up the Alpha FXM:
1. Mounting the Alpha FXM
2. Wiring the external batteries
3. Wiring the Alpha FXM
5.1 Tools and Equipment Required for Installation
DC voltmeter.
Labels or masking tape and marker.
Torque wrench for input/output terminal blocks.
Slot head screwdriver to fit the terminal blocks.
Minimum #10 AWG copper wire for input/output terminal blocks.
High strength, flame-proof tape such as duct tape.
Battery terminal corrosion inhibitor such as NOCO Company NCP-2 or Sanchem Inc. No-Ox ID Grease “A”.
5.2 Mounting the Alpha FXM
The Alpha FXM can be placed on a shelf with no other parts needed. Any version of the FXM can be rack or wall
mounted or secured to a shelf, such as on an outdoor enclosure shelf, with the optional mounting brackets as
shown in the figure below The brackets and the screws to attach them to the Alpha FXM case are available from
Alpha and Outback Energy (part number 740-697-21).