C-18
DeviceNet Objects
Class Code
Instances
The number of instances depends on the number of parameters in the
device. The total number of parameters can be read in Instance 0,
Attribute 0.
Class Attributes
DPI Parameter Object
Hexadecimal Decimal
0x93
147
Number
Description
0
Class Attributes (Drive)
1
Drive Parameter 1 Attributes
2
Drive Parameter 2 Attributes
…
…
16384
Class Attributes (Adapter)
16385
Adapter Parameter 1 Attributes
…
…
Attribute
ID
Access
Rule
Name
Data Type
Description
0
Get
Number of
Instances
WORD
Number of parameters in the device
1
Get/Set Write Protect
Password
WORD
0 = Password disabled
n = Password
2
Set
NVS Command
Write
BYTE
0 = No Operation
1 = Store values in active memory to NVS
2 = Load values in NVS to active memory
3 = Load default values to active memory
3
Get
NVS Parameter
Value Checksum
WORD
Checksum of all parameter values in a
user set in NVS
4
Get
NVS Link Value
Checksum
WORD
Checksum of parameter links in a user set
in NVS
5
Get
First Accessible
Parameter
WORD
First parameter available if parameters
are protected by passwords. A “0”
indicates all parameters are protected.
7
Get
Class Revision
WORD
2 = DPI
8
Get
First Parameter
Processing Error
WORD
The first parameter that has been written
with a value outside of its range. A “0”
indicates no errors.
9
Set
Link Command
BYTE
0 = No Operation
1 = Clear All Parameter Links (This does
not clear links to function blocks.)
Содержание PowerFlex 20-COMM-D
Страница 1: ...DeviceNet Adapter 20 COMM D FRN 1 xxx User Manual...
Страница 6: ...iv Table of Contents Notes...
Страница 72: ...6 14 Using Explicit Messaging Notes...
Страница 90: ...B 8 Adapter Parameters Notes...
Страница 122: ...C 32 DeviceNet Objects Notes...
Страница 132: ...E 8 Master Slave I O Configuration Notes...
Страница 148: ......