background image

INSTALLATION GUIDE 

Page 4

 

EFM / ELB Series Installation Guide

 

START UP 

Once  all  connections  are  completed,  the  unit  should  be 
started up and a check of the completed system should 
be performed.  Before performing any system test make 
sure that all grilles, registers and dampers are open and 
set to the correct positions.  Also make certain that an air 
filter is installed in the return air prior to the Air Handler.  
A  performance  test  should  be  completed  in  accordance 
with  the  outdoor  equipment 

manufacturer’s  instructions.  

Airflow  test  should  be  conducted  in  the  heating  and 
cooling modes to ensure satisfactory operation. 

MAINTENANCE 

The  system  air  filter(s)  should  be  inspected,  cleaned  or 
replaced at least monthly.  If the filter is mounted internal 
to  unit,  make  sure  that  electrical  power  is  disconnected 
before  removing  the  access  panels.    Make  certain  that 
the  access  panels  are  replaced  and  secured  properly 
before placing the unit back in operation.  This product is 
designed  for  dependable  service;  however,  periodic 
maintenance  should  be  scheduled  to  be  conducted  by 
trained  professional  service  personnel.    This  service 
should  be  conducted  at  least  annually,  and  should 
include  testing  and  inspection  of  electrical  and 
refrigerant  components.    The  heat  transfer  surface 
should  be  cleaned.    The  blower  motor  is  permanently 
lubricated for normal operating conditions. 

SEQUENCE OF OPERATION 

Cooling  (cooling  only  or  heat  pump  with  reversing 
valve  energized  in  heat mode):

    When  the  thermostat 

calls for cooling, the blower relay is energized.  The N.O. 
contacts  will  close  after  a  time  delay, 

and 

the  indoor 

blower  will  operate.    The  circuit  between  R  and  Y  is 
complete

  which 

caus

es

  the  contactor  on  the  outdoor 

equipment  to  close

,

  and  start  the  compressor  and  the 

outdoor fan motor. 

Cooling  (heat  pump  with  reversing  valve  energized 
in  cooling  mode):

    When  the  thermostat  calls  for 

cooling,  the  circuit  between  R  and  G  and  R  and  O  is 
complete.    Circuit  R  and  O  energizes  the  reversing 
valve  to  the  cooling  position,  Circuit  R  and  G  energizes

 

the

  blower  relay.    The  N.O.  contacts  will  close  after  a 

time delay,

 and 

the  indoor  blower  will  operate.    The 

circuit  between R and Y is complete

, which 

caus

es

 the 

contactor on the outdoor equipment to close and start the 
compressor and the outdoor fan motor. 

Heating (electric heat only): 

 When the thermostat calls 

for  heat  the  circuit  between  R  and  W  is  complete, 

and 

the  heat  sequencer  is  energized.    A  time  delay  will 
occur

  which  allows 

the  heating  element(s)  and  the 

indoor blower motor

 to

 come on. 

Heating  (heat  pump  reversing  valve  energized  in 
heat  mode): 

  When  the  thermostat  calls  for  heat,  the 

circuits  between  R  and  B,  R  and  Y

,

  and  R  and  G  are 

complete.  Circuit R and B energize the reversing valve 
switching  it  to  the  heat  position.    Circuit  R  and  Y 
energized  the  outdoor  unit  contactor  starting  the 
compressor and outdoor fan.  Circuit R and G energizes 
the blower relay starting the blower motor. 

If  the  indoor  room  temperature  should  continue  to  fall, 
circuit R and W2 is by the second-stage heat bulb on the 
thermostat.  Circuit R-W2 energizes the heat sequencer.  
The  completed  circuit  will  energize  the  supplemental 
electric heat. 

Blower Time Delay: 

 This unit is equipped with timed on 

and  a  timed  off  relay.    This  relay  delays  the  start  and 
delays the stopping of the indoor fan motor to maximize 
the efficiency of the unit. 

Defrost:

   

When  the  unit  starts  the  defrost  cycle 

s

upplemental  heat  during  defrost  can  be provided  by 

connecting  B  on  the  blower  coil  to  the defrost  relay 
on  the  outdoor  heat  pump.    This  will complete the 
circuit between R and B in the blower coil

,

 through  a  set 

of  contacts  in  the  defrost  relay  in  the  outdoor  unit.   
This circuit,  when  it  is  connected,  will  help  prevent  cold 
air from  being  discharged  from  the  indoor  unit  during 
the defrost mode. 

WARNING:

 

Do  not  store  or  use  any 

corrosives or combustibles in the vicinity of this 
unit.    All  panels  must  be  in  place  and  properly 
secured before operating this equipment. 

All  electrical  power  servicing  this  unit  must  be 
disconnected  prior  to  removal  of  any  panels.  
Service  of  this  unit  must  be  accomplished  by 
qualified trained professional personnel only. 

Отзывы: