background image

POINT I/O 
EtherNet/IP 
Adapter Module

1734-AENT

User Manual

Содержание Rockwell Automation 1734-AENT

Страница 1: ...POINT I O EtherNet IP Adapter Module 1734 AENT User Manual...

Страница 2: ...ribes some important differences between solid state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication...

Страница 3: ...ventions are used throughout this manual Numbered lists provide sequential steps Bulleted lists provide information not procedural steps Information in bold text identifies menu windows screen options...

Страница 4: ...ons that demonstrate the procedures for configuring and communicating with POINT I O using the 1734 AENT adapter The example applications are intended as building blocks to help you get your own syste...

Страница 5: ...34 OW2 C 1 DIN Rail 199 DR1 or equivalent 1 ControlLogix chassis 1756 A4 or A7 A13 A17 1 ControlLogix power supply 1756 PA72 or PB72 1 Logix5555 controller 1756 L55 1 ControlLogix EtherNet IP Bridge M...

Страница 6: ...s 1756 IN019 ControlLogix EtherNet IP Bridge Module User Manual 1756 UM050 RSLogix 5000 programming software Getting Results with RSLogix 5000 version 3 2 1 or higher 9399 RLD300GR RSLinx communicatio...

Страница 7: ...stallation Instructions 1734 IN585 POINT I O 2 relay output module POINT I O 2 Relay Output Module Installation Instructions OX2 1734 IN587 POINT I O 2 Relay Output Module Installation Instructions OW...

Страница 8: ...same time their signals collide When the collision is detected they both back off and each waits a random amount of time before retrying determinism The ability to predict when information will be de...

Страница 9: ...a value between 0 and 255 0x00 to 0xFF This address is assigned in the hardware and cannot be changed The hardware address is required to identify the device if you are using a BOOTP utility host nam...

Страница 10: ...rk segments A switch provides each sender receiver the full network bandwidth 2x in full duplex mode reduces collisions and increases determinism TCP The Transport Control Protocol is a more reliable...

Страница 11: ...ack Optimized and Direct Connections 1 6 Mix Rack Optimized and Direct Connections 1 7 What s Next 1 8 Chapter 2 Install the 1734 AENT Adapter What This Chapter Contains 2 1 Identify Module Components...

Страница 12: ...ith Fixed IP Address 4 18 An Overloaded 1734 AENT 4 19 Chapter 5 Configure the 1734 AENT for Direct Connection and Rack Optimization in RSLogix 5000 What s in This Chapter 5 1 Set Up the Hardware 5 2...

Страница 13: ...5000 Data Types C 2 Discrete 2 POINT Input C 3 Discrete 4 POINT Input C 4 Discrete 2 POINT Output Without Diagnostic Status C 5 Discrete 2 POINT Output With Over Load and Open Load Diagnostic Status C...

Страница 14: ...Publication 1734 UM011A EN P February 2004 Table of Contents iv...

Страница 15: ...information about See page Important Adapter Considerations 1 2 Set the Chassis Size 1 2 Adapter replacement 1 2 Empty Slots and RIUP Situations 1 3 Power Up a System For the First Time 1 4 Adapter Fe...

Страница 16: ...he adapter s backplane e g the adapter plus 4 I O modules will use a chassis size of 5 The adapter stores this chassis size setting in non volatile storage When the adapter s non volatile chassis size...

Страница 17: ...ermine what has changed Whenever a module with an active connection is removed from the POINT I O system the adapter will indicate this by flashing the PointBus Status LED red and report a minor recov...

Страница 18: ...this operation takes is proportional to the size of your POINT I O system Adapter Features The 1734 AENT adapter s features include use of EtherNet IP messages encapsulated within standard TCP UDP IP...

Страница 19: ...The 1734 AENT adapter uses the Common Industrial Protocol CIP CIP is the application layer protocol specified for EtherNet IP the Ethernet Industrial Protocol as well as for ControlNet and DeviceNet...

Страница 20: ...rNet IP network This data exchange conforms to the producer consumer model Specify the Requested Packet Interval RPI The RPI is the update rate specified for a particular piece of data on the network...

Страница 21: ...only need a single connection the connection to the 1734 AENT adapter See the EtherNet IP Performance and Application Guide publication number ENET AP001 for more information on connections Mix Rack O...

