background image

INSTALLATION GUIDE 

EFM / ELB Series Installation Guide

 

Page 3

 

REFRIGERANT PIPING 

Refrigerant  piping  external  to  the  unit  shall  be  sized  in 
accordance  with  the  instructions  of  the  manufacturer  of 
the outdoor equipment. 

METERING DEVICE 

Optional air conditioning or heat pump coils are shipped 
with a check

-

flow piston installed which is designed for air 

conditioning or heat pump operation.  If your application 
requires  a  thermal  expansion  valve  or  check  expansion 
valve then it is necessary to remove the piston from the 
distributor  assembly  and  install  the  proper  metering 
device.    Be  sure  to  follow  the  instruction  in  the  kit  to 
ensure proper installation. 

WIRING 

Consult  all  schematic  and  pictorial  wiring  diagrams  of 
this  unit  and  the  outdoor  equipment  to  determine 
compatibility of the wiring connections and to determine 
specific requirements. 

All  field  wiring  to  the  blower  coil  should  be  installed  in 
accordance with the latest edition of the National Electric 
Code NFPA No. 70 and any local codes. 

Check  rating  plates  on  unit  for  rated  volts,  minimum 
circuit  ampacity  and  maximum  over  current  protection.  
Supply  circuit  power  wiring  must  be  75

°

C.  (167

°

F) 

minimum  copper  conductors  only.    Copper supply wires 
shall be sized to the National Electric Code or local code 
requirements, whichever is more stringent. 

The  unit  is  shipped  wired  for  230/240  Volt  AC

,

  60  HZ

,

  1 

Phase  operation.    If  the  unit  is  to  be  operated  at  208 
VAC

,

 60HZ, then follow the instruction on the indoor unit 

wiring diagram to change the low voltage transformer to 
208 VAC operation. 

Be sure the unit is properly grounded. 

Class  2  low  voltage  control  wiring  should  not  be  run  in 
conduit  with  power  wiring  and  must  be  separated  from 
power wiring, unless class 1 wire of proper voltage rating 
is  used.    Low  voltage  control  wiring  should  be  18  Awg, 
color  coded  (10

5

°

C  minimum).    For  lengths  longer 

than 100ft., 16 Awg wire should be used.  Make certain 
that  separation  of  control  wiring  and  power  wiring  has 
been maintained. 

AIR FILTER 

An air filter must be installed prior to the air entering the 
evaporator  coil  to  protect  the  coil,  blower  and  other 
internal  parts  from  excessive  dirt  and  dust.    The  door 
must  be  securely  fastened  in  place  to  ensure  proper 
filtration of the return air.  A remote return air filter grille 
may be 

us

ed for ducted return air applications.  Change 

the filter every 30 days or as soon as dust or dirt appear 
on  the  filter.    Failure  to  change  the  filter  in  a  timely 
fashion  can  result  in  reduced  airflow,  increased 
operating  cost  and  may  result  in  damage  to  the  indoor 
unit and or outdoor unit. 

THERMOSTAT 

Select  a  thermostat  that  is  commonly  referred  to  as  a 
single  stage  cooling  with  electric  heat  sub  base.    This 
thermostat will energize the fan on a demand for heat or 
cool. 

Install the thermostat on an inside wall, away from drafts, 
lights  or  other  heat  sources  in  a  location  that  has  good 
air  circulation  from  the  other  rooms  being  controlled  by 
the thermostat.  The thermostat should be mounted 4 to 
5 feet above the floor. 

BLOWER 

This  unit  is  supplied  with  a  multi-speed  motor  with  a 
direct  drive  blower  wheel  which  can  obtain  various  air 
flows (See specification sheet for airflow data).  The unit 
is shipped with the blower connected for high speed.  If a 
lower  blower  speed  is  required,  disconnect  all  power  to 
the unit, remove the black indoor fan motor lead from the 
fan  relay,  place  an  insulated  cap  on  the  black  lead, 
remove the insulated cap from the red indoor fan motor 
lead, place a spade connector on the lead and connect it 
to  the  fan  relay  where  the  black  lead  was  originally 
connected.    Be  sure  to  check  the  air  flow  and  the 
temperature  drop  across  the  evaporator  coil  to  ensure 
that you have sufficient air flow. 

Отзывы: