Rockwell Automation Publication 750-IN020D-EN-P - May 2017
21
PowerFlex 755 IP00, NEMA/UL Open Type Drive
Figure 6 - Terminal Block for Enclosure Fans - TB2
TB2 Terminal Designations
ATTENTION:
To avoid an electric shock hazard when servicing the drive, a
means for Lockout/Tagout of an external 120/240V power source must be
provided. Locking and tagging the common bus precharge disconnect switch
alone does not provide sufficient protection when servicing the drive.
TB2
1
2
3
4
TB2
1
2
3
4
5
6
Flat
0.5 N•m (4.5 lb•in)
Flat
0.5 N•m (4.5 lb•in)
=
AC Input Drive
Common DC Input Drive
Drive
Terminal
Name
Description
Strip Length
AC Input
Drive
1
Shunt Trip Com.
Do Not Use
–
2
Shunt Trip N.O.
3
Fan
240V AC, 240 VA for enclosure fans
7.0 ±0.5 mm (0.28
±0.02 in.)
4
Fan
Common DC
Input Drive
1
120V UPS Control
Power Input
Do Not Use
–
2
3
120/240V Control
Power Input
Control Power (user supplied) - 120/
240V AC, 50/60 Hz, 8.3/4.2 A, 1 kVA
7.0 ±0.5 mm (0.28
±0.02 in.)
(1)
(1) See page
for control and I/O wire recommendations.
4
5
Fan
240V AC, 240 VA for enclosure fans
7.0 ±0.5 mm (0.28
±0.02 in.)
(2)
(2) See page
for wire recommendations.
6
Fan