508067-01
Issue 2016
Page 9 of 75
DWH124S4
Left Rear Hole
2-1/2 in. (64 mm)
diameter
Right Rear Hole
2-1/2 in. (64 mm)
diameter
21-3/4 (553)
11-7/8
(301)
Wall-Mount
Unit Outline
2-1/8 (54)
42-1/2 (1080)
13-1/4 (337)
1-7/8
(48)
6-7/8 (175)
8-5/8 (219)
1-7/8 (48)
DWH136S4
10-7/8
(276)
10-1/8
(257)
46-3/4 (1187)
13-1/2 (343)
Left rear side
refrigerant pipe inlet
2-1/2 (64) diameter
Right rear side
refrigerant pipe inlet
2-1/2 (64) diameter
Indoor unit
outline
7/8 (22)
1-3/4 (44)
Indoor Unit Type
Outdoor Unit
Indoor Unit
Cooling
Capacity
SEER
EER
Heat
Capacity
47F
HSPF
(IV)
Wall-Mounted
Non-Ducted
4DHV1S09S-1L
DWH109S4-1L
9000
19
11.5
10000
10
4DHV1S09S-1P
DWH109S4-1P
9000
18
11
9000
9.5
4DHV1S12S-1L
DWH112S4-1L
12000
19
10.5
12000
9.5
4DHV1S12S-1P
DWH112S4-1P
12000
19
11
12000
9.5
4DHV1S18S-1P
DWH118S4-1P
18000
19
11
18000
10
4DHV1S24S-1P
DWH124S4-1P
24000
17
9.5
24000
9.5
4DHV1S36S-1P
DWH136S4-1P
36000
16
8.6
36000
8.5
Ratings are AHRI certified to AHRI Standard 210/240-2008
Cooling Ratings - 80°F dry bulb/67°F wet bulb entering indoor coil air and 95°F wet bulb/75°F dry bulb outdoor air temperature.
High Temperature Heating Ratings - 70°F dry bulb/60°F wet bulb entering indoor coil air and 47°F dry bulb/43°F wet bulb outdoor air temperature.
Low Temperature Heating Ratings - 70°F dry bulb/60°F wet bulb entering indoor coil air and 17°F dry bulb/15°F wet bulb outdoor air temperature.
To convert HSPF from Region IV to Region V - Divide by 1.15.
AHRI System Matches