508093-01
Issue 2033
Page 21 of 59
Figure 16.
1
2
3
4
5
C
L
G
N
Multi−Meter
(set to VAC)
P48
P49
120
120
Turn on power to unit. Check for 120 volts across terminals
“L” and “N” on input plug P48. If voltage is present continue
upstream of plug P48. Proceed to test 3.
1
2
3
4
5
C
L
G
N
Multi−Meter
(set to VAC)
P48
P49
24
Switch thermostat to CONTINUOUS FAN MODE. Check for
24 volts across terminal “C” on input plug P48and speed tap
used for continuous fan. (1, 2, 3, 4 or 5) on input plug P49. If
24 volts is not present problem may be up stream of plug P49.
Proceed to test 4.
Multi−Meter
(set to VAC)
12
0
12
0
24
Multi−Meter
(set to VAC)
problem is with the harness. If voltage is not present,
problem may be may be with the integrated control.
Check for 120 volts across terminals “CIRC” and “Neutrals”
on the integrated control. If voltage is present, problem is
with the harness. If voltage is not present problem may be
may be with the integrated control.
Test 1
Test 2
Test 3 (if necessary)
Test 4 (if necessary)
to test 2. If voltage is not present, problem may be
Check for 24 volts across terminals “24 COM” and “FAN”
terminals on the integrated control. If voltage is present,