Charge Controller Settings
900-0117-01-00 Rev A
99
Grid Tie Mode
IMPORTANT:
Grid-Tie Mode requires an inverter that is grid-interactive, (also known as grid-tied or
grid-tie enabled.) Not all inverters are grid-interactive. If the MATE3 is connected to an
inverter that is not grid-interactive, Grid-Tie Mode will not function if selected.
This menu allows the charge controller to work more effectively with any grid-interactive inverters present
on the HUB. When enabled, this setting automatically raises the charge controller’s Float voltage to equal
its Absorption voltage. Since the inverter sells power to maintain its own Float, Absorption, or Sell settings
(all of which should be lower than those of the controller), this mode makes it easier for the inverter to
sell power.
NOTE:
The charge controller’s Float voltage returns to normal any time the inverter enters
PassThru
or
Silent
To
access
the
Grid Tie Mode
menu:
1.
Access the
Charge Controller
menu as shown in Figure 90 on page 94.
2.
Use the control wheel to highlight the
Grid Tie Mode
menu.
Press the button in the center of the control wheel to accept the selection.
3.
Use the control wheel to increase or decrease the set points to the correct voltage.
Press the button in the center of the control wheel to accept the selection.
This should automatically move the highlighting to the next set point.
4.
After setting the parameters for each set point, press the
TOP
navigation key to return to the
Main Menu
screen.
Figure 95
Grid Tie Mode
Set Points:
Two options are available in this menu;
N
and
Y
.
~
N
(No) disables Grid-Tie Mode;
~
Y
(Yes) enables it.
Y/N
Содержание OutBack Power MATE3
Страница 1: ...MATE3 System Display and Controller Owner s Manual ...
Страница 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Страница 159: ......