Maximum Allowable Intake or Exhaust Vent Length in Feet
Concentric Termination at Elevation 0 - 2,000 ft
Number
of 90°
Elbows
Used
1-1/2” Pipe
2” Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
Capacity
030 045 070 090 110 135
030/
045 070 090 110 135
030/
045 070 090 110 135
030/
045 070 090 110 135
1
20
15
10
n/a n/a n/a
73
58
42
22
n/a
105 105 89
54
n/a
121 121 114 114 70
2
15
10
n/a
68
53
37
17
100 100 84
49
116 116 109 109 65
3
10
n/a
63
48
32
12
95
95
79
44
111 111 104 104 60
4
n/a
58
43
27
n/a
90
90
74
39
106 106 99
99
55
5
53
38
22
85
85
69
34
101 101 94
94
50
6
48
33
17
80
80
64
29
96
96
89
89
45
7
43
28
12
75
75
59
24
91
91
84
84
40
8
38
23
n/a
70
70
54
19
86
86
79
79
35
9
33
18
65
65
49
14
81
81
74
74
30
10
28
13
60
60
44
n/a
76
76
69
69
25
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake
and Exhaust must be same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length
calculation.
NOTE - Contact your local FTC if more than 85ft of venting is needed.
Table 5C.
Maximum Allowable Intake or Exhaust Vent Length in Feet
Concentric Termination at Elevation 2,001 - 10,000 ft
Number of
90° Elbows
Used
2” Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
030/
045
070
090
110
135
030/
045
070
090
110
135
030/
045
070
090
110
135
1
73
30
15
n/a
n/a
105
96
53
38
n/a
121
121
114
114
70
2
68
25
10
100
91
48
33
116
116
109
109
65
3
63
20
n/a
95
86
43
28
111
111
104
104
60
4
58
15
90
81
38
23
106
106
99
99
55
5
53
10
85
76
33
18
101
101
94
94
50
6
48
n/a
80
71
28
13
96
96
89
89
45
7
43
75
66
23
n/a
91
91
84
84
40
8
38
70
61
18
86
86
79
79
35
9
33
65
56
13
81
81
74
74
30
10
28
60
51
n/a
76
76
69
69
25
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake
and Exhaust must be same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length
calculation.
NOTE - Contact your local FTC if more than 85ft of venting is needed.
Table 5D.