B-4
Adapter Parameters
15
[Flt Cfg Logic]
Sets the Logic Command data that is sent to the
drive if any of the following is true:
•
Parameter 10 - [Comm Flt Action] is set to
Send Flt Cfg and communications are
disrupted.
•
Parameter 11 - [Idle Flt Action] is set to Send
Flt Cfg and the scanner is put into Program or
Test mode.
•
Parameter 34 - [Peer Flt Action] is set to Fault
Cfg and communications are disrupted.
The bit definitions will depend on the product to
which the adapter is connected.
Default:
0000 0000 0000 0000
Minimum:
0000 0000 0000 0000
Maximum:
1111 1111 1111 1111
Type:
Read/Write
Reset Required:
No
16
[Flt Cfg Ref]
Sets the Reference data that is sent to the drive if
any of the following is true:
•
Parameter 10 - [Comm Flt Action] is set to
Send Flt Cfg and communications are
disrupted.
•
Parameter 11 - [Idle Flt Action] is set to Send
Flt Cfg and the scanner is put into Program
mode.
•
Parameter 34 - [Peer Flt Action] is set to Send
Flt Cfg and communications are disrupted.
Default:
0
Minimum:
0
Maximum:
4294967295
Type:
Read/Write
Reset Required:
No
Important:
If the drive uses a 16-bit
Reference, the most significant word of this
value must be set to zero (0) or a fault will
occur.
17
18
19
20
21
22
23
24
[Flt Cfg A1]
[Flt Cfg A2]
[Flt Cfg B1]
[Flt Cfg B2]
[Flt Cfg C1]
[Flt Cfg C2]
[Flt Cfg D1]
[Flt Cfg D2]
Sets the data that is sent to the Datalink in the
drive if any of the following is true:
•
Parameter 11 - [Idle Flt Action] is set to Send
Flt Cfg and the scanner is put into Program
mode.
•
Parameter 10 - [Comm Flt Action] is set to
Send Flt Cfg and communications are
disrupted.
•
Parameter 34 - [Peer Flt Action] is set to Send
Flt Cfg and communications are disrupted.
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Minimum:
0
Maximum:
4294967295
Type:
Read/Write
Reset Required:
No
Important:
If the drive uses 16-bit
Datalinks, the most significant word of this
value must be set to zero (0) or a fault will
occur.
25
[M-S Input]
Master-Slave input data. This data is produced by
the scanner and consumed by the adapter.
Default:
xxx0 0001
Bit Values:
0 = I/O disabled
1 = I/O enabled
Type:
Read/Write
Reset Required:
Yes
Bit Definitions
0 = Cmd/Ref
1 = DL A Input
2 = DL B Input
3 = DL C Input
4 = DL D Input
5 = Not Used
6 = Not Used
7 = Not Used
Parameter
No. Name and Description
Details
Bit
Default
1
0
0
0
0
x x
x
0
1
2
3
4
5
7 6
Содержание PowerFlex 20-COMM-D
Страница 1: ...DeviceNet Adapter 20 COMM D FRN 1 xxx User Manual...
Страница 6: ...iv Table of Contents Notes...
Страница 72: ...6 14 Using Explicit Messaging Notes...
Страница 90: ...B 8 Adapter Parameters Notes...
Страница 122: ...C 32 DeviceNet Objects Notes...
Страница 132: ...E 8 Master Slave I O Configuration Notes...
Страница 148: ......