Make sure the ECI333 you wish to program is connected to your BUS. Once you
click
Program
, you will be prompted:
>
On the ECI333 you would like to program, momentarily short the ‘S1’ and ‘C’
screw terminals.
The programming frame will automatically close once an address from the device
is received. Once this is done, Specify which type of devices will be in the S1 and S2
inputs and click
Save.
The device on S1 should then be connected to S1 and C. The
device on S2 should then be connected to S2 and C.
Programming & Configuring a Stationary Wireless Device
Make sure you have the wireless device’s support module handy and have opened the
housing. Locate the rectangular reset button, pictured in the photograph to the right. Once
you click
Program
, you will be prompted:
> On the wireless device you would like to program, press and release the ‘Reset’ button.
The programming frame will automatically close once an address from the device is received.
Once this is done, Specify which type of Call Device this wireless devices will be treated as
and click
Save.
»
Locations: Floor Plan
If you are using Floor Plans, you can specify where on the Floor Plan this location is. Select the Floor Plan image from the
drop-down box, and then click on the map where that Location is. When a call is placed from this location, an image of your
floor plan with the master’s location beacon will be displayed. After setting the correct floor plan image and clicking a coordi
-
nate, click on the
Save
button. See “Setup: Floor Plans” on page 23 for more information.
»
Locations: Fingerprinting
If you are using ambulatory devices such as wireless pendants or wrist bands, and are using the fingerprinting function to
triangulate the calls placed by these devices, you will also need to program a fingerprinting pendant and then Fingerprint
each location as instructed here: “Fingerprinting to Establish Your Wireless Map” on page 41
After making any changes in the Locations area you must click the ‘Save’ button to apply them to that Location.
25
Содержание AEC200DM
Страница 16: ...EPS339 Mushroom Button Emergency Push Switch EPS156 Code Blue Push Pull Switch 16...
Страница 17: ...VSS110 Staff Station VPS101 VPS102 Patient Bed Stations 17...
Страница 36: ...Figure RL 1 In this configuration the repeater may have difficulty differentiating between the two locations 36...
Страница 37: ...Figure RL 2 In this configuration the repeater will have an easier time differentiating between locations 37...
Страница 38: ...Figure RL 3 Arrange repeaters in triangle patterns to promote signal strength 38...
Страница 39: ...Figure RL 4 Offset triangles from floor to floor for maximum signal strength efficiency 39...
Страница 42: ...Figure RL 5 The Compass Method of Fingerprinting 42...