Страница 22: ...ication 1734 UM011A EN P February 2004 1 8 About the 1734 AENT Adapter What s Next The following chapter describes how to physically install the 1734 AENT adapter and connect it to the EtherNet IP net...

Страница 23: ...erNet IP network The following table lists where to find specific information Topic See Page Identify Module Components 2 2 Mount the Adapter on a DIN Rail Before Installing Modules 2 2 Mount or Repla...

Страница 24: ...ess down firmly to install the adapter on the DIN rail The locking mechanism will lock the adapter to the DIN rail Description Description 1 Ethernet Network RJ45 Connector 5 System Power and Field Po...

Страница 25: ...replacement adapter slide the safety end cap up to remove This exposes the backplane and power connections 3 Position the replacement adapter vertically above the DIN rail Make certain the DIN rail lo...

Страница 26: ...place Wiring Refer to the illustration to wire the Ethernet adapter 43264 System Power CHAS GND C V NC Network Address Thumbwheels Field Power NC No Connection CHAS GND Chassis Ground C Common V Supp...

Страница 27: ...apter describes how to configure the adapter to communicate on your EtherNet IP network by providing an IP address Gateway address and Subnet mask inches millimeters A DIN rail B Secure DIN rail appro...

Страница 28: ...Publication 1734 UM011A EN P February 2004 2 6 Install the 1734 AENT Adapter Notes...

Страница 29: ...re You can also use this utility to reconfigure a device whose IP address must be changed Using a third party DHCP server Using the Network Address thumbwheel switches Having your network administrato...

Страница 30: ...ue IP address The IP address is 32 bits long and has a net ID part and a Host ID part Networks are classified A B C or other The class of the network determines how an IP address is formatted IMPORTAN...

Страница 31: ...lti network systems If you have a single network system please skip to the next section The Gateway Address is the default address of a network It provides a single domain name and point of entry to t...

Страница 32: ...ddressed using a net ID matching its own Subnet Mask The Subnet Mask is used for splitting IP networks into a series of subgroups or subnets The mask is a binary pattern that is matched up with the IP...

Страница 33: ...with Network 2 2 Hosts D and E will use Gateway G2 to communicate with hosts not on Network 2 2 Hosts B and C will use Gateway G to communicate with hosts not on Network 2 1 When B is communicating wi...

Страница 34: ...x represents the number set on the switches The adapter s subnet mask will be 255 255 255 0 and the gateway address is set to 0 0 0 0 The adapter will not have a host name assigned or use any Domain N...

Страница 35: ...CD The 1734 AENT adapter must have DHCP enabled factory default and the network address switches set to an illegal value to use the utility To configure your adapter using the BootP utility perform th...

Страница 36: ...section it signifies that the IP address assignment has been made 4 To assign this configuration to the device highlight the device in the Relation List panel and click on the Disable BOOTP DHCP butt...

Страница 37: ...on List to use later To save the Relation List perform the following steps 1 Select Save As from the File menu You will see the following window 2 Select the folder you want to Save in 3 Enter a File...

Страница 38: ...IP address When 50 percent of the leased time has expired the 1734 AENT adapter will attempt to renew its IP address with the DHCP server The possibility exists that the adapter will be assigned a di...

Страница 39: ...e the Example Application 4 3 Configure the I O 4 4 Add the Local EtherNet IP Bridge to the I O Configuration 4 4 Add the POINT I O Adapter to the I O Configuration 4 6 Add the POINT I O Modules to th...

Страница 40: ...as shown above Note that in the example application the Logix5555 controller and 1756 ENBT module firmware version 2 3 or higher are assumed to be in the slots shown above Verify the IP addresses for...

Страница 41: ...e New Controller pop up window will open 3 Enter an appropriate Name for the Controller e g POINT_IO_Controller 4 Select the correct Version Chassis Type and Slot number of the Logix5555 controller an...

Страница 42: ...on Next you add the 1734 AENT adapter as a child of the 1756 ENBT module Then you add the I O modules as children of the 1734 AENT adapter Add the Local EtherNet IP Bridge to the I O Configuration 1 S...

