19 / 55
Installation
This Manual introduces the basic steps of how to install and set up AlphaESS Storion-
SMILE-T10
M4856-S is a sealed component with no access to battery terminals or cell
components within module.
NOTE: please pay attention to unpacking the battery, the worst case is that
some components could be damaged.
2.1
Installation Site and Environment
2.1.1
General
The M4856-S has two versions, one is indoor, and the other is outdoor. This SMILE-
T10 energy storage system (indoor version) can only be installed in an indoor
location. This SMILE-T10 energy storage system (outdoor version) can be installed in
both outdoor and an indoor location.
If SMILE-T10 system is installed in a room, it shall be located so that access to SMILE-
T10 is not obstructed by the structure of the building, fixtures and fittings within the
room.
SMILE-T10 adopts natural ventilation. The location should be clean, dry and
adequately ventilated. The room’s entry doors and panels shall open in the direction
of egress and allow unobstructed access to the SMILE-T10 for installation and
maintenance purposes.
The following location are not allowed for installation:
•
habitable rooms;
•
in ceiling spaces;
•
wall cavities;
•
on roofs not specifically deemed suitable;
•
areas of access/egress;
•
under stairways;
•
under access walkways;
•
sites where the freezing point is reached, like garages, carports or other
places;
•
sites with humidity and condensation over 85%;
•
sites which are salty and where humid air can penetrate;