508093-01
Issue 2033
Page 5 of 59
Technical Specifications - 95G1UHE
PHYSICAL AND ELECTRICAL DATA
Model
Input
(Btuh)
Output
(Btuh)
AFUE
(ICS)
Nominal
Cooling
Capacity
Gas
Inlet
(in.)
Volts/
Hz/
Phase
Max.
Time
Delay
Breaker
or Fuse
Nominal
F.L.A.
Trans.
(V.A.)
Approx.
Shipping
Weight
(lbs.)
Upflow/Horizontal
95G1UH045BE12
44,000
42,000
95%
1-1/2 — 3
1/2
120 - 60 - 1
15
6.8
40
129
95G1UH070BE12
66,000
64,000
95%
1-1/2 — 3
1/2
120 - 60 - 1
15
6.8
40
134
95G1UH090CE16
88,000
85,000
95%
2-1/2— 4
1/2
120 - 60 - 1
15
8.4
40
158
95G1UH110CE20
110,000
106,000
95%
3 — 5
1/2
120 - 60 - 1
15
10.9
40
170
95G1UH135DE20
132,000
128,000
95%
3-1/2 — 5
1/2
120 - 60 - 1
15
10.9
40
187
Note: For vent length and clearances to combustibles, please reference installation instructions.
MODEL NUMBER GUIDE
Major Revision
12 = 3 Ton add on cooling
16 = 4 Ton add on cooling
20 = 5 Ton add on cooling
P = PSC
E = High Efficency
V= Variable Speed
B = 17.5” width
C = 21.0” width
D = 24.5” width
95% Efficency
Gas
1 = 1 Stage
UH = Upflow/Horizontal
DF = Downflow
Heating Input x 1000
9 5 G 1 U H 0 7 0 B E 1 2 - 0 1