Dew Point Sensors
–
Mini
User Manual v1.1
www.compressedairalliance.com
17
Commuication Settings
Default Modbus Settings
All dew point sensors use the following default Modbus settings. Settings can be
changed to suit system requirements using the Service Software (contact
Compressed Air Alliance for more information)
.
Default Modbus RTU (RS485) Settings
Address
Baud
Rate
Frame /
Parity /
Stop Bit
Response
Time
Response
Delay
Frame Spacing
1
9600
8 / N / 1
1 Sec
0 Milliseconds
7 Characters
Modbus Registers
Holding
Register
Address Data Type
Byte
Length
Description
Unit
Read /
Write
1
0
FLOAT
4
Temperature
ºC or
ºF
Read
3
2
FLOAT
4
Relative
Humidity
%RH
Read
5
4
FLOAT
4
Pressure Dew
Point
ºCtd or
ºFtd
Read
Optional integrated pressure sensor
21
20
FLOAT
4
Absolute
Pressure
KPa,
Mpa,
Bar, PSI
Read
42
41
FLOAT
4
Gauge
Pressure
KPa,
Mpa,
Bar, PSI
Read