Страница 43: ...The Select Module Type window will open 3 Select the 1756 ENBT EtherNet IP Bridge and click on OK The Module Properties window will open 4 We used the following values 5 Click on Finish to accept the...

Страница 44: ...figuration Next you must add the 1734 AENT adapter as a child of the local 1756 ENBT module 1 In the Project window right click on the local 1756 ENBT module under the I O Configuration folder and sel...

Страница 45: ...ck optimization read or verify data only but does not control the modules when you have multiple processors one processor is used to control and the other processors are used to monitor Because we are...

Страница 46: ...to the I O Configuration You must now add the POINT I O modules to the I O Configuration List under the 1734 AENT adapter In this example you will add a 1734 OW2 relay output and a 1734 OV4E sink out...

Страница 47: ...ay output module from the list and click on OK The Module Properties window will open 3 We used the following values TIP At the bottom of the Select Module Type screen you can choose Clear All and the...

Страница 48: ...ou are using a discrete input module then the Comm Format would be Input Data 4 Choose Next Notice that RPI is selectable on the screen below since it is a direct connection 5 Enter the RPI requested...

Страница 49: ...h button to save the configuration The relay output module will appear in the I O configuration indented under the 1734 AENT adapter Add the Digital Output Module 8 Right click on the 1734 AENT adapte...

Страница 50: ...used the following values 11 Click the Next button 12 Leave 10 ms as the RPI for the 1734 OV4E module 13 Click on the Finish button to accept the configuration The I O Configuration in the Project wi...

Страница 51: ...ication program For the example application you need to add one more Controller Tag 1 Double click on the Controller Tags folder in the project window The Controller Tags window will open You will see...

Страница 52: ...ction in RSLogix 5000 3 Close the Controller Tags window Create the Ladder Program Next create the example ladder program to test the I O 1 Double click on Main Routine under the Main Program folder 2...

Страница 53: ...gram to the Controller Follow this procedure to download the program we just saved to the ControlLogix controller 1 From the main menu choose Communications Who Active 2 Navigate to select the slot wh...

Страница 54: ...SLogix 5000 software used the chassis size from the 1734 AENT General tab Now you need to download this new chassis size value into the 1734 AENT adapter hardware This procedure will synchronize the c...

Страница 55: ...4 AENT for Direct Connection in RSLogix 5000 4 17 6 Click Set Chassis Size in Module 7 Read and acknowledge the warning screen 8 Click OK to continue Notice the chassis size in the module has been mod...

Страница 56: ...e Configure the 1734 AENT with Fixed IP Address To configure the 1734 AENT with a fixed IP address to prevent the adapter from ceasing to communicate with the ControlLogix controller 1 Click on the Po...

Страница 57: ...the connection and the rate of change of the I O The 1734 AENT continuously monitors this bandwidth and will reject requests for new connections when there is insufficient bandwidth available to supp...

Страница 58: ...Publication 1734 UM011A EN P February 2004 4 20 Configure the 1734 AENT for Direct Connection in RSLogix 5000 Notes...

Страница 59: ...ir own set RPIs and ignore the 1734 AENT adapter s RPI Note that the modules presented in this chapter are configured using RSLogix 5000 version 11 The chapter contains the following main sections Wha...

Страница 60: ...your system as shown above Note that in the example application the Logix5555 controller and 1756 ENBT module firmware version 2 3 or higher are assumed to be in the slots shown above Verify the IP ad...

Страница 61: ...lect New The New Controller pop up window will open 3 Enter an appropriate Name for the Controller e g POINT_IO_Controller 4 Select the correct Version Chassis Type and Slot number of the Logix5555 co...

Страница 62: ...onfiguration Next you add the 1734 AENT adapter as a child of the 1756 ENBT module Then you add the I O modules as children of the 1734 AENT adapter Add the Local EtherNet IP Bridge to the I O Configu...

Страница 63: ...ix 5000 5 5 The Select Module Type window will open 3 Select the 1756 ENBT EtherNet IP Bridge and click on OK The Module Properties window will open 4 We used the following values 5 Click on Finish to...

Страница 64: ...the I O Configuration Next you must add the 1734 AENT adapter as a child of the local 1756 ENBT module 1 In the Project window right click on the local 1756 ENBT module under the I O Configuration fol...

