50
Rockwell Automation Publication 1756-RM100F-EN-P - October 2018
Chapter 3
Replacement Considerations with CompactLogix and Compact GuardLogix Systems
Motion axes
1769-L30ERMS - As many as 4 axes
1769-L33ERMS - As many as 8 axes
1769-L36ERMS, 1769-L37ERMS,1769-L38ERMS - As many as 16
axes
Any combination of these supported axis types:
• CIP
• Consumed
• Virtual
• Position loop drives
5069-L306ERMS2: As many as 2 axes
5069-L310ERMS2: As many as 4 axes
5069-L320ERMS2: As many as 8 axes
5069-L330ERMS2: As many as 16 axes
5069-L340ERMS2: As many as 20 axes
5069-L350ERMS2: As many as 24 axes
5069-L380ERMS2: As many as 28 axes
5069-L3100ERMS2: As many as 32 axes
Any combination of these supported axis types:
• CIP
• Consumed
• Virtual
• Position loop drives
Axes/ms over EtherNet/IP port
As many as 2 (2 ms coarse update period and 50% controller load)
As many as 32 when you use the built-in EtherNet/IP port at
1 Gbps
IMPORTANT
: Not all Compact GuardLogix 5380 controllers
support Integrated Motion over an EtherNet/IP network.
Voltage and current ratings
Controller power: 850 mA @ 5.1V DC and 700 mA @ 24V DC
MOD Power:
475 mA @ 18…32V DC
MOD Power Inrush:
1200 mA for 125 ms
SA Power:
10 mA @ 0…32V DC
MOD Power (Passthrough)
(3)
: 4.525 A @ 18…32V DC
SA Power (Passthrough)
(4)
:
9.99 A @ 0…32V DC
Energy storage module
Non-removable
Non-removable
Weight, approx
0.54 kg (1.18 lb)
0.768 kg (1.693 lb)
Wire category
(1)
3 - on USB port
2 - on Ethernet port
3 - on USB port
1 - on power ports
2 - on Ethernet port
Wire size
RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e
minimum cable according to TIA 568-B.1 or Category 5 cable
according to ISO/IEC 24702
Ethernet connections:
Ethernet Cabling and Installation according to IEC 61918 and IEC
61784-5-2
Removable terminal block
Not applicable
Kit 5069-RTB64-SCREW or kit 5069-RTB64-SPRING
You must order the kit separately. RTBs do not ship with the
controller.
5069-RTB4-SCREW, 5069-RTB6-SCREW connections:
0.5...1.5 mm
2
(22…16 AWG) solid or stranded copper wire rated
at 105 °C (221 °F), or greater, 3.5 mm (0.14 in.) max diameter
including insulation, single wire connection only
5069-RTB4-SPRING, 5069-RTB6-SPRING connections:
0.5...1.5 mm
2
(22…16 AWG) solid or stranded copper wire rated
at 105 °C (221 °F), or greater, 2.9 mm (0.11 in.) max diameter
including insulation, single wire connection only
Reset Button
Clears the user application and memory but retains the firmware
revision and all network settings
A stage 1 reset clears the user application program and memory,
but retains the controller IP address.
A stage 2 reset returns the controller to out-of box settings
(including firmware), and clears all network settings.
(1) Use this conductor category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication
.
(2) Data size = 32-bits / 1-DINT
(3) Maximum level of MOD Power current that the module can pass through to the next module in the system. The specific level of current passed through varies based on system configuration.
(4) Maximum level of SA Power current that the module can pass through to the next module in the system. The specific level of current passed through varies based on system configuration.
Table 9 - Technical Specifications
Attribute
Compact GuardLogix 5370 Controller
Compact GuardLogix 5380 Controller
Содержание Studio 5000 Logix Emulate
Страница 8: ...8 Rockwell Automation Publication 1756 RM100F EN P October 2018 Table of Contents Notes...
Страница 16: ...16 Rockwell Automation Publication 1756 RM100F EN P October 2018 Chapter 1 BeforeYou Begin a Migration Notes...
Страница 170: ...170 Rockwell Automation Publication 1756 RM100F EN P October 2018 Index Notes...
Страница 171: ......