Frame 3A and 3B Installation
3-37
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Figure 3.34 Frame 3B 700S Phase II Control Synchronization Cable Connection
Inverter-to-Converter DPI Communication Cable
To enable the Frame 3B Inverter and Converter Power Modules to
communicate with each other, you must connect one DPI port on the bottom
of the Converter to a DPI port on the bottom of the Inverter with a DPI
communication cable (see
DPI Connections for Frame
3A and 3B Drives
Drive Connection Points
The PowerFlex 700L provides a number of cable connection points as
shown in
. If an additional external HIM is
required for the application, the HIM can be connected to the DPI port on
the bottom of the Power Module. Only one additional external HIM device
may be connected. The use of two external HIM devices is not supported. If
multiple external HIM devices are required, then install a user-supplied
splitter cable or splitter box.
J9 Header for
Control Synchronization
Cable Connection
P6 Header for
Control Synchronization
Cable Connection
Active Converter Power Module
Inverter Power Module
Active Converter
Control Cassette
700S Phase II
Control Cassette
Control Synchronization Cable
(Factory-Provided)
24 VDC
DC POSITIVE
DC NEGATIVE
1 120 VAC
2 PRECHARGE COIL
6 INDUCTOR OVERTEMP
WIRE RANGE:
24-10 AWG
(0.2-4 MM)
4 CHARGE FEEDBACK
GATE ENABLE
STRIP LENGTH:
0.31 IN (8 MM)
TORQUE:
8 IN-LB
(0.9 N-M)
24 VDC
DC POSITIVE
DC NEGATIVE
1 120 VAC
2 PRECHARGE COIL
6 INDUCTOR OVERTEMP
WIRE RANGE:
24-10 AWG
(0.2-4 MM)
4 CHARGE FEEDBACK
GATE ENABLE
STRIP LENGTH:
0.31 IN (8 MM)
TORQUE:
8 IN-LB
(0.9 N-M)