4-6
Configuring the Scanner
Mapping the Input I/O
1.
In the Scanner Module dialog box, click the
Input
tab. (If necessary,
right-click the scanner in the configuration view (
) to
display this dialog box.)
Figure 4.5 Input Page on the Scanner Module Dialog Box
If you selected the
Automap on Add
), RSNetWorx has already mapped the I/O. If it is not mapped, click
Automap
to map it. If you need to change the mapping, click
Advanced
and change the settings. Click
Help
for assistance.
2.
In the Memory box, select a location in scanner memory.
In our example, we are using a 1747-SDN and selected Discrete.
3.
In the Start Word box, select the word in memory at which the data
should start. In our example, we selected 1. Logic Status and Speed
Feedback information will be found in I:1.1 and I:1.2, respectively.
Scanner
Memory Locations
1747-SDN
Discrete or M-File
1756-DNB
Assembly Data
1771-SDN
Block Xfer 62 – 57