In some applications which permit the use of several
different sizes of vent pipe, a combination vent pipe may
be used. Contact Allied Air Technical Service for assistance
in sizing vent pipe in these applications.
NOTE:
The exhaust collar on all models is sized to
accommodate 2” Schedule 40 vent pipe. In horizontal
applications, any transition to exhaust pipe larger than 2”
must be made in vertical runs of the pipe. Therefore a 2”
elbow must be added before the pipe is transitioned to
any size larger than 2”. This elbow must be added to the
elbow count used to determine acceptable vent lengths.
Contact the Application Department for more information
concerning sizing of vent systems which include multiple
pipe sizes.
NOTE
- Exhaust pipe MUST be glued to furnace exhaust fittings.
NOTE -
ward unit. A minimum of 1/4” (6mm) drop for each 12” (305mm)
of horizontal run is mandatory for drainage.
NOTE
- Exhaust piping should be checked carefully to make
sure there are no sags or low spots.
Exhaust Pipe
Horizontal
Gas Furnace
12” Min.
12” Max.
Figure 21.
Horizontal Installation Offset Requirements
Model
Min. Vent Length*
040, 060, 080, 100
15 ft. or
5 ft. plus 2 elbows or
10 ft. plus 1 elbow
*Any approved termination may be added to the minimum
length listed.
Table 10. Minimum Vent Pipe Lengths
Use the following steps to correctly size vent pipe diameter.
040, 060,
080, 100 btuh
Standard or
Concentric?
See Table 11
Intake or
Exhaust?
2” or 3”
Furnace capacity?
1
Which termination?
2
Which needs most
elbows?
3
How many?
4
Desired pipe size?
5
What is the altitude?
6
Use Table 12A through
Table 13 to find max pipe
length or exhaust pipe
length. Includes all vent
pipe and elbows inside
and outside the house.
7
Figure 22.
Do not use screens or perforated metal in exhaust or
intake terminations. Doing so will cause freeze-ups and
may block the terminations.
IMPORTANT