Programming and Parameters
3-27
Communications Group
C101 [Language]
Selects the language displayed by the integral LCD display and remote communications option.
Options
1
“English” (Default)
2
“Français”
3
“Español”
4
“Italiano”
5
“Deutsch”
6
“Reserved”
7
“Português”
8
“Reserved”
9
“Reserved”
10
“Nederlands”
C102 [Comm Format]
Related Parameter(s):
-
Selects the protocol data bits (8 data bits only), parity (None, Even, Odd), and stop bits (1 or 2) used
by the RS485 port on the drive.
Refer to
for details on using the drive communication features.
Important:
Power to drive must be cycled before any changes will affect drive operation.
Options
0
“RTU 8-N-1” (Default)
1
“RTU 8-E-1”
2
“RTU 8-O-1”
3
“RTU 8-N-2”
4
“RTU 8-E-2”
5
“RTU 8-O-2”
6
“MetaSys N2”
7
“P1 8-N-1”
Floor Level Network (FLN)
8
“P1 8-E-1”
Floor Level Network (FLN)
9
“P1 8-O-1”
Floor Level Network (FLN)
C103 [Comm Data Rate]
Related Parameter(s):
Sets the serial port rate for the RS485 (DSI) port.
Important:
Power to drive must be cycled before any changes will affect drive operation.
Options
0
“1200”
1
“2400”
2
“4800”
3
“9600” (Default)
4
“19.2K”
5
“38.4K”
Содержание PowerFlex400
Страница 1: ...Adjustable Frequency AC Drive for Fan Pump Applications FRN 4 xx User Manual www abpowerflex com...
Страница 42: ...1 32 Installation Wiring Notes...
Страница 52: ...2 10 Start Up Notes...
Страница 112: ...3 60 Programming and Parameters Notes...
Страница 128: ...A 8 Supplemental Drive Information Notes...
Страница 164: ...D 14 Application Notes Notes...
Страница 170: ...E 6 Modbus RTU Protocol Notes...
Страница 178: ...F 8 Metasys N2 Notes...
Страница 190: ...Index 4...
Страница 191: ......