![Alliance Laundry Systems DCB50CE Скачать руководство пользователя страница 44](http://html1.mh-extra.com/html/alliance-laundry-systems/dcb50ce/dcb50ce_service-manual_2901298044.webp)
44
M411429
Section 3 Troubleshooting
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be
reconnected to ensure that the tumbler is properly grounded.
W002
WARNING
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
48. MM NONREVERSING MODELS: MOTOR DOES NOT RUN WITH DOOR CLOSED, CYCLE
SELECTED AND START BUTTON PRESSED
120 Volt/60 Hertz/1 Phase Gas and Steam
208-240 Volt/60 Hertz/3 Phase Gas
480 Volt/60 Hertz/3 Phase Steam
NOTE: Voltage checks referenced to are for neutral unless stated otherwise.
Step Problem
If No, then
1
Is there120 VAC to the COM of the door switch?
If yes, continue to next step.
Correct wiring between door switch and L1 supply for
low voltage units. Check between door switch and X1 of
transformer for high voltage units.
2
Is there 120 VAC to the N.O. terminal of the door switch?
If yes, continue to next step.
Check for proper operation of door switch arm and/or
replace door switch.
3
Is there 120 VAC to terminal P2 of the micro control?
If yes, continue to next step.
Correct wiring between door switch and micro control.
4
Is there 120 VAC to terminal P1 of the micro control?
If yes, continue to next step for gas models, step 9 for steam
models.
Replace micro control.
5
Gas Models: Is there 120 VAC across the coils of the CR1?
If yes, continue to next step for gas models, step 9 for steam
models.
Correct wiring to the coil of CR1.
6
Is there 120 VAC to terminal 1 on CR1? If yes, continue to
next step.
Correct wiring between terminal 1and door switch.
7
Is there 120 VAC to terminal 3 on CR1? If yes, continue to
next step for 120 VAC units, or step 12 for 240 VAC units.
Replace CR1
8
Is there 120 VAC across the terminals 1 and 4 of the motor?
If yes, replace motor.
Correct wiring to motor.
9
STEAM: Is there 120 VAC across M coil?
Correct the wiring to M coil.
10
Is there 120 VAC on terminal L1 of the motor relay for
single phase units, or across L1, L2, and L3 for three phase
units? If yes, continue to next step.
Correct wiring between motor and motor relay and the
terminal block.
11
Is there 120 VAC on terminal T1 of the motor relay for
single phase units, or across T1, T2, and T3 for three phase
units? If yes, continue to step 8.
Replace motor control relay.
12
Is there 120 VAC to terminal 1 of the motor?
If yes, continue to next step.
Correct wiring between motor CR1.
13
Is there 240 VAC across terminals 1 and 4 of the motor?
If yes, replace motor.
Continue to next step.
14
Is there 120 VAC to terminal 8 of CR1? If yes, continue to
next step.
Correct wiring between CR1-8 and L2.
15
Is there 120 VAC to terminal 7 of CR1? If yes, correct
wiring between CR1-7 and terminal 4 of the motor.
Replace CR1.