this emergency input device has been activated. For example, on a pull cord you could set a 10 second delay. This delay would 

allow the device to be reset within 10 seconds before any calls, relays, or notification are made. This is useful if you often 

have accidental emergency calls placed that are often reset a few seconds later. If the device is reset within this number of 

seconds it will be as if the call was never placed.

•  Play reminder tone

 - This option will automatically turn the tone back on for an emergency call that has been silenced, but 

has not been reset or closed from the list of calls. The tone will turn back on after the number of seconds specified has passed 

since the tone was last silenced. The tone for a call can be then silenced again after it is turned back on and will play again 

after the specified number of seconds passes.

 

»

Call Device Types: Display

•  Icon Image

 - On the Master(s) this emergency call is displayed on you can select from a list of icons that will be shown.

•  Icon Color

 - On the Master(s) this emergency call is displayed on you can select the color that will be used for the icon.

 

»

Call Device Types: Relays

ECI333 Relay  

- Only if this type of input is for a 

Wired ECI333 

will you see this box. The ECI333 input has a relay built into it 

that can be triggered when an emergency call is placed. The relay has four different states that can be selected from:

•  Off

 (open) - select this option to not use the relay.

•  Toggle

 

Slow

 - select this option to flash a dome light slowly for lower priority calls.

•  Toggle

 

Fast

 - select this option to flash a dome light quickly for higher priority calls.

• 

On

 (closed) - select this option to hold the relay closed to turn on a dome light or other device.

Only activate relay for this many seconds 

- With the ECI333 relay if you would like to only activate the slow, fast, or on state 

relay for a specific number of seconds enter that number in this text box. This is optional and if not used the relay will remain 

active until the call is reset/closed.

Activate Relay (RY008AE) 

- With AlphaECall™ 200 you can connect external relay boards to trigger up to two relays per activa

-

tion when any type of emergency call is received. To configure these relay boards you need to specify the Relay Board # (1-16) 

and the Relay # (1-8) that you would like to trigger. The relay will stay active until the call is reset/closed or you can specify the 

number of seconds you would like the relay to stay active for, using the ‘Active Seconds’ option. Also, you can specify a delay 

in the relay activation. For example, if a call is not reset/closed in 300 seconds (5 minutes), it can then trigger a relay for a 

strobe or a siren to alert staff of an emergency call.

 

»

 Call Device Types: Notifications

•  Text Message Notification 

- When an emergency call is received for an input device type you can set a specific text 

message to send a notification to or you can select from any Staff Members who have cell phone numbers configured 

in their settings. Text messages can also be used as an elevated notification, by using the delay option for a specified 

number of seconds, if you do not want text messages sent out right away.

•  Pager Notification

 - When an emergency call is received by AlphaECall™ 200 a notification can be sent to pagers at an 

installation. You can either specify an 8 digit Capcode to send the notification to or select from a list of Staff Members 

who have pagers configured in their settings. Paging can also be used as an elevated notification, by using the delay 

option for a specified number of seconds, if you do not want pages sent out right away.

•  Family Notification

 - If you want to allow this type of input device to be able to alert family members of a resident place 

a checkmark next to this option. Any residents who then have a cell phone number of a family member configured in 

their settings will be notified automatically when an emergency occurs. Family notifications also have a delay option for a 

specified number of seconds, if you do not want family text messages sent out right away. 

 

»

Call Device Types: Central Station

To enable the ability for this type of input device to communicate to a Central Station/Alarm Monitoring service place a 

checkmark next to this “Contact Central Station”. The phone number that is configured in the Central Station menu item will 

be used to send data when an emergency call is received. Central Station communication can also be used as an elevated 

level of notification, by using the delay option for a specified number of seconds, if you do not want central station dialing to 

be done right away.

 

After making any changes to an Input Device Type you must click the ‘Save’ button to apply them.

29

Содержание AEC200DM

Страница 1: ...Configuration Manual Alpha Communications and Alpha Media Inc 42 Central Drive Farmingdale NY 11735 1202 Phone 631 777 5500 Fax 631 777 5599 http www alphacommunications com Copyright 2016 2018 Alpha...

Страница 2: ...mponents 10 ECI333 12 AlphaECall 200 QwikBUS Wiring Diagram 13 STR QwikBUS Wiring Requirements 13 Typical Room Wiring for Devices to ECI333 14 Wiring Alpha Communications U L 1069 Devices to ECI333 15...

Страница 3: ...Types Notifications 29 Call Device Types Central Station 29 Residents 30 Residents General 30 Residents Notes 30 Residents Wireless Pendants 30 Residents Notification Tab 31 Residents Photo 31 Staff M...

Страница 4: ...ou fail to comply with the terms and conditions of this EULA In such event you must destroy all copies of the SOFTWARE PRODUCT 4 COPYRIGHT All title including but not limited to copyrights in and to t...

Страница 5: ...rtant to know what other types of wires may be run alongside QwikBUS wiring to prevent interference Wiring will be explained in more detail later in the manual AlphaECall 200 QwikBUS Wiring Diagram on...

Страница 6: ...t will be used in your system They can be called anything that makes sense for your application Each device type has its own settings for priority level display options trigger actions and more When y...

Страница 7: ...e a display connected to it It can be used to connect additional serial hardware to your AlphaECall 200 system or just be used to backup your AlphaECall 200 database AEC200DM Visual Master Station AEC...

Страница 8: ...ake out carefully remove the bottom plate from the Master After the bottom plate is removed feed a network cable through one of the circular openings in the bottom plate and then plug the cable into t...

Страница 9: ...playing on all masters and the date and time the silence button was pressed will be stored At the bottom of the screen there are three tab icons displayed Calls clicking will display all current emer...