Страница 65: ...data only but does not control the modules when you have multiple processors one processor is used to control and the other processors are used to monitor Because we are making a mixed connection bot...

Страница 66: ...1734 ENBT in the I O Configuration folder Add the POINT I O Module and Configure For Direct Connection 1 Highlight the 1734 AENT under I O configuration right click and select New Module 2 Choose the...

Страница 67: ...t is Output Data because we are configuring a mixed direct connection and rack optimized connection with the 1734 OW2 C Relay Output module configured for a direct connection If you are using a discre...

Страница 68: ...since it is a direct connection 6 Enter the RPI requested packet interval to set how often the data is exchanged with the 1734 AENT 7 Enter 50 for the RPI 8 Choose Finish Notice that the 1734 OW2 is n...

Страница 69: ...O Configuration right click and select New Module The Select Module Type window will open 2 Choose the 1734 OV4E C module 3 Click OK The Module Properties window will open 4 Enter a Name Slot Comm Fo...

Страница 70: ...he configuration The I O Configuration in the Project window should look similar to the one shown below 6 Choose Finish 7 Choose File Save and enter the name and location of the RSLogix 5000 file Down...

Страница 71: ...t the I O tree in RSLogix 5000 and the RSLogix 5000 software used the chassis size from the 1734 AENT General tab Now you need to download this new chassis size value into the 1734 AENT adapter hardwa...

Страница 72: ...1734 AENT for Direct Connection and Rack Optimization in RSLogix 5000 You see the Module Fault error code 5 Click the Chassis Size tab 6 Click Set Chassis Size in Module 7 Read and acknowledge the war...

Страница 73: ...n RSLogix 5000 5 15 8 Click OK to continue Notice the chassis size in the module has been modified to 3 9 Click OK At this point you PointBus status LED should be solid green All the yellow triangles...

Страница 74: ...troller information refer to ControlLogix System User Manual publication no 1756 UM001 Slot Status Bits The Slot Status bits display the connection status for each of the POINT I O modules that use a...

Страница 75: ...Green System power on dc dc converter active 5V dc Field Power Off Not active field power is off Green Power on 24V dc present Indication Probable Cause Module Status Off No power applied to device Fl...

Страница 76: ...d Ethernet Device Flashing Red Green The module is performing a self test only occurs during powerup test Network Activity Off No link established Flashing Green Off Transmit or receive activity Stead...

Страница 77: ...ts dangereux Lorsque plusieurs produits sont combin s dans un syst me le code de temp rature le plus d favorable code de temp rature le plus faible peut tre utilis pour d terminer le code de temp ratu...

Страница 78: ...each the 63 module maximum Cat No PointBus Current Requirements 1734 IB2 75mA 1734 IB4 75mA 1734 IV2 75mA 1734 IV4 75mA 1734 OB2E 75mA 1734 OB2EP 75mA 1734 OB4E 75mA 1734 OV2E 75mA 1734 OV4E 75mA 1734...

Страница 79: ...3 4L Environmental Conditions Operational Temperature IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 20 to 55 C 4 to 131 F...

Страница 80: ...ed C UL US UL Listed Industrial Control Equipment certified for US and Canada C UL US UL Listed for Class I Division 2 Groups A B C and D Hazardous locations certified for US and Canada CE2 European U...

Страница 81: ...he Web page shown below The adapter s Web pages provide the following Diagnostic information Browse Chassis capability Configuration information Some examples of these pages are shown on the following...

Страница 82: ...ry 2004 A 2 1734 AENT Adapter Web Pages Diagnostic Information From the Diagnostic Home page you can access other diagnostic web pages including Module Information Detailed Network Statistics Connecti...

Страница 83: ...endor ID product type product code firmware revision status switches and CPU utilization EDS Files You can access the 1734 AENT EDS files from the Module Information page These EDS files are coming fr...

Страница 84: ...Web Pages Network Statistics The Network Statistics page provides information that echoes the state of The Network Statistics page provides information that echoes the state of the module You can obta...

Страница 85: ...A EN P February 2004 1734 AENT Adapter Web Pages A 5 Connection Statistics The Connection Statistics page list CIP related statistic and connection activity You can obtain the following statistics req...

