Page 22 of 75
Power and Communication Wiring for Systems
This unit must be properly grounded and protected by a circuit breaker. The ground wire for the unit must not be connected
to a gas or water pipe, a lightning conductor or a telephone ground wire.
Do not connect power wires to the outdoor unit until all other wiring and piping connections have been completed.
Install all wiring at least 3 feet (1 m) away from televisions, radios or other electronic devices in order to avoid the
possibility of interference with the unit operation.
Do not install the unit near a lighting appliance that includes a ballast. The ballast may affect remote control operation.
CAUTION
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the
current Canadian Electrical Code (CEC).
Overview
Refer to unit nameplate for minimum circuit ampacity and
maximum over-current protection size.
• All indoor units are powered by the outdoor unit.
•
Make all electrical power wiring connections at the
outdoor unit.
•
Size outdoor unit power per local code and power
requirements.
•
Connect wiring between indoor and outdoor terminals.
• Refer to unit name plate for rated voltage.
•
Be sure to reattach all electrical box covers after
connections are complete.
•
Follow NEC/CEC standards and all local and state
codes during wiring installation.
See Table 5 on page 23 and Table 6 on page 28 for
wiring requirements.
208/230V Outdoor Unit
Terminal Block
From Power
Supply
1 2 3 L1 L2
Terminal Block
1 2 3
208/230V Indoor Unit
Outdoor Unit
Indoor Unit
Figure 6. Single Zone Wiring - 36K
208/230V Outdoor Unit
Terminal Block
From Power
Supply
Terminal Block
208/230V Indoor Unit
Outdoor Unit
Indoor Unit
3
2
L1
L2
1
Y/G
1
3
Y/G
Y/G
115VAC Outdoor Unit
Terminal Block
From Power
Supply
Terminal Block
115VAC Indoor Unit
Outdoor Unit
Indoor Unit
3
2
L
N
1
Y/G
1
3
Y/G
Y/G
*
*
18 and 24K
unit has
five terminal
sets.
Figure 7. Single Zone Wiring - 09K,12K, 18K and 24K