PLC-5C Applications
5-5
When enabled, the Logic Command/Status word is always word 0 in the
I/O image. The
Logic Command
is a 16-bit word of control produced by
the scanner and consumed by the adapter. The
Logic Status
is a 16-bit
word of status produced by the adapter and consumed by the scanner.
This manual contains the bit definitions for compatible products
available at the time of publication in
. For other products, refer to their documentation.
The
Reference
(16 bits or 32 bits) is produced by the controller and
consumed by the adapter. The
Feedback
(16 bits or 32 bits) is produced
by the adapter and consumed by the controller. The size of the
Reference/Feedback is determined by the drive and displayed in
Parameter 07 - [Ref/Fdbk Size]
in the adapter.
A Datalink is a mechanism used by PowerFlex drives to transfer data to
and from the controller. Datalinks allow a parameter value to be changed
without using an Explicit Message. When enabled, each Datalink
consumes either two 16-bit or 32-bit words in both the input and output
image depending on its size. The size of Datalinks (16-bit words or
32-bit words) is determined by the drive and displayed in
Parameter 08
- [Datalink Size]
in the adapter.
Rules for Using Datalinks
•
Each set of Datalink parameters in a PowerFlex drive can be used by
only one adapter. If more than one adapter is connected to a single
drive, multiple adapters must not try to use the same Datalink.
•
Parameter settings in the drive determine the data passed through the
Datalink mechanism. Refer to the documentation for your drive.
•
When you use a Datalink to change a value, the value is not written
to the Non-Volatile Storage (NVS). The value is stored in volatile
memory and lost when the drive loses power.
Using Logic Command/Status
Using Reference/Feedback
Size
Valid Values
In I/O Image
Example
16-bit
-32768 to 32767
Word 1
32-bit
-2147483648 to 2147483647
Word 2 and Word 3
Using Datalinks
20COMM-UM003A-EN-P.book Page 5 Wednesday, November 7, 2001 3:46 PM
Содержание PowerFlex 20-comm-c FRN 1. Series
Страница 6: ...iv Table of Contents Notes 20COMM UM003A EN P book Page iv Wednesday November 7 2001 3 46 PM...
Страница 18: ...1 8 Getting Started 20COMM UM003A EN P book Page 8 Wednesday November 7 2001 3 46 PM...
Страница 34: ...3 10 Configuring the Adapter Notes 20COMM UM003A EN P book Page 10 Wednesday November 7 2001 3 46 PM...
Страница 74: ...5 20 PLC 5C Applications Notes 20COMM UM003A EN P book Page 20 Wednesday November 7 2001 3 46 PM...
Страница 98: ...6 24 ControlLogix Applications Notes 20COMM UM003A EN P book Page 24 Wednesday November 7 2001 3 46 PM...
Страница 114: ...B 6 Adapter Parameters Notes 20COMM UM003A EN P book Page 6 Wednesday November 7 2001 3 46 PM...
Страница 144: ...C 30 ControlNet Objects Notes 20COMM UM003A EN P book Page 30 Wednesday November 7 2001 3 46 PM...
Страница 152: ...Glossary 6 Notes 20COMM UM003A EN P book Page 6 Wednesday November 7 2001 3 46 PM...
Страница 154: ...20COMM UM003A EN P book Page 2 Wednesday November 7 2001 3 46 PM...