Adapter Parameters
B-3
11
[Idle Flt Action]
Sets the action that the adapter and drive take if
the adapter detects that scanner is idle because
the controller was switched to program mode. This
setting is effective only if I/O that controls the drive
is transmitted through the adapter.
Default:
0 = Fault
Values:
0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg
Type:
Read/Write
Reset Required:
No
12
[DN Active Cfg]
Source from which the adapter node address and
data rate are taken. This will either be switches or
parameters in EEPROM. It is determined by the
settings of the switches on the adapter.
Default:
1 = Switches
Values:
0 = EEPROM
1 = Switches
Type:
Read Only
13
[DPI I/O Config]
I/O that is transferred through the adapter.
Default:
xxx0 0001
Bit Values:
0 = I/O disabled
1 = I/O enabled
Type:
Read/Write
Reset Required:
Yes
Bit Definitions
0 = Cmd/Ref
1 = Datalink A
2 = Datalink B
3 = Datalink C
4 = Datalink D
5 = Not Used
6 = Not Used
7 = Not Used
14
[DPI I/O Active]
I/O that the adapter is actively transmitting. The
value of this parameter will usually be equal to the
value of Parameter 13 - DPI I/O Config.
Default:
xxx0 0001
Bit Values:
0 = I/O disabled
1 = I/O enabled
Type:
Read Only
Bit Definitions
0 = Cmd/Ref
1 = Datalink A
2 = Datalink B
3 = Datalink C
4 = Datalink D
5 = Not Used
6 = Not Used
7 = Not Used
Parameter
No. Name and Description
Details
!
ATTENTION:
Risk of injury or equipment damage exists.
Parameter 11 - [Idle Flt
Action]
lets you determine the action of the adapter and connected drive if the
scanner is idle. By default, this parameter faults the drive. You can set this
parameter so that the drive continues to run. Precautions should be taken to
ensure that the setting of this parameter does not create a hazard of injury or
equipment damage.
Bit
Default
1
0
0
0
0
x x
x
0
1
2
3
4
5
7 6
Bit
Default
1
0
0
0
0
x x
x
0
1
2
3
4
5
7 6
Содержание PowerFlex 20-COMM-D
Страница 1: ...DeviceNet Adapter 20 COMM D FRN 1 xxx User Manual...
Страница 6: ...iv Table of Contents Notes...
Страница 72: ...6 14 Using Explicit Messaging Notes...
Страница 90: ...B 8 Adapter Parameters Notes...
Страница 122: ...C 32 DeviceNet Objects Notes...
Страница 132: ...E 8 Master Slave I O Configuration Notes...
Страница 148: ......