Страница 10: ...tral station alarm service to automatically let them know an emergency call has taken place Relay Boards RY008AE these can be used to tie in other types of notification devices to AlphaECall When an e...

Страница 11: ...tation VPS101 Wired LED Emergency Single Bed Station VPS102 Wired LED Emergency Double Bed Station SF301 8 8 Foot Bed Station Call Cord Available in 10 15 and 20 Foot Lengths Use with VPS Series Bed S...

Страница 12: ...contact inputs on it S1 and S2 that can be used for emergency calls You can connect any type of dry contact device to the S1 and S2 inputs The ECI333 also has a relay that can be activated when an eme...

Страница 13: ...hey are still susceptible to RFI from unusually strong nearby transmitters EMI from electrical lines running nearby or existing wiring that is not twisted in poor condition or not of a suitable gauge...

Страница 14: ...with a suitable isolation relay This diagram illustrates using a Double Pole Single Throw Emergency Switch SF119 2A to close the S1 contact on one side to send the emergency call and also closes the c...

Страница 15: ...Wiring Alpha Communications U L 1069 Devices to ECI333 EPS155 Emergency Push Pull Switch EPS337 Water Resistant Emergency Push Pull Switch 15...

Страница 16: ...EPS339 Mushroom Button Emergency Push Switch EPS156 Code Blue Push Pull Switch 16...

Страница 17: ...VSS110 Staff Station VPS101 VPS102 Patient Bed Stations 17...

Страница 18: ...call is placed The system size can be scaled as needed Repeaters are not required in all wireless networks If you have a small location and you are using only fixed devices repeaters may not be needed...

Страница 19: ...ter Resistant Use with WSM537 Support Module WES556 Wireless LED Code Blue Pull Cord Station Use with WSM555 Support Module WSM517 Wireless Support Module 2 Pin WSM555 Wireless Support Module 6 Pin WS...

Страница 20: ...t 2 Week Rental WRR504 Wireless Relay Controller 4 Relays WRR512 Wireless Relay Controller 12 Relays WRR516 Wireless Relay Controller 16 Relays IHS527 Quick Snap Surface Housing 2 55 Deep ACC500K Wire...

Страница 21: ...pager transmitter TX125 ENC needs to be connected to one of the AlphaECall 200 Masters and any number of pocket pagers PGR AL924 can be alerted for emergency calls When an emergency call is placed Alp...

Страница 22: ...ff into different groups to specify which Masters display calls and which Staff members are alerted for calls dependant on Resident location See Setup Zones on page 23 Call Device Types This is where...

Страница 23: ...have renamed the zone be sure to click save to apply your changes You will be able to associate your various Masters Residents and Staff to their zone s in their respective areas Once you do this you...

Страница 24: ...ocation option enabled See Call Device Types Setup on page 28 for more information on setting up call devices type To configure the settings for a specific location first select it in this list You wi...

Страница 25: ...address from the device is received Once this is done Specify which type of Call Device this wireless devices will be treated as and click Save Locations Floor Plan If you are using Floor Plans you c...

Страница 26: ...onfigure the settings for a specific master click the list item with that master s name and you two tabs Setup and Options appear Masters Setup Master Name This is the name you would like to call this...

Страница 27: ...the map where that master is located After setting the correct floor plan image and clicking a coordinate click on the Save button See Setup Floor Plans on page 23 for more information Masters Adminis...

Страница 28: ...wo options to select from Wired ECI333 or Wireless Device to indicate how this device will communicate with AlphaECall 200 Series Find Location When using wireless devices that are not in a fixed loca...

Страница 29: ...oard 1 16 and the Relay 1 8 that you would like to trigger The relay will stay active until the call is reset closed or you can specify the number of seconds you would like the relay to stay active fo...

Страница 30: ...umber is clicked on it will place a phone call to that location Note The first and last name are optional for use in general locations like Lobby Office Cafeteria etc Residents Notes Resident Notes Co...

Страница 31: ...NG or GIF For more information on uploading your custom resident photos please see Uploading Images to your Master Stations on page 27 After making any changes in the Residents area you must click the...

Страница 32: ...st setup a secu rity code for one Staff person or multiple people Security codes are not required when creating Staff members Security Codes can also be used for login to the AlphaECall app When the A...

Страница 33: ...from when the call was placed to when the call was reset It will display the name of the resident their room number the type of input device used the initial call time the time the input device type...

Страница 34: ...ber or input device type Programmed Devices This report will give you a current list of all input devices programmed into AlphaECall The report will show the resident name and room number the device w...

Страница 35: ...wireless map to determine the location of a pendant As such repeaters must be configured with more care in a location finding facility than in a facility where repeaters are used solely for increased...

Страница 36: ...Figure RL 1 In this configuration the repeater may have difficulty differentiating between the two locations 36...

Страница 37: ...Figure RL 2 In this configuration the repeater will have an easier time differentiating between locations 37...

Страница 38: ...Figure RL 3 Arrange repeaters in triangle patterns to promote signal strength 38...

Страница 39: ...Figure RL 4 Offset triangles from floor to floor for maximum signal strength efficiency 39...

Страница 40: ...cated when an emergency call is placed Depending on how precise you want the accuracy of location finding to be you can create more locations in the Wireless Map area to be more specific or less locat...

Страница 41: ...your browser screen and click the button Stop Receiving Fingerprints Test Location Finding Perform a location test immediately after fingerprinting by activating a pendant in each locatable area and e...

Страница 42: ...Figure RL 5 The Compass Method of Fingerprinting 42...

Страница 43: ...ber of Repeaters for an Installation To achieve the 99 99 alarm message reliability system installations must operate within the following limits for end device and repeater counts End Devices Maximum...

Отзывы: