Troubleshooting
PowerFlex 527 Drive Status Indicators
The fault status indicator is located between the LCD display and keypad. There
are also four status indicators located at the bottom right of the drive and can be
seen through the front cover of the control module.
NODE FLT 06 – LOST CTRL CONN
Lost Controller Connection Fault
Communication with the controller has been
lost.
•
Check Ethernet connection.
•
Check controller and Ethernet switch
operation.
NODE FLT 07 – CLOCK SYNC
Clock Sync Fault
Drive's local clock has lost synchronization
with controller's clock and was not able to
resynchronize within allotted time.
•
Check Ethernet connection.
•
Check controller and Ethernet switch
operation.
NODE FLT 09 – DUPLICATE IP ADDRESS
Duplicate IP Address Fault
Several consecutive updates from the
controller have been lost.
Select an IP address not already in use on
the network.
NODE FLT Fault Codes
Exception Code on Display
Exception Text
Problem
Possible Solutions
NODE ALARM Fault Codes
Exception Code on Display
Exception Text
Problem
Possible Solutions
NODE ALARM 01 – LATE CTRL UPDATE
Control Connection Update Alarm
Updates from the controller have been late.
•
Remove unnecessary network devices
from the motion network.
•
Change network topology so that fewer
devices share common paths.
•
Use high performance network
equipment.
•
Use shielded cables.
•
Separate signal wiring from power
wiring.
NODE ALARM 03 – CLOCK JITTER
Clock Jitter Alarm
The sync variance has exceeded the sync
threshold while the device is running in sync
mode.
•
Check the Ethernet connection.
•
Check controller and Ethernet switch
operation.
NODE ALARM 04 – CLOCK SKEW ALARM
Clock Skew Alarm
The controller time and the drive's system
time are not the same.
•
Check the Ethernet connection.
•
Check controller and Ethernet switch
operation.
NODE ALARM 05 – CLOCK SYNC ALARM
Clock Sync Alarm
Drive's local clock has lost synchronization
with controller's clock for a short time
during synchronous operation.
•
Check the Ethernet connection.
•
Check controller and Ethernet switch
operation.
Module status
Network status
Link A status (Ethernet port 1)
Link B status (Ethernet port 2)
Fault status
Содержание PowerFlex 527
Страница 1: ...PowerFlex 527 Adjustable Frequency AC Drive Catalog Number 25C User Manual Original Instructions...
Страница 4: ...4 Rockwell Automation Publication520 UM002B EN E December 2017 Summary of Changes Notes...
Страница 8: ...8 Rockwell Automation Publication 520 UM002B EN E December 2017 Table of Contents Notes...
Страница 102: ...102 Rockwell Automation Publication520 UM002B EN E December 2017 Chapter 5 Hardwired Control of Safe Torque Off Notes...
Страница 162: ...162 Rockwell Automation Publication520 UM002B EN E December 2017 Appendix B Accessories and Dimensions Notes...
Страница 173: ...Rockwell Automation Publication520 UM002B EN E December 2017 173 Notes...
Страница 174: ...174 Rockwell Automation Publication 520 UM002B EN E December 2017 Notes...
Страница 175: ......