Страница 86: ...011A EN P February 2004 A 6 1734 AENT Adapter Web Pages Diagnostic Messaging The Diagnostic Messaging page lets you retrieve module status or conditions such as Service I O slot position Class Instanc...

Страница 87: ...The Browse Chassis page provides an easy and helpful way to see what modules the adapter is recognizing on your system Select the Display compact button so a check mark appears to decrease the font si...

Страница 88: ...you quickly and easily identify where the module is in the facility As you enter the parameters in the field and press the Enter or Update on the web page key the field will turn blue to indicate tha...

Страница 89: ...et to True the Ethernet link will be negotiated automatically the Auto Negotiate function will be set to True the web server will be enabled the Disabled Web Server function will be disabled the passw...

Страница 90: ...Publication 1734 UM011A EN P February 2004 A 10 1734 AENT Adapter Web Pages Notes...

Страница 91: ...the RSLinx Software Use the following procedure to install RSLinx software on your computer 1 Insert the CD in the CD ROM drive Note The CD ROM supports Windows Autorun Once inserted into the CD ROM d...

Страница 92: ...me screen Configure the AB_ETH Driver To configure the AB ETH Ethernet communication driver perform the following steps 1 Start RSLinx 2 From the Communications menu select Configure Drivers 3 Click o...

Страница 93: ...our own name and click on OK The Configure driver window will appear with the Station Mapping page open 6 Click on Add New and enter the IP address or Host Name of your Ethernet device e g 10 88 70 4...

Страница 94: ...display the drivers you have configured on your workstation 9 Close RSLinx Configure the AB_ETH IP Driver To configure the AB ETHIP Ethernet communication driver perform the following steps 1 Start R...

Страница 95: ...1734 UM011A EN P February 2004 Configure the RSLinx Ethernet Communication Driver B 5 4 Select EtherNet IP Devices and click on Add New You see this window 5 Make sure the Browse Local Subnet button...

Страница 96: ...4 B 6 Configure the RSLinx Ethernet Communication Driver RSLinx will browse your local subnet and automatically read the IP address 6 Click OK The AB ETHIP driver is now configured and appears in the...

Страница 97: ...4 IV4 C 4 POINT 10V 28V DC Input Source 1734 OA2 C 2 POINT 120V AC Output 1734 OB2E C 2 POINT 10V 28V DC Electronically Fused Output Source 1734 OB2EP C 2 POINT 10V 28V DC Electronically Fused Protect...

Страница 98: ...anges for RSLogix 5000 Data Types Accepted parameter values are dependent on POINT I O Module type and Tag type 1734 POINT I O Catalog Number RSLogix5000 Module Description Specialty I O 1734 232ASC C...

Страница 99: ...ms filter time 40000 65536 25536 1734 IA2 2 POINT 120V AC Input 1734 IB2 2 POINT 10V 28V DC Input Sink 1734 IM2 2 POINT 240V AC Input 1734 IV2 2 POINT 10V 28V DC Input Source Configuration Data Data T...

Страница 100: ...nput Source Configuration Data Data Type Default Value Valid Data Values Filter Off On Time POINT 0 INT 1 000 32 768 to 32 767 s 0 65 535 Filter On Off Time POINT 0 INT 1 000 32 768 to 32 767 s 0 65 5...

Страница 101: ...put N O N C Configuration Data Data Type Default Value Valid Data Values Fault Mode POINT 0 1 SINT BIT 0 0 Fault Value 1 Hold Last State Fault Value POINT 0 1 SINT BIT 0 0 Off 1 On Program Mode POINT...

Страница 102: ...Fault Value POINT 0 1 SINT BIT 0 0 Off 1 On Program Mode POINT 0 1 SINT BIT 0 0 Program Value 1 Hold Last State Program Value POINT 0 1 SINT BIT 0 0 Off 1 On No Load Enable POINT 0 1 Wire Off Diagnos...

Страница 103: ...State Fault Value POINT 0 1 SINT BIT 0 0 Off 1 On Program Mode POINT 0 1 SINT BIT 0 0 Program Value 1 Hold Last State Program Value POINT 0 1 SINT BIT 0 0 Off 1 On Auto Restart Enable POINT 0 1 Over...

Страница 104: ...gram Mode POINT 0 1 2 3 SINT BIT 0 0 Program Value 1 Hold Last State Program Value POINT 0 1 2 3 SINT BIT 0 0 Off 1 On No Load Enable POINT 0 1 2 3 Wire Off Diagnostic SINT BIT 1 0 Disabled 1 Enabled...

Страница 105: ...Value POINT 0 1 2 3 SINT BIT 0 0 Off 1 On Program Mode POINT 0 1 2 3 SINT BIT 0 0 Program Value 1 Hold Last State Program Value POINT 0 1 2 3 SINT BIT 0 0 Off 1 On Auto Restart Enable POINT 0 1 2 3 O...

Страница 106: ...el 0 SINT 3 3 4 20mA 8 0 20mA Limit Alarm Latch Channel 0 SINT 0 0 No Latching 1 Alarms Latch Alarm Disable Channel 0 SINT 0 0 Alarms Enabled 1 Alarms Disabled Low Engineering Channel 1 INT 3 277 32 7...

Страница 107: ...to 32 767 Data Channel 1 INT 0 32 768 to 32 767 Status Byte Channel 0 SINT 0 Bit 0 Fault Bit 1 Calibration Bit 2 LowAlarm Bit 3 HighAlarm Bit 4 LowLowAlarm Bit 5 HighHighAlarm Bit 6 Underrange Bit 7...

Страница 108: ...to 10V 2 0 to 10V Limit Alarm Latch Channel 0 SINT 0 0 No Latching 1 Alarms Latch Alarm Disable Channel 0 SINT 0 0 Alarms Enabled 1 Alarms Disabled Low Engineering Channel 1 INT 0 32 768 to 32 767 Hig...

Страница 109: ...to 32 767 Data Channel 1 INT 0 32 768 to 32 767 Status Byte Channel 0 SINT 0 Bit 0 Fault Bit 1 Calibration Bit 2 LowAlarm Bit 3 HighAlarm Bit 4 LowLowAlarm Bit 5 HighHighAlarm Bit 6 Underrange Bit 7...

Страница 110: ...No Latching 1 Alarms Latch Alarm Disable Channel 0 SINT 0 0 Alarms Enabled 1 Alarms Disabled Sensor Type Channel 0 SINT 1 0 Ohms 1 100 Pt 385 2 200 Pt 385 5 100 JPt 3916 6 200 JPt 3916 9 10 Cu 427 10...

Страница 111: ...otch Filter Channel 0 1 SINT 1 0 50Hz 1 60Hz 2 100Hz 3 120Hz 4 200Hz 5 240Hz 6 300Hz 7 400Hz 8 480Hz Input Data Data Type Default Value Valid Data Values Data Channel 0 INT 0 32 768 to 32 767 Data Cha...

Страница 112: ...l 0 INT 7 000 32 768 to 32 767 Alarm Disable Channel 0 SINT 0 0 Alarms Enabled 1 Alarms Disabled Limit Alarm Latch Channel 0 SINT 0 0 No Latching 1 Alarms Latch Notch Filter Channel 0 SINT 1 0 50Hz 1...

Страница 113: ...to 32 767 High Engineering Channel 1 INT 7 000 32 768 to 32 767 Alarm Disable Channel 1 SINT 0 0 Alarms Enabled 1 Alarms Disabled Limit Alarm Latch Channel 1 SINT 0 0 No Latching 1 Alarms Latch Notch...

Страница 114: ...0 to 7 000 0 00 70 00 Input Data Data Type Default Value Valid Data Values Data Channel 0 INT 0 32 768 to 32 767 Data Channel 1 INT 0 32 768 to 32 767 Status Byte Channel 0 SINT 0 Bit 0 Fault Bit 1 C...

Страница 115: ...ault Mode Channel 0 SINT 1 0 Hold Last State 1 Go to Low Clamp 2 Go to High Clamp 3 Go to Fault Value Idle Mode Channel 0 SINT 1 0 Hold Last State 1 Go to Low Clamp 2 Go to High Clamp 3 Go to Fault Va...

Страница 116: ...ult Value Limit Alarm Latch Channel 1 SINT 0 0 No Latching 1 Alarms Latch Alarm Disable Channel 1 SINT 0 0 Alarms Enabled 1 Alarms Disabled Input Data Data Type Default Value Valid Data Values Status...

Страница 117: ...2 Go to High Clamp 3 Go to Fault Value Idle Mode Channel 0 SINT 1 0 Hold Last State 1 Go to Low Clamp 2 Go to High Clamp 3 Go to Fault Value Limit Alarm Latch Channel 0 SINT 0 0 No Latching 1 Alarms L...

Страница 118: ...atching 1 Alarms Latch Alarm Disable Channel 1 SINT 0 0 Alarms Enabled 1 Alarms Disabled Input Data Data Type Default Value Valid Data Values Status Byte Channel 0 SINT 0 Bit 0 Fault Bit 1 Calibration...

Страница 119: ...Rate 0111 7 Rate Measurement 1000 8 Pulse Generator 000 Store Count Disable 001 Store Continue 010 Store Wait Resume 011 Store Reset Wait Start 100 Store Reset Start 0 Z Input Not Inverted 1 Z Input I...

Страница 120: ...Out 1 Window 1 Out 1 Window 2 Out 1 Window 3 Out 1 Window 4 SINT BIT 0 BIT 1 BIT 2 BIT 3 0 0 Output 1 Not Tied 1 Output 1 Tied to Window Counter Config 3 PWM Output 1 Window 1 PWM In Rollover DINT 16...

Страница 121: ...xample For a Scalar of 128 128 256 128 1734 VHSC24 1 Channel 15 24V DC Very High Speed Counter 1734 VHSC5 1 Channel 5V DC Very High Speed Counter Configuration Data Data Type Default Value Valid Data...

Страница 122: ...5 Stored Data DINT 0 2 147 483 648 to 2 147 483 647 0 4 294 967 295 Status Zero Frequency Detected Stored Data Count_2 Stored Data Count_3 A Input Status B Input Status Z Input Status Output Status_8...

Страница 123: ...and not zero OR Counter 0 window ON OFF value is greater than the Rollover 7 A tie has been connected to an unprogrammed window 6 A configuration was selected that requires the scalar and none was pro...

Страница 124: ...0 0 0 0 0 Count Unchanged 1 Count Cleared 0 Count Unchanged 1 Count Set to Preset 0 Count Unchanged 1 Count Cleared Output Control Output 0 Force Output 0 Enable Output 0 Electronic Fuse Output 0 Dia...

Страница 125: ...Store Reset Wait Start 100 Store Reset Start 0 Z Input Not Inverted 1 Z Input Is Inverted Filter Filter_0 Filter_1 Filter_2 Filter_3 FilterA FilterB FilterZ SINT BIT 0 BIT 1 BIT 2 BIT 3 BIT 4 BIT 5 BI...

Страница 126: ...rval Value 256 Entered Gate Interval Value Example For a Gate Interval of 200 200 256 56 Scalar Note Desired Scalar Value 256 Entered Scalar Value Example For a Scalar of 128 128 256 128 1734 IJ 1 Cha...

Страница 127: ...Data Data Type Default Value Valid Data Values Present Data DINT 0 0 to 16 777 215 Stored Data DINT 0 2 147 483 648 to 2 147 483 647 0 4 294 967 295 Status Zero Frequency Detected Stored Data Count_2...

Страница 128: ...and not zero OR Counter 0 window ON OFF value is greater than the Rollover 7 A tie has been connected to an unprogrammed window 6 A configuration was selected that requires the scalar and none was pro...

Страница 129: ...ncoder Counter 1734 IK 1 Channel 15 24V DC Encoder Counter Output Data Data Type Default Value Valid Data Values Counter Control Counter Reset Counter Preset Value Reset Stored Accumulated Count SINT...

Страница 130: ...Delay Time INT 64 32 768 to 32 767 s 16 65 535 Trailing No of Trailing Bits SINT 0 0 to 16 Input Latch Control InputLatch_0 InputLatch_1 SINT BIT 0 BIT 1 0 00 Off 01 Falling Edge of Input 10 Rising Ed...

Страница 131: ...use this conversion formula Desired Resolution Value 65536 Entered Resolution Value Example For a 40 000 count sensor 40000 65536 25536 Sensor Cycle Note To enter Cycle values from 32 768 to 65 535 us...

Страница 132: ...47 483 647 0 4 294 967 295 Status Input Status Run Decreasing Count Increasing Count Compare0 Reached Compare1 Reached Compare0 Status Compare1 Status Power Fault Configuration Fault Communication Fau...

Страница 133: ...fault Value Valid Data Values Control Latch Acknowledge Compare 0 Acknowledge Compare 1 Acknowledge Compare 0 Select Compare 1 Select SINT BIT 0 BIT 1 BIT 2 BIT 3 BIT 4 0 0 0 0 0 0 0 Latch Not Cleared...

Страница 134: ...Exclude Start Delimiter 2 Include Start Delimiter Receive Start Delimiter Character SINT 58 0x3A Any Valid ASCII Character Default is Colon Receive Record End Mode SINT 2 0 No End Delimiter 1 Exclude...

Страница 135: ...sired Decimal Value 256 Entered Decimal Value Example For an ASCII Character value of 128 128 256 128 1734 232ASC 1 Channel ASCII Interface Module Configuration Data Data Type Default Value Valid Data...

Страница 136: ...r 1 Handshake Error 0 No New Data 1 New Data Present Length_Lo SINT 20 128 to 127 0 128 Length_Hi SINT 0 0 or 1 Data 128 SINT 0 Received ASCII Message Output Data Data Type Default Value Valid Data Va...

Страница 137: ...record Number of Length_Lo values of 0 127 which RSLogix 5000 does support in the signed Short Integer data type SINT 128 to 127 range Note that 8 data bits allows Transmit Receive record Number of Le...

Страница 138: ...Publication 1734 UM011A EN P February 2004 C 42 1734 POINT I O Module RSLogix 5000 Controller Tag Reference Notes...

Страница 139: ...T module must be version 2 3 or higher The 1734 POINT I O modules must be Series C except for the 1734 232ASC modules which can be Series A The recommended RPIs are being used Discrete 10 ms or higher...

Страница 140: ...ck Optimization if you want a rack optimized connection 4 For the Electronic Keying field select Compatible Module 5 Enter the Chassis Size Note Regarding chassis size the POINT I O adapter itself tak...

Страница 141: ...u will notice that the data under this tab is grayed out while offline The Chassis Size tab is used to send the module size from the General tab to the module itself once you are online Otherwise you...

Страница 142: ...le from the Module Type list and click on OK 3 In the Module Properties window enter the following information a Name b Slot c Comm Format d Electronic Keying choose Compatible Module e Click on Next...

Страница 143: ...e you can set the entire module s configuration alarms etc In this configuration window you enter the values that would correspond to the desired range According to Appendix C of this user manual the...

Страница 144: ...controller only sends the configuration data when connection is being established Should you need to modify any of the tag values once you change the tag you will need to access the updated informati...

Страница 145: ...onnection Tab You will see the following message The module is faulted because even though you have set up the 1734 AENT s POINT I O chassis size to the actual number of the modules plus the adapter t...

Страница 146: ...olLogix processor 1 Double click on the RSLinx icon on the Desktop to launch RSLinx software 2 Click on the RSWho icon IMPORTANT The information found in the Appendix C of this user manual is also ava...

Страница 147: ...twork or device icon to expand the view and begin browsing When a network or device is expanded as indicated by the sign you can click on the sign or double click on the network or device icon to coll...

Страница 148: ...IP Driver 3 Click on the Add New button 4 Click on OK to accept the default name AB_ETHIP 1 5 Ensure that the radio button for Browse Local Subnet is enabled 6 Click on OK 7 Verify that the driver yo...

Страница 149: ...ter replacing on system 2 3 adapter wiring 2 4 adding modules to configuration select a communication module 5 4 B BootP see Rockwell Bootp utility using a third party BootP server 3 10 browse chassis...

Страница 150: ...re modules installed 2 2 replacing adapter 2 3 set the network address 2 3 wiring 2 4 IP address 3 2 L ladder program 4 15 LED status indicators 6 1 M module data access 4 19 module information web pa...

Страница 151: ...RSLogix 5000 data types valid number ranges C 2 S safety approvals 7 1 set the network address 2 3 specifications 7 2 subnet mask 3 4 3 5 T terminology Preface 6 Preface 8 W web pages A 1 A 10 browse...

Страница 152: ...Publication 1734 UM011A EN P February 2004 4 Index...