Advance Program Group
(continued)
A198 [Program Lock]
Protects parameters against change by unauthorized personnel. Enter a user-selected password to
lock the parameters via Option 1. Enter the same password to unlock the parameters.
Options
0
“Unlocked” (Default)
1
“Locked”
Locks all parameters.
2
“Locked”
Parameter edits allowed over communications network.
3
“Locked”
Locks
[Maximum Freq] and
[Boost Select].
A199 [Motor NP Poles]
Related Parameter(s):
Sets the motor poles. This is used to calculate
[Output RPM].
Values
Default:
4
Min/Max:
2/40
Display:
1
A200 [Motor NP FLA]
Related Parameter(s):
Set to the motor nameplate rated full load amps.
Values
Default:
Drive Rated Amps
Min/Max:
0.1/(Drive Rated Amps
×
2)
Display:
0.1 Amps