
86
Rockwell Automation Publication 1789-UM002K-EN-P - January 2015
Chapter 4
Communicate with Serial Devices
DF1 Point-to-Point Configuration
Example 2: Workstation
Remotely Connected to a
SoftLogix Controller
In this example, a workstation remotely connects to a SoftLogix controller over a
serial device. A modem is connected to the controller to provide remote access.
IMPORTANT
The workstation with the Logix Designer application must also have the
Logix5550
®
serial port driver installed through RSLinx software.
Field
Description
Station Address
The station address for the serial port on the DF1 point-to-point network. Enter a valid DF1 address (0…254). Address
255 is reserved for broadcast messages. The default is 0.
NAK Receive Limit
Specifies the number of NAKs the controller can receive in response to a message transmission.
Enter a value 0…127. The default is 3.
ENQ Transmit Limit
Specifies the number of inquiries (ENQs) you want the controller to send after an ACK timeout.
Enter a value 0…127. The default is 3.
ACK Timeout
Specifies the amount of time you want the controller to wait for an acknowledgment to its message transmission.
Enter a value 0…32767. Limits are defined in 20 ms intervals. The default is 50 (1000 ms).
Embedded Response
Specifies how to enable embedded responses.
Choose Autodetect (enabled only after receiving one embedded response) or Enabled. The default is Autodetect.
Error Detection
Choose BCC or CRC error detection.
Configure both stations to use the same type of error checking.
BCC: the controller sends and accepts messages that end with a BCC byte for error checking. BCC is quicker and easier to
implement in a computer driver. This is the default.
CRC: the controller sends and accepts messages with a 2-byte CRC for error checking. CRC is a more complete method.
Enable Duplicate Detection
Choose whether the controller should detect duplicate messages. The default is duplicate detection enabled.
2
3
4
1
Содержание SoftLogix 5800
Страница 1: ...SoftLogix 5800 System Catalog Numbers 1789 L10 1789 L30 1789 L60 User Manual...
Страница 4: ...4 Rockwell Automation Publication 1789 UM002K EN P January 2015 Summary of Changes Notes...
Страница 104: ...104 Rockwell Automation Publication 1789 UM002K EN P January 2015 Chapter 5 Configure and Use Simulated I O Notes...
Страница 110: ...110 Rockwell Automation Publication 1789 UM002K EN P January 2015 Chapter 6 Execute External Routines 9 Click OK...
Страница 148: ...148 Rockwell Automation Publication 1789 UM002K EN P January 2015 Chapter 7 Develop External Routines Notes...
Страница 256: ...256 Rockwell Automation Publication 1789 UM002K EN P January 2015 Appendix E System Performance Tuning Guidelines Notes...
Страница 262: ...262 Rockwell Automation Publication 1789 UM002K EN P January 2015 Appendix G SoftLogix 5800 Revision History Notes...
Страница 270: ...270 Rockwell Automation Publication 1789 UM002K EN P January 2015 Index...
Страница 